Plan Review Details - Permit 19110398
Plan Review Stops For Permit 19110398
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By pvalenti Date 2019-12-23 Time 13:46 Rev Time 0.00
Received By pvalenti Date 2019-12-23 Time 10:02 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-25 Cont ID  
Sent By jwitmer Date 2019-11-25 Time 10:02 Rev Time 0.00
Received By jwitmer Date 2019-11-25 Time 05:43 Sent To  
Notes
2019-11-25 10:02:05COMMERCIAL. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT
 FROM THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By pvalenti Date 2019-12-23 Time 09:46 Rev Time 0.00
Received By pvalenti Date 2019-12-23 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-25 Cont ID  
Sent By jwitmer Date 2019-11-25 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2019-11-25 Time 05:43 Sent To  
Notes
2019-11-25 10:01:112017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110398
 ADD: 400 N. CONGRESS AVE. SUITE: 140
 CONT: ROBB CONSTRUCTION
 TEL: 561-222-7908
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 25/ 2019
 ACTION: DENIED
  
 1) SHEET A.1 SHOWS 3 NEW CHECK-IN STATIONS. SHEET A3.1
 INDICATES THE HEIGHT OF THE CHECK-IN COUNTER AT 3 FEET
 2 INCHES.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY
 CODE SECTIONS:
 1A) CHECK WRITING SURFACES. 904.3.3. CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
  
 1B) WORK SURFACES. 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1C) CLEAR FLOOR SPACE, 305.5 POSITION. UNLESS OTHERWISE
 SPECIFIED, CLEAR FLOOR OR GROUND SPACE SHALL BE
 POSITIONED FOR EITHER FORWARD OR PARALLEL APPROACH TO
 AN ELEMENT. SEE FIGURE 305.5.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2019-12-20 Cont ID  
Sent By jpearson Date 2019-12-20 Time 10:10 Rev Time 0.00
Received By jpearson Date 2019-12-20 Time 10:10 Sent To B
Notes
2019-12-20 10:10:36PER ARCHITECT LETTER, NO ELECTRICAL WORK WILL BE DONE
 ON THIS PROJECT. A SEPARATE PERMIT AND PLAN SUBMISSION
 WILL BE REQUIRED IF THIS CHANGES. WPB FBC 105.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-25 Cont ID  
Sent By jpearson Date 2019-11-25 Time 15:46 Rev Time 0.00
Received By jpearson Date 2019-11-25 Time 13:28 Sent To  
Notes
2019-11-25 15:46:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED(AND
 SEALED WHERE APPLICABLE) BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-15 Cont ID  
Sent By pleduc Date 2019-11-15 Time   Rev Time 0.00
Received By pleduc Date 2019-11-15 Time 14:40 Sent To  
Notes
2019-11-15 14:41:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-23 Cont ID  
Sent By pvalenti Date 2019-12-23 Time 13:47 Rev Time 0.00
Received By pvalenti Date 2019-12-16 Time 15:18 Sent To  
Notes
2019-12-23 07:24:19TO PV DESK
  
2019-12-17 15:18:17RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-11-25 Time   Rev Time 0.00
Received By cpuell Date 2019-11-07 Time 10:43 Sent To  
Notes
2019-11-09 10:44:19B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-11-25 Cont ID  
Sent By jwitmer Date 2019-11-25 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2019-11-25 Time 05:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-19 Cont ID  
Sent By llouie Date 2019-11-19 Time   Rev Time  
Received By llouie Date 2019-11-19 Time   Sent To  
Notes
2019-11-19 09:32:25- INTERIOR MODIFICATIONS TO EXISTING SUITE ONLY (NO
 CHANGE IN USE).
  
 - DOES NOT TRIGGER 50% LANDSCAPE REQUIREMENT.
  
  


Account Summary | Usage Policy | Privacy Policy