Plan Review Details - Permit 19110715
Plan Review Stops For Permit 19110715
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-02-05 Cont ID  
Sent By jwitmer Date 2020-02-05 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2020-02-05 Time 10:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By jleahy Date 2020-02-05 Time 11:52 Rev Time 0.00
Received By jleahy Date 2020-02-05 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-01 Cont ID  
Sent By jleahy Date 2020-02-01 Time 10:52 Rev Time 0.00
Received By jleahy Date 2020-02-01 Time 10:52 Sent To  
Notes
2020-02-01 11:07:24JAKE LEAHY ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 SECONDARY CONDUCTORS OF THE TRANSFORMER ARE THEY 10' OR
 25' PER 240.21? IF MORE THAN 10 OR 25' THEY WILL NEED A
 DISCONNECT AT THE TRANSFORMER LOCATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-27 Cont ID  
Sent By pleduc Date 2020-01-27 Time   Rev Time 0.00
Received By pleduc Date 2020-01-27 Time 13:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-02-05 Time   Rev Time 0.00
Received By cpuell Date 2020-01-24 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-02-05 Cont ID  
Sent By ccole Date 2020-02-05 Time 15:34 Rev Time 0.00
Received By ccole Date 2020-02-05 Time 15:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-05 Cont ID  
Sent By rmcdouga Date 2020-02-05 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2020-02-05 Time 11:16 Sent To  
Notes
***NONE***