Plan Review Details - Permit 19110320
Plan Review Stops For Permit 19110320
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-01-02 Cont ID  
Sent By rmcdouga Date 2020-01-02 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2020-01-02 Time 13:21 Sent To  
Notes
2020-01-02 13:24:02LETTER FROM LEGACY BROTHERS, LLC ADDRESSING ASBESTOS
 WAS SUBMITTED.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By jwitmer Date 2019-11-19 Time 12:56 Rev Time 0.00
Received By jwitmer Date 2019-11-19 Time 07:00 Sent To  
Notes
2019-11-19 12:56:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110320
 ADD: 534 DATURA ST.
 CONT: LEGACY BROTHERS, LLC
 TEL: 912-484-0721
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 19/2019
 ACTION: DENIED
  
 1) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-07-20 Cont ID  
Sent By rmcdouga Date 2020-07-20 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2020-07-20 Time 11:13 Sent To  
Notes
2020-07-20 11:15:27VALUATION HAS BEEN ADJUSTED TO $68,276.00 BASED ON THE
 SUBMITTED DOCUMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-02-10 Cont ID  
Sent By rmcdouga Date 2020-02-10 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2020-02-10 Time 08:14 Sent To  
Notes
2020-02-10 09:43:38PLAN REVIEW AUDIT FOR PERMIT #19110320
  
 ROBERT MCDOUGAL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6714
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED.
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) NOT COMPLIED. THE VALUE OF SEVERAL ITEMS HAVE BEEN
 EXCLUDED FROM THE COST BREAKDOWN THAT WAS SUBMITTED.
 FOR PERMITTING PURPOSES THE VALUE OF ALL LABOR AND
 MATERIALS REQUIRED TO COMPLETE THE PROJECT ARE REQUIRED
 TO BE INCLUDED IN THE COST.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 THE DECLARED VALUE FOR THIS WORK IS LOW. PROVIDE A
 DETAILED COST BREAKDOWN FOR THE WORK. FBC 109.3
  
 7) COMPLIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-02 Cont ID  
Sent By rmcdouga Date 2020-01-02 Time 17:51 Rev Time 0.00
Received By rmcdouga Date 2020-01-02 Time 15:44 Sent To P
Notes
2020-01-02 17:51:34PLAN REVIEW AUDIT FOR PERMIT #19110320
  
 ROBERT MCDOUGAL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6714
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 THIS REVIEW AUDIT IS TO PROVIDE SOME CLARIFICATION OF
 THE REVIEW THAT WAS DONE BY JIM WITMER ON 11/19/2019.
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) NOT COMPLIED. THERE ARE STILL REFERENCES TO THE 2010
 AND 2014 EDITIONS OF THE FBC, AS WELL AS, SECTIONS FROM
 THE FBC RESIDENTIAL WHICH DO NOT APPLY TO THIS PROJECT.
 THE RESIDENTIAL CODE ONLY APPLIES TO DETACHED ONE AND
 TWO FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE
 STORIES ABOVE GRADE PLANE IN HEIGHT PER FBC 101.2. ON
 SHEET A-O NOTES 1,3,5 AND 6 REFERENCE THE WRONG EDITION
 OF THE CODE OR SPECIFY SECTION FROM THE
 FBC-RESIDENTIAL. PLEASE CORRECT. THIS PROJECT IS UNDER
 THE 2017 FBC EXISTING BUILDING.
  
 6) NOT COMPLIED. THE VALUE OF SEVERAL ITEMS HAVE BEEN
 EXCLUDED FROM THE COST BREAKDOWN THAT WAS SUBMITTED.
 FOR PERMITTING PURPOSES THE VALUE OF ALL LABOR AND
 MATERIALS REQUIRED TO COMPLETE THE PROJECT ARE REQUIRED
 TO BE INCLUDED IN THE COST.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 THE DECLARED VALUE FOR THIS WORK IS LOW. PROVIDE A
 DETAILED COST BREAKDOWN FOR THE WORK. FBC 109.3
  
 7) ON SHEET A-2 THE PROPOSED 2ND FLOOR PLAN SHOWS THAT
 THE DOORS AND WALLS SEPARATING THE ELEVATOR LOBBY FROM
 THE EAST AND WEST CORRIDORS HAVE BEEN REMOVED. THIS
 WILL NO LONGER BE AN ELEVATOR LOBBY IF IT IS OPEN TO
 THE CORRIDORS. THE DEMOLITION PLAN SHEET AND OTHER
 SHEETS INDICATE THAT THE DOORS ARE BEING REPLACED.
 PLEASE CLARIFY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-03 Cont ID  
Sent By shill Date 2019-12-03 Time 07:57 Rev Time 0.00
Received By rmcdouga Date 2019-12-03 Time 07:56 Sent To  
Notes
2019-12-03 07:57:51PLAN REVIEW AUDIT FOR PERMIT #19110320
  
