Plan Review Details - Permit 19101273
Plan Review Stops For Permit 19101273
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2019-12-09 Cont ID  
Sent By shill Date 2019-12-09 Time 17:07 Rev Time 0.00
Received By shill Date 2019-12-09 Time 17:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:48 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 15:21 Rev Time 0.00
Received By rmcphers Date 2020-03-11 Time 15:11 Sent To  
Notes
2020-03-11 15:20:25LIGHT POLES -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE SIGNED AND SEALED LIGHT POLE DETAILS
 (FOUNDATION, ATTACHMENTS ETC.) SHOWING THE WIND DESIGN
 CRITERIA TO COMPLY WITH FBC 1609 (SEE DRAWING L-9)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By shill Date 2019-12-09 Time 17:13 Rev Time 0.00
Received By shill Date 2019-12-09 Time 17:13 Sent To  
Notes
2019-12-09 17:13:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B 1609, SHEET L-9, REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA.
  
 2. ENGINEERING FOR THE LIGHT POLE AND ARM WERE NOT
 PROVIDED; PLEASE PROVIDE. DELEGATED ENGINEERING IS TO
 BE REVIEWED BY SEOR, FAC61G15.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By jpearson Date 2020-03-11 Time 10:54 Rev Time 0.00
Received By jpearson Date 2020-03-11 Time 10:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-11 Cont ID  
Sent By jpearson Date 2019-12-11 Time 14:07 Rev Time 0.00
Received By jpearson Date 2019-12-11 Time 14:07 Sent To  
Notes
2019-12-11 14:04:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE SERVICE AREA RECEPTACLE. NEC 210.64
 5. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION. FBC EC C405.2.5
 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:51 Rev Time 0.00
Received By rmcphers Date 2020-04-10 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 15:24 Rev Time 0.00
Received By rmcphers Date 2020-02-25 Time 11:04 Sent To  
Notes
2020-03-11 15:25:25E MAIL SENT TO PERMIT LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-24 Cont ID  
Sent By cpuell Date 2020-01-24 Time 10:32 Rev Time 0.00
Received By cpuell Date 2019-11-13 Time 08:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-04-23 Cont ID  
Sent By rmcphers Date 2020-04-23 Time 09:00 Rev Time 0.00
Received By rmcphers Date 2020-04-23 Time 09:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:48 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 10:48 Sent To  
Notes
2020-04-15 10:50:50DRAWINGS L-1,2,3,4,5,6,7,8,9,12, AND 13 DO NOT SHOW AS
 ELECTRONICALLY SIGNED IN "ADOBE"

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 15:24 Rev Time 0.00
Received By rmcphers Date 2020-03-11 Time 15:24 Sent To  
Notes
2020-03-11 15:24:46OK AT THIS TIME - NEW DRAWINGS WILL NEED TO BE CHECKED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By shill Date 2019-12-09 Time 17:13 Rev Time 0.00
Received By shill Date 2019-12-09 Time 17:13 Sent To  
Notes
2019-12-09 17:13:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. THE PAGES PREPARED BY MATTHEW FURSETZER,P.E.
 ARE NOT DIGITALLY SIGNED.
  
 ENGINEER IS REQUIRED TO HAVE A TITLE BLOCK ON EACH
 PAGE, FS471.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By aaponte Date 2020-03-11 Time 12:30 Rev Time 0.00
Received By aaponte Date 2020-03-11 Time 12:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-01-13 Cont ID  
Sent By aaponte Date 2020-01-13 Time 16:44 Rev Time 0.00
Received By aaponte Date 2020-01-13 Time 16:44 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved