Plan Review Details - Permit 19101533
Plan Review Stops For Permit 19101533
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-11-04 Cont ID  
Sent By rmcdouga Date 2019-11-04 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2019-11-04 Time 08:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-08 Cont ID  
Sent By fgiaquin Date 2019-11-08 Time 07:10 Rev Time 0.00
Received By fgiaquin Date 2019-11-08 Time 07:01 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-13 Cont ID  
Sent By cpuell Date 2019-11-13 Time 09:21 Rev Time 0.00
Received By cpuell Date 2019-10-29 Time 15:17 Sent To  
Notes
2019-10-30 15:17:50ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-14 Cont ID  
Sent By abelisle Date 2019-11-14 Time 16:05 Rev Time 0.00
Received By abelisle Date 2019-11-14 Time 16:05 Sent To I
Notes
2019-11-14 16:07:2811/14/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 ATELYO BELISLE
 PLUMBING PLAN EXAMINER
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By abelisle Date 2019-11-13 Time 06:54 Rev Time 0.00
Received By abelisle Date 2019-11-13 Time 06:25 Sent To I
Notes
2019-11-13 06:59:1911/13/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE
 DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED
 CORRECTIONS.
  
 1- SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2-INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING
 INSTALLED. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 3-IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1.
  
 4-SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 5- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-14 Cont ID  
Sent By rfalcone Date 2019-11-14 Time 16:13 Rev Time 0.00
Received By rfalcone Date 2019-11-14 Time 16:13 Sent To I
Notes
2019-11-14 16:13:37COMMENTS ADDRESSED.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-31 Cont ID  
Sent By rfalcone Date 2019-10-31 Time 10:17 Rev Time 0.00
Received By rfalcone Date 2019-10-31 Time 10:17 Sent To  
Notes
2019-10-31 10:44:4710/31/19 FAILED.
  
 PLEASE REVISE THE LOCATION OF THE POOL EQUIPMENT TO
 COMPLY WITH CODE REGULATIONS. THE REAR SETBACK
 REQUIREMENT IS 12.7 FT. PER ZLDR SEC. 94-305(B)(4),
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME
 NTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  