 ROBERT MCDOUGAL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6714
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 THIS REVIEW AUDIT IS TO PROVIDE SOME CLARIFICATION OF
 THE REVIEW THAT WAS DONE BY JIM WITMER ON 11/19/2019.
 1) AS JIM NOTED IN HIS REVIEW THIS CAN NOT BE AN R-4
 OCCUPANCY BECAUSE MORE THAN 16 PERSONS RESIDE THERE ON
 A 24 HOUR BASIS. HOWEVER, THERE IS NOT ENOUGH
 INFORMATION PROVIDED TO DETERMINE IF IT IS AN
 INSTITUTIONAL GROUP I-1 OR I-2. THE DESIGN PROFESSIONAL
 WILL NEED TO DISCUSS WITH THE OWNERS TO MAKE THAT
 DETERMINATION. THE OCCUPANCY TYPE IS BASED ON WHETHER
 OR NOT THE OCCUPANTS ARE RECEIVING MEDICAL CARE ON A
 24-HOUR BASIS AND IF THEY ARE CAPABLE OF
 SELF-PRESERVATION OR NOT. THE DESIGN PROFESSIONAL WILL
 ALSO NEED TO SPECIFY THE CONDITION AS 1 OR 2. SEE FBC
 SECTIONS 308.3 THRU 308.4.1.2
  
 2) SPECIFY THE CURRENT USE OF THE FACILITY AS LICENSED
 BY THE STATE AND INDICATE IF THE USE OF THE FACILITY IS
 GOING TO CHANGE. FBC 107.2.1
  
 3) THE DESIGN PROFESSIONAL WILL NEED TO SPECIFY THE
 CONSTRUCTION TYPE AS V-A OR V-B OR OTHER. FBC TABLE 601
  
 4)THE DESIGN PROFESSIONAL WILL NEED TO SPECIFY THE
 LEVEL OF FIRE PROTECTION FOR THE BUILDING (ALARMS,
 SPRINKLER SYSTEM, ETC.)
  
 5) ON SHEET A-O NOTES 1,3,5 AND 6 REFERENCE THE WRONG
 EDITION OF THE CODE OR SPECIFY SECTION FROM THE
 FBC-RESIDENTIAL. PLEASE CORRECT. THIS PROJECT IS UNDER
 THE 2017 FBC EXISTING BUILDING.
  
 6) THE DECLARED VALUE FOR THIS WORK IS LOW. PROVIDE A
 DETAILED COST BREAKDOWN FOR THE WORK. FBC 109.3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By jwitmer Date 2019-11-19 Time 15:04 Rev Time 0.00
Received By jwitmer Date 2019-11-19 Time 07:00 Sent To  
Notes
2019-11-19 15:04:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110320
 ADD: 534 DATURA ST.
 CONT: LEGACY BROTHERS, LLC
 TEL: 912-484-0721
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 19/2019
 ACTION: DENIED
  
 1) WITHIN THIS PERMIT PACKAGE THERE ARE FORMS FOR
 PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT.
 PLEASE BE AWARE THE BUILDING DEPARTMENT HAS NOT
 RECEIVED NOTICE TO THE BUILDING OFFICIAL FROM THE OWNER
 OR CONTRACTOR REQUESTING THE USE OF A PRIVATE PROVIDER
 FOR EITHER PLAN REVIEW OR INSPECTIONS. PROPER
 NOTIFICATION MUST BE PROVIDED TO THE CITY OF WEST PALM
 BEACH IN ACCORDANCE WITH SECTION 553.791 (2), (3) (4)
 AND (5).
  
 2) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 3) SHEET A-0 THE COVERSHEET:
 3A) THE COVERSHEET UNDER THE HEADING OF PROJECT INFO,
 INDICATES THE OCCUPANCY TO BE AN R-4 ASSISTED LIVING
 FACILITY. THERE IS ALSO A LETTER WITHIN THE PERMIT
 PACKAGE FROM ARCHITECTURAL CONSULTING SERVICES STATING
 THE PROJECT DESCRIPTION IS AN EXISTING 45,000 SQUARE
 FOOT, FOUR STORY BUILDING BUILT IN 1926. THE USE IS AN
 ASSISTED LIVING FACILITY WITH APPROXIMATELY 200 BEDS.
 PLEASE REVIEW THE 2017 FBC-B SECTION 310.6 RESIDENTIAL
 GROUP R-4. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL
 INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR
 MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING
 STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED
 RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE.
 THE CORRECT OCCUPANCY TYPE IS: I-2 / CONDITION 2. 308.4
 INSTITUTIONAL GROUP I-2. INSTITUTIONAL GROUP I-2
 OCCUPANCY SHALL INCLUDE BUILDINGS AND STRUCTURES USED
 FOR MEDICAL CARE ON A 24-HOUR BASIS FOR MORE THAN FIVE
 PERSONS WHO ARE INCAPABLE OF SELF-PRESERVATION. THIS
 GROUP SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
 NURSING HOMES
 PSYCHIATRIC HOSPITALS
 FOSTER CARE FACILITIES
 DETOXIFICATION FACILITIES
 HOSPITALS
  
 308.4.1.2 CONDITION 2. THIS OCCUPANCY CONDITION SHALL
 INCLUDE FACILITIES THAT PROVIDE NURSING AND MEDICAL
 CARE AND COULD PROVIDE EMERGENCY CARE, SURGERY,
 OBSTETRICS OR IN-PATIENT STABILIZATION UNITS FOR
 PSYCHIATRIC OR DETOXIFICATION, INCLUDING BUT NOT
 LIMITED TO HOSPITALS.
  
