Plan Review Details - Permit 19110612
Plan Review Stops For Permit 19110612
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-06 Cont ID  
Sent By lcrespo Date 2020-01-06 Time 15:18 Rev Time 0.00
Received By lcrespo Date 2020-01-06 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-14 Cont ID  
Sent By tklarge Date 2019-11-14 Time 06:17 Rev Time 0.00
Received By tklarge Date 2019-11-14 Time 05:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-06 Cont ID  
Sent By lcrespo Date 2020-01-06 Time 15:18 Rev Time 0.00
Received By lcrespo Date 2020-01-06 Time 15:18 Sent To  
Notes
2020-01-06 15:20:0801/06/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By tklarge Date 2019-11-14 Time 06:17 Rev Time 0.00
Received By tklarge Date 2019-11-14 Time 05:58 Sent To  
Notes
2019-11-14 06:14:121) A PLUMBING CONTRACTOR CANNOT INSTALL A BACKFLOW
 DEVICE ON A FIRE PROTECTION SYSTEM UNLESS THE
 CONTRACTOR IS LICENSED AS A FIRE PROTECTION CONTRACTOR
 I, II OR V IN ACCORDANCE WITH FL. STATUTE 633.102,
 633.336. IF YOU ARE LICENSED AS ONE OF THE
 AFOREMENTIONED CONTRACTOR TYPES, SUBMIT A COPY OF YOUR
 CURRENT FIRE PROTECTION CONTRACTOR LICENSENE.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE BACKFLOW DEVICE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) ALL BACKFLOW DEVICES MUST BE LEAD FREE AND BE ON THE
 APPROVED LIST OF DEVICES OF THE UNIVERSITY OF SOUTHERN
 CALIFORNIA FOUNDATION FOR CROSS-CONNECTION CONTROL AND
 HYDRAULIC RESEARCH PER THE CITY OF WEST PALM BEACH
 CROSS CONNECTION CONTROL MANUAL AS ADOPTED BY
 ORDINANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  