Plan Review Details - Permit 19110224
Plan Review Stops For Permit 19110224
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2019-11-14 Cont ID  
Sent By dbattles Date 2019-11-08 Time 13:14 Rev Time 0.00
Received By dbattles Date 2019-11-08 Time 13:14 Sent To  
Notes
2019-11-14 14:53:10RECEIVED ASBESTOS LETTER VIA E-MAIL AND ADDED TO THE
 PERMIT SET.
2019-11-08 13:13:59PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By dbattles Date 2019-11-25 Time 14:41 Rev Time 0.00
Received By dbattles Date 2019-11-25 Time 14:41 Sent To  
Notes
2020-01-30 10:23:03PROVISO:
 PROVIDE LETTER FROM THE DESIGNER OF RECORD TO CERTIFY
 THAT THE PARTITION WALL WAS BUILT ACCORDING TO PLANS.
 PROVIDE THE PHOTOS TO SHOW MATERIALS AND STUD SPACING.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-08 Cont ID  
Sent By dbattles Date 2019-11-08 Time 13:03 Rev Time 0.00
Received By dbattles Date 2019-11-08 Time 13:03 Sent To  
Notes
2019-11-08 13:11:48BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19110224
 REVIEWED: NOVEMBER 8, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 IS FLOORING BEING REPLACED?
 IF SO SEE ITEMS BELOW TO PROVIDE FOR CODE COMPLIANCE.
  
 1207.2 FBC[B] FLOORING SUBMITTAL.
 - FLOOR PLAN LAYOUT TO SHOW DIMENSIONS, AREA AND TYPE
 OF FLOORING FOR EACH AREA.
  
 1207.2 FBC[B] FLOORING SUBMITTAL.
 - TYPE OF CEILING ASSEMBLY INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT FLOORING
 AND UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE
 REQUIRED:
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 11:06 Rev Time 0.00
Received By jleahy Date 2019-11-18 Time 11:06 Sent To  
Notes
2019-11-08 11:17:07NOTE PERMIT 19100140 PREVIOUSLY ISSUED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-15 Cont ID  
Sent By pleduc Date 2019-11-15 Time   Rev Time 0.00
Received By pleduc Date 2019-11-15 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-25 Cont ID  
Sent By dbattles Date 2019-11-25 Time 14:41 Rev Time 0.00
Received By dbattles Date 2019-11-25 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 11:06 Rev Time 0.00
Received By jleahy Date 2019-11-05 Time 10:33 Sent To  
Notes
2019-11-06 10:33:46B08

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-11-08 Cont ID  
Sent By gjohnson Date 2019-11-08 Time 12:56 Rev Time 0.00
Received By gjohnson Date 2019-11-08 Time 12:56 Sent To  
Notes
***NONE***