 3B) THE COVERSHEET UNDER THE HEADING OF PROJECT INFO,
 ALSO INDICATES THE CONSTRUCTION TYPE AS TYPE: V. THE
 PLAN DOES NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLERED AND WHAT TYPE? PLEASE REVIEW THE 2017 FBC-B
 TABLE 504.4 LIST THE MINIMUM CONSTRUCTION TYPE AS TYPE
 I-B NON-SPRINKLERED BUILDING FOR A 4 STORY BUILDING.
 FOOTNOTE (D) THE NS VALUE IS ONLY FOR USE IN EVALUATION
 OF EXISTING BUILDING HEIGHT IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, EXISTING BUILDING.
 FOOTNOTE (F) NEW AND EXISTING GROUP I-2 OCCUPANCIES ARE
 REQUIRED TO BE PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 903.2.6 AND THE
 FLORIDA FIRE PREVENTION CODE. WHEN THE BUILDING IS FIRE
 SPRINKLERED THEY GIVE YOU THE EXTRA STORY IN HEIGHT TO
 A 5 STORY / I-2 OCCUPANCY GROUP.
  
 3C) THE COVERSHEET UNDER THE HEADING OF PROJECT INFO
 LIST THE 2017 EXISTING BUILDING CODE AND A LEVEL II
 ALTERATION. PLEASE REVIEW IN THE 2017 FBC-B SECTION
 450.1.3 THE FLORIDA BUILDING CODE, EXISTING BUILDING,
 SECTION 101.2, SCOPE EXEMPTS STATE LICENSED FACILITIES
 SUCH AS NURSING HOMES FROM COMPLIANCE WITH THAT CODE.
 ANY REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF AN EXISTING STATE LICENSED NURSING
 HOME SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 THIS CODE AND THIS SECTION. WHICH MEANS WE ONLY USE THE
 2017 FBC-B AS FOR NEW CONSTRUCTION.
  
 PLEASE SEE OTHER CODES AND AGENCY REQUIREMENTS THAT
 WILL NEED TO BE ADDRESSED.
  
  
 3D) 2017 FBC-B 450.1.4 FOR PROJECT SUBMISSION AND FEE
 REQUIREMENTS, AND OTHER ADMINISTRATIVE, LICENSURE, AND
 PROGRAMMATIC PROVISIONS FOR NURSING HOMES, SEE AGENCY
 FOR HEALTH CARE ADMINISTRATION (AHCA) CHAPTER 59A-4
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 400 PART II,
 FLORIDA STATUTES.
  
 3E) 2017 FBC-B 450.1.5 FOR STATE LICENSURE PURPOSES,
 THESE CODES AND STANDARDS SHALL BE APPLICABLE TO THE
 PROJECT ON THE EFFECTIVE DATE OF THIS CODE AT THE TIME
 OF STAGE II PRELIMINARY PLAN APPROVAL BY THE AGENCY FOR
 HEALTH CARE ADMINISTRATION (THE AGENCY) AS DESCRIBED IN
 CHAPTER 59A-4 FLORIDA ADMINISTRATIVE CODE OR AT THE
 FIRST STAGE III CONSTRUCTION DOCUMENT REVIEW IF THERE
 HAS BEEN NO PREVIOUS STAGE II PRELIMINARY PLAN APPROVAL
 FOR THAT PROJECT.
  
 3F) 2017 FBC-B 450.2 ADDITIONAL CODES AND STANDARDS FOR
 THE DESIGN AND CONSTRUCTION OF NURSING HOMES.
 IN ADDITION TO THE MINIMUM DESIGN AND CONSTRUCTION
 STANDARDS REQUIRED BY SECTION 450 OF THIS CODE, CHAPTER
 59A-4, MINIMUM STANDARDS FOR NURSING HOMES, FLORIDA
 ADMINISTRATIVE CODE OR BY CHAPTER 400 PART II, FLORIDA
 STATUTES, THE FOLLOWING CODES AND STANDARDS SHALL ALSO
 BE MET ON THE EFFECTIVE DATE OF THIS CODE AS DESCRIBED
 IN SECTION 450.1.5 OF THIS CODE.
  
 3G) 2017 FBC-B 450.2.1. THE FIRE CODES DESCRIBED IN
 CHAPTER 69A-53, UNIFORM FIRE SAFETY STANDARDS FOR
 HOSPITALS AND NURSING HOMES, FLORIDA ADMINISTRATIVE
 CODE.
  
  
  
 3H) 450.2.2 THE GUIDELINES FOR DESIGN AND CONSTRUCTION
 OF RESIDENTIAL HEALTH, CARE, AND SUPPORT FACILITIES
 (THE GUIDELINES), INCLUDING CHAPTER 3.2 SPECIFIC
 REQUIREMENTS FOR NURSING HOMES AS REFERENCED IN CHAPTER
 35 OF THIS CODE.
  
 3I) 2017 FBC-B 450.3 ADDITIONAL PHYSICAL PLANT
 REQUIREMENTS FOR NURSING HOMES. IN ADDITION TO THE
 CODES AND STANDARDS REFERENCED IN SECTION 450.2 THE
 FOLLOWING MINIMUM STANDARDS OF CONSTRUCTION AND
 SPECIFIED MINIMUM ESSENTIAL FACILITIES SHALL APPLY TO
 ALL NEW NURSING HOMES, AND ALL ADDITIONS, ALTERATIONS
 OR RENOVATIONS TO AN EXISTING LICENSED NURSING HOME, AS
 DESCRIBED IN SECTION 450.1 AND LISTED IN THIS SECTION.
  
 4) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:40 Rev Time 0.00
Received By jleahy Date 2020-07-30 Time 12:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-02-07 Cont ID  
Sent By jpearson Date 2020-02-07 Time 15:14 Rev Time 0.00
Received By jpearson Date 2020-02-07 Time 10:29 Sent To  
Notes
2020-02-07 14:51:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 IT SEEMS THERE WAS NO RESPONSE PROVIDED FROM THE LAST
 REVIEW. PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. BASED ON RECORDS SEARCH, IT APPEARS A GENERATOR
 PERMIT FOR A PERMANENTLY INSTALLED GENERATOR THAT IS
 MAINTAINED AT THE FACILITY IN COMPLIANCE WITH THE
 FLORIDA ADMINISTRATIVE CODE HAS NOT BEEN OBTAINED FOR
 THIS SITE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS.
 FAC 59A-36.025(1)(A)
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, ALTERNATE POWER SOURCES, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO ANY SUB-PANEL(S) AND/OR TRANSFER SWICHES.
 SHOW GEC SIZE AND SYSTEM. NEC 215.5, 230, 250.50,
 250.94, 408.30
 4. PROVIDE LOAD CALCULATION FOR ITEMS THAT ARE FED FROM
 THE GENERATOR. NEC 220, 701.4
 5. THE GENERATOR IDENTIFIED IN THE EMERGENCY
 ENVIRONMENTAL CONTROL PLAN AND IN THE GENERATOR
 INFORMATION SHEET IS DIFFERENT THAN WHAT IS SPECIFIED
 IN THE SUPPORTING DOCUMENTATION UNDER LOSS OF
 ELECTRICAL, FACILITY GENERATOR. WHICH IS IT? 177 KW OR
 60 KW? PROVIDE CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-01-06 Cont ID  
Sent By jpearson Date 2019-12-22 Time 11:57 Rev Time 0.00
Received By jpearson Date 2019-12-22 Time 11:57 Sent To  
Notes
2020-01-06 13:59:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
  
 NEW COMMENTS:
  
 2. BASED ON RECORDS SEARCH, IT APPEARS A GENERATOR
 PERMIT FOR A PERMANENTLY INSTALLED GENERATOR THAT IS
 MAINTAINED AT THE FACILITY IN COMPLIANCE WITH THE
 FLORIDA ADMINISTRATIVE CODE HAS NOT BEEN OBTAINED FOR
 THIS SITE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS.
 FAC 59A-36.025(1)(A)
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, ALTERNATE POWER SOURCES, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO ANY SUB-PANEL(S) AND/OR TRANSFER SWICHES.
 SHOW GEC SIZE AND SYSTEM. NEC 215.5, 230, 250.50,
 250.94, 408.30
 4. PROVIDE LOAD CALCULATION FOR ITEMS THAT ARE FED FROM
 THE GENERATOR. NEC 220, 701.4
 5. THE GENERATOR IDENTIFIED IN THE EMERGENCY
 ENVIRONMENTAL CONTROL PLAN AND IN THE GENERATOR
 INFORMATION SHEET IS DIFFERENT THAN WHAT IS SPECIFIED
 IN THE SUPPORTING DOCUMENTATION UNDER LOSS OF
 ELECTRICAL, FACILITY GENERATOR. WHICH IS IT? 177 KW OR
 60 KW? PROVIDE CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-03 Cont ID  
Sent By jpearson Date 2019-12-03 Time 07:26 Rev Time 0.00
Received By jpearson Date 2019-12-03 Time 07:26 Sent To  
Notes
2019-12-03 07:25:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULES INDICATE THAT THE SERVICE IS 120/240
 VOLT THREE PHASE, WHICH WOULD HAVE A HIGH LEG. BUT, THE
 LOAD CALCULATION USES 208 VOLT TIMES 1.73 FOR THE
 CALCULATION, INDICATING THAT THE SERVICE IS 120/208
 VOLT THREE PHASE. PROVIDE CLARIFICATION AND/OR
 CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 110.3,
 110.15
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-02-12 Cont ID  
Sent By pleduc Date 2020-02-12 Time   Rev Time 0.00
Received By pleduc Date 2020-02-12 Time 10:10 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-12-31 Cont ID  
Sent By pleduc Date 2019-12-31 Time   Rev Time 0.00
Received By pleduc Date 2019-12-31 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By pleduc Date 2019-11-15 Time   Rev Time 0.00
Received By pleduc Date 2019-11-15 Time 14:08 Sent To  
Notes
2019-11-15 14:22:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A O - THERE IS AN INDICATION OF EXISTING FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS REMAINING
 ACTIVE....HOWEVER, THERE ARE NO INDICATIONS OF ALL NEW
 SPRINKLER AND ALARM WORK BEING DONE UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS AND BY CERTIFIED CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE WITH THE ABOVE.
  
  
 2) SHEET A 4 & A 5 - THERE ARE INDICATIONS OF NEW
 CEILING GRID SYSTEMS.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS AND BY CERTIFIED CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE WITH THE ABOVE.
  
  
  
 3) SHEETS ELECTRICAL - THE NEWLY CREATED/REMODELED
 ROOMS REQUIRE CODE COMPLIANT FA NOTIFICATIONS.
  
 ANY AND ALL WORK ON THE FIRE ALARM, INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY
 CERTIFIED CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE WITH THE ABOVE.
  
  
  
 4) SHEETS ELECTRICAL - THE NEWLY CREATED/REMODELED
 ROOMS REQUIRE CODE COMPLIANT SMOKE ALARMS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT AND COMPLIANCE WITH THE ABOVE OR
 JUSTIFY WITH NARRATIVE AND SPECIFIC CODES REFERNECES.
  
  
  
  
 5) THERE IS NO INDICATION OF A LIFE SAFETY SHEETS
 SHOWING THE NEW OCCUPANCY LOAD COUNTS OF EACH
 FLOOR/ROOM.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE LIFE SAFETY
 DETAILS AND OCCUPANCY LOADS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-08-18 Cont ID  
Sent By shill Date 2020-08-18 Time 13:07 Rev Time 0.00
Received By shill Date 2020-08-04 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:41 Rev Time 0.00
Received By jleahy Date 2020-07-16 Time 09:29 Sent To  
Notes
2020-07-20 09:18:54CONVERTED TO DIGITAL.
 DRAWINGS WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE IN
 CITY'S FILE. JG
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-27 Cont ID  
Sent By shill Date 2020-02-13 Time 09:11 Rev Time 0.00
Received By shill Date 2020-02-04 Time 14:02 Sent To  
Notes
2020-02-05 14:03:00B16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 10:32 Rev Time 0.00
Received By gjohnson Date 2019-12-17 Time 14:27 Sent To  
Notes
2019-12-18 14:27:27B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-03 Cont ID  
Sent By gjohnson Date 2019-12-03 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2019-11-06 Time 16:12 Sent To  
Notes
2019-11-06 16:12:43B12

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-07-23 Cont ID  
Sent By medwards Date 2020-07-23 Time 15:49 Rev Time 0.00
Received By medwards Date 2020-07-23 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-07-22 Cont ID  
Sent By medwards Date 2020-07-22 Time 10:34 Rev Time 0.00
Received By medwards Date 2020-07-22 Time 09:41 Sent To  
Notes
2020-07-22 10:34:06UNDER THE MECHANICAL RESPONSES IT IS MENTIONED THAT
 THERE IS AN ATTACHED LETTER OF ATTESTATION FROM ROBERT
 SHUMATE, A LICENSED ELECTRICAL CONTRACTOR. I DO NOT SEE
 THIS LETTER IN THE DOCUMENTS OF THIS CYCLE OF REVIEWS.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-02-10 Cont ID  
Sent By ccole Date 2020-02-10 Time 11:07 Rev Time 0.00
Received By ccole Date 2020-02-10 Time 11:02 Sent To  
Notes
2020-02-10 11:28:283RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19110320
 2/10/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) NO ADDITIONAL INFORMATION HAS BEEN PROVIDED ON THE
 PLANS TO VERIFY THAT THE FACILITY IS EQUIPPED TO INSURE
 AMBIENT AIR TEMPERTURES FOR RESIDENTS WILL BE
 MAINTAINED AT OR BELOW 81 DEGREES FAHRENHEIT FOR A
 MINIMUM OF 96 HOURS IN THE EVENT OF THE LOSS OF PRIMARY
 ELECTRICAL POWER- SECTION 59A-.025 (1)(A) FAC. PLEASE
 NOTE THAT NEW THROUGH-THE-WALL AC SYSTEMS FOR RESIDENT
 ROOMS ARE SHOWN ON THE PLANS HOWEVER IT IS NOT KNOW IF
 THESE SYSTEMS ARE CONNECTED TO THE EMERGENCY POWER
 SOURCE. SECONDLY THE EMERGENCY CONTROL PLAN SUBMITTAL
 TO PALM BEACH INDICATES THAT 160 BEDS IN THE COMMON
 AREA(S) WILL BE PROVIDED WITH THE REQUIRED COOLING
 UNDER EMERGENCY POWER. PLEASE SHOW THESE COMMON
 AREA(S)AND THEIR RESPECTIVE AC SYSTEMS ON THE PLANS.
  
 2) SHEETS M1 & M2: PROVIDE CONDESNATE DISPOSAL PLANS
 FOR THE NEW THOUGH-THE-WALL AC SYSTEMS. SHOW PIPING
 RUNS AND DISCHARGE LOCATIONS- SECTION 307.2.1 FBC M
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-12-27 Cont ID  
Sent By ccole Date 2019-12-27 Time 14:02 Rev Time 0.00
Received By ccole Date 2019-12-27 Time 11:24 Sent To  
Notes
2019-12-27 14:33:072ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19110320
 12/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE NEW DOCUMENTS SUBMITTED- EMERGENCY PLAN APPROVAL
 LETTER FROM THE PB DEPT. OF PUBLIC SAFETY DIVISION OF
 EMERGENCY MANAGEMENT, AND THE AHCA SAMPLE FORMAT FOR
 PLAN SUBMISSION- APPEAR TO INDICATE THAT A NEW
 EMERGENCY GENERATOR IS TO BE INSTALLED AT THE FACILITY.
 PLEASE ACKNOWLEDGE. WEST PALM BEACH BUILDING DEPARTMENT
 PERMIT RECORDS DO NOT INDICATE THAT AN EMERGENCY
 GENERATOR PERMIT WAS EVER ISSUED FOR THE FACILITY.
 FINAL APPROVAL OF THE MECHANICAL COOLING AND HEATING
 SYSTEM INSTALLATIONS AT THE FACILITY UNDER THIS PERMIT
 IS ON HOLD PENDING CLARIFICATION OF EMERGENCY GENERATOR
 INSTALLATION. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By ccole Date 2019-11-21 Time 16:41 Rev Time 0.00
Received By ccole Date 2019-11-21 Time 16:41 Sent To  
Notes
2020-02-07 12:53:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110320
 11/21/19
  
 CODE IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M - FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC - FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG - FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX - FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS - FLORIDA STATUTES
 FAC - FLORID ADMINISTRATIVE CODE
 WPB - WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1. PLEASE REFERE TO FLORIDA ADMINISTRATIVE CODE SECTION
 59A-36.025 EMERGENCY ENVIRONMENTAL CONTROL FOR ASSISTED
 LIVING FACILITIES. A DETAILED EMERGENCY ENVIRONMENTAL
 CONTROL PLAN IS REQUIRED. I HAVE COPIED ITEM (1) AND
 (1) (A) OF THE SECTION BELOW. COMPLIANCE WITH ALL ITEMS
 LISTED UNDER THE SECTION IS REQUIRED.
 (1) DETAILED EMERGENCY ENVIRONMENTAL CONTROL PLAN. EACH
 ASSISTED LIVING FACILITY SHALL PREPARE A DETAILED PLAN
 ("PLAN") TO SERVE AS A SUPPLEMENT TO ITS COMPREHENSIVE
 EMERGENCY MANAGEMENT PLAN, TO ADDRESS EMERGENCY
 ENVIRONMENTAL CONTROL IN THE EVENT OF THE LOSS OF
 PRIMARY ELECTRICAL POWER IN THAT ASSISTED LIVING
 FACILITY WHICH INCLUDES THE FOLLOWING INFORMATION:
 (A) THE ACQUISITION OF A SUFFICIENT ALTERNATE POWER
 SOURCE SUCH AS A GENERATOR(S), MAINTAINED AT THE
 ASSISTED LIVING FACILITY, TO ENSURE THAT CURRENT
 LICENSEES OF ASSISTED LIVING FACILITIES WILL BE
 EQUIPPED TO ENSURE AMBIENT AIR TEMPERATURES WILL BE
 MAINTAINED AT OR BELOW 81 DEGREES FAHRENHEIT FOR A
 MINIMUM OF NINETY-SIX (96) HOURS IN THE EVENT OF THE
 LOSS OF PRIMARY ELECTRICAL POWER.
 (2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCUATIONS FOR
 ALL ROOMS AND SPACES INVOLVED IN THE RENOVATION. SEE
 TABLE 403.3.1.1 FBC M AND PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
 (3) PROVIDE DETAILS FOR INSTALLATION OF THE WALL AC
 UNITS - SECTION 310.15 FBC M. INSTALLATIONS SHALL BE IN
 GUIDELINES FOR HURRICANE ZONE INSTALLATIONS OR SITE
 SPECIFIC ENGINEERING SHALL BE PROVIDED.
 (4) SHEET M-2: PLEASE UPDATE THE CODE REFERENCES LISTED
 IN THE HVAC NOTES TO THE CURRENT APPLICABLE EDITIONS OF
 THE FBC, NFPA, SMACNA AND ASHRAE.
 (5) THE $40,000 PROJECT VALUE ON THE PERMIT APPLICATION
 APPEARS TO BE A LOW VALUE FOR THE SCOPE OF WORK SHOWN
 ON THE PLANS. PLEASE PROVIDE COPIES OF CONTRACTS,
 ESTIMATES, INVOICES, ETC. FOR THE ENTIRE SCOPE OF WORK
 INCLUDING ARCHITECTURAL, STRUCTURAL, MEP, SITE WORK,
 DESIGN FEES, OVERHEAD AND PROFIT. PLEASE NOTE VALUE IS
 BASED ON ALL COSTS ASSOCIATED WITH THE PROJECT
 INCLUDING LABOR, MATERIALS, EQUIPMENT, FIXTURES,
 APPLIANCES, ETC.
  
 WHEN RESUBMITTING IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 09:43 Rev Time 0.00
Received By gjohnson Date 2020-01-03 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-03 Cont ID  
Sent By gjohnson Date 2019-12-03 Time 10:24 Rev Time 0.00
Received By gjohnson Date 2019-12-03 Time 10:24 Sent To  
Notes
2019-12-03 10:31:511ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.2 STANDARD
 ROLL-IN TYPE SHOWER COMPARTMENTS. IN STANDARD ROLL-IN
 TYPE SHOWER COMPARTMENTS, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE THE GRAB BAR,
 BUT NO HIGHER THAN 48 INCHES ABOVE THE SHOWER FLOOR.
 WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL
 ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27
 INCHES MAXIMUM FROM THE SEAT WALL. AND
 608.6 SHOWER SPRAY UNIT AND WATER. A SHOWER SPRAY UNIT
 WITH A HOSE 59 INCHES LONG MINIMUM THAT CAN BE USED
 BOTH AS A FIXED-POSITION SHOWER HEAD AND AS A HAND-HELD
 SHOWER SHALL BE PROVIDED. THE SHOWER SPRAY UNIT SHALL
 HAVE AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF. IF
 AN ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS
 USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT
 THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER
 WATER THAT IS 120?F (49?C) MAXIMUM
  
 2. PROVIDE SHUT OF VALVE FOR ALL DOWN FED WATER LINE
 CAN BE ON THE BRANCH FROM MAIN LINE. PER FBC PL 606.1
 (5)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status N Date 2020-09-01 Cont ID  
Sent By rmcdouga Date 2020-09-01 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2020-09-01 Time 10:51 Sent To  
Notes
2020-09-01 10:55:52A LETTER WAS RECIEVED FROM KEN SOLOWAY WITH COLONIAL
 ASSISTED LIVING/GOLD STANDARD OF CARE DATED 9/1/2020
 STATING THAT THEY WISH TO FORGO THE PRIVATE PROVIDER
 FROM THEIR PROJECT.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2020-08-18 Cont ID  
Sent By shill Date 2020-08-18 Time 12:28 Rev Time 0.00
Received By rgathrig Date 2020-08-06 Time 16:28 Sent To  
Notes
2020-08-18 12:26:58PRIVATE PROVIDER REVIEWER FAILED
  
  
  
  534 DATURA
  J.C.D. ARCHITECT
  PERMIT 19110320
 SHEETS IN SHEETS IN
 PROJECTDOX WIECHMANN REVIEW
 SHEET # DATE SHEET # DATE
 A-0 1/23/2020 A-0 1/5/2020
 A-1 10/31/2019 A-1 10/31/2019
 A-2 1/23/2020 A-2 1/15/2020
 A-3 10/31/2019 A-3 10/31/2019
 A-4 10/31/2019 A-4 10/31/2019
 A-5 10/31/2019 A-5 10/31/2019
 E-1 10/31/2019 E-1 NOT IN AFFIDAVIT
 E-2 10/31/2019 E-2 8/27/2019
 E-3 10/31/2019 E-3 8/27/2019
 E-4 12/16/2019 E-4 12/12/2019
 E-5 NOT THERE E-5 10/31/2019
 LS-1 12/16/2019 LS-1 12/12/2019
 M-1 12/16/2019 M-1 7/14/2020
 M-2 12/11/2019 M-2 7/14/2020
 P-1 10/31/2019 P-1 10/31/2019
 P-2 12/11/2019 P-2 12/11/2019
 FS-0 12/16/2019 FS-0 12/11/2019
 FS-1 12/16/2019 FS-1 12/11/2019
 FS-2 12/16/2019 FS-2 12/11/2019
  
 THE PAGES IN THE AFFIDAVIT ARE ONLY IDENTIFIED BY PAGE
 NUMBER AND DATE
 THERE IS NO MENTION OF DESIGNER OF RECORD, PLANS IN
 PROJECTDOX ARE PREPARED BY J.C.D. ARCHITECT
 THE AFFIDAVIT OF CODE COMPLIANCE NEEDS TO BE SIGNED BY
 THE PRIVATE PROVIDER (BUCK EVANS)
 IN SUPPORTING DOCUMENTS THERE IS A GENERATOR ELECTRICAL
 RISER DIAGRAM THAT IDENTIFIES NEW WORK
 THIS DOCUMENT IS NOT MENTIONED IN THE PLAN REVIEW
 AFFIDAVIT
  
 RICHARD GATHRIGHT
  
  
  
2020-08-06 16:31:07**REVIEW IN PROGRESS**
  
 COMPLIANCE AFFIDAVIT DOES NOT HAVE DATES/VERSIONS OF
 PLANS REVIEWED. [email protected], 561-805-6724
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2020-07-30 Cont ID  
Sent By shill Date 2020-07-30 Time 14:23 Rev Time 0.00
Received By shill Date 2020-07-30 Time 14:23 Sent To  
Notes
2020-07-30 14:25:27NOTE - PLAN REVIEWS HAVE PASSED BUT THERE ARE STILL
 OUTSTANDING PRIVATE PROVIDER COMMENTS. OWNER MAY ELECT
 TO SUBMIT A NEW NOTICE TO BUILDING OFFICIAL FOR
 INSPECTIONS ONLY; THEN THE PERMIT CAN BE ISSUED AFTER
 RECEIPT OF NAMES/LICENSE NUMBERS OF THE INSPECTORS.
  
 FEES HAVE NOT YET BEEN ADJUSTED PENDING RESOLUTION OF
 THIS ISSUE.
  
 AUTHORITY 553.791
  
 PRIVATE PROVIDER REVIEW NOT APPROVED.
  
 COMPLIANCE AFFIDAVIT DOES NOT HAVE DATES/VERSIONS OF
 PLANS REVIEWED, AND LACKS A DATE THAT THE AFFIDAVIT WAS
 SIGNED. - [email protected], 561-805-6724
  
 BEFORE APPROVAL THE FOLLOWING MUST BE SUBMITTED
 A CURRENT CERTIFICATE OF INSURANCE THAT STATES THE
 PRIVATE PROVIDER HAS THE APPROPRIATE INSURANCE FOR BOTH
 PLAN REVIEW AND INSPECTIONS. THE CERTIFICATE SUBMITTED
 EXPIRED 2/10/2020 AND STATES FOR PRIVATE PROVIDER
 INSPECTIONS ONLY.
 MUST PROVIDE PLAN REVIEW CERTIFICATES FROM THE PRIVATE
 PROVIDER FOR ALL THE PLAN REVIEWS PERFORMED
 MUST PROVIDE QUALIFICATION STATEMENTS OR RESUMES, FOR
 EACH PRIVATE PROVIDER AND ANY DULY AUTHORIZED
 REPRESENTATIVE WHO WILL BE PERFORMING OR WILL PERFORM
 SUCH SERVICES, THEIR PROFESSIONAL LICENSE OR
 CERTIFICATION NUMBER.
  
 RICHARD GATHRIGHT
 [email protected]
 561-805-6679
 RECEIVED NOTICE TO BUILDING OFFICIAL FORM.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2020-01-02 Cont ID  
Sent By rmcdouga Date 2020-01-02 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2020-01-02 Time 18:03 Sent To  
Notes
2020-07-24 10:47:58AUTHORITY 553.791
  
 PRIVATE PROVIDER REVIEW NOT APPROVED.
  
 BEFORE APPROVAL THE FOLLOWING MUST BE SUBMITTED
 A CURRENT CERTIFICATE OF INSURANCE THAT STATES THE
 PRIVATE PROVIDER HAS THE APPROPRIATE INSURANCE FOR BOTH
 PLAN REVIEW AND INSPECTIONS. THE CERTIFICATE SUBMITTED
 EXPIRED 2/10/2020 AND STATES FOR PRIVATE PROVIDER
 INSPECTIONS ONLY.
 MUST PROVIDE PLAN REVIEW CERTIFICATES FROM THE PRIVATE
 PROVIDER FOR ALL THE PLAN REVIEWS PERFORMED
 MUST PROVIDE QUALIFICATION STATEMENTS OR RESUMES, FOR
 EACH PRIVATE PROVIDER AND ANY DULY AUTHORIZED
 REPRESENTATIVE WHO WILL BE PERFORMING OR WILL PERFORM
 SUCH SERVICES, THEIR PROFESSIONAL LICENSE OR
 CERTIFICATION NUMBER.
  
 RICHARD GATHRIGHT
 [email protected]
 561-805-6679
2020-01-02 18:05:00RECEIVED NOTICE TO BUILDING OFFICIAL FORM.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2019-11-22 Cont ID  
Sent By shill Date 2019-11-22 Time 07:11 Rev Time 0.00
Received By shill Date 2019-11-22 Time 07:11 Sent To  
Notes
2019-11-22 07:13:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE PLANS ARE STAMPED AND COMPLIANCE AFFIDAVITS
 SUBMITTED, BUT THE NOTIFICATION COMMONLY KNOWN AS THE
 "NOTICE TO BUILDING OFFICIAL OF USE OF PRIVATE
 PROVIDER" (PER FS553.791(4)(A)&(C)) WAS NOT SUBMITTED.
 PLEASE PROVIDE THIS AS SOON AS POSSIBLE. THIS PROJECT
 FAILED FIRE ON 11/15; PLEASE SUBMIT THE FORM AS SOON AS
 POSSIBLE AS IT WAS REQUIRED AT TIME OF SUBMISSION; IF
 IT IS NOT RECEIVED BEFORE YOU PASS REVIEW BY THE OTHER
 REQUIRED ENTITIES, YOUR AUDIT PLAN REVIEW START DATE
 WILL BE DELAYED UNTIL RECEIPT OF THE REQUIRED
 DOCUMENTATION. CONTRACTOR WAS EMAILED ON 11/19; NO
 RESPONSE AS OF 11/22.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-20 Cont ID  
Sent By jgomez Date 2020-07-20 Time 09:17 Rev Time 0.00
Received By jgomez Date 2020-07-20 Time 09:16 Sent To  
Notes
2020-07-20 09:18:01CONVERTED TO DIGITAL.
 DRAWINGS WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE IN
 CITY'S FILE. JG
  