Plan Review Details - Permit 19101207
Plan Review Stops For Permit 19101207
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-03 Cont ID  
Sent By pvalenti Date 2020-01-03 Time 07:02 Rev Time 0.00
Received By pvalenti Date 2020-01-03 Time 07:02 Sent To  
Notes
2020-01-03 07:04:28***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 INDICATE ON PLANS LOCATIONS OF GATES WITH
 SIZES.
  
 FBC B 3306.1 PLEASE PROVIDE SPECIFIC DETAILS FOR
 PROTECTION OF PEDESTRIANS INCLUDING THE SAFE GUARDS
 DURING CONSTRUCTION OF THE FOLLOWING CODE SECTIONS:
 FBC B 3306.2 WALKWAYS
 FBC B 3306.3 DIRECTIONAL BARRICADES
 FBC B 3306.4 CONSTRUCTION RAILINGS
 FBC B 3306.5/3306.6 BARRIERS
 FBC B 3306.7 COVERED WALKWAYS
 FBC B 3307 PROTECTION OF ADJOINING PROPERTY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-22 Cont ID  
Sent By pvalenti Date 2019-11-22 Time 14:27 Rev Time 0.00
Received By pvalenti Date 2019-11-22 Time 14:27 Sent To  
Notes
2019-11-22 14:29:22***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 INDICATE ON PLANS LOCATIONS OF GATES WITH
 SIZES.
  
 FBC B 3306.1 PLEASE PROVIDE SPECIFIC DETAILS FOR
 PROTECTION OF PEDESTRIANS INCLUDING THE SAFE GUARDS
 DURING CONSTRUCTION OF THE FOLLOWING CODE SECTIONS:
 FBC B 3306.2 WALKWAYS
 FBC B 3306.3 DIRECTIONAL BARRICADES
 FBC B 3306.4 CONSTRUCTION RAILINGS
 FBC B 3306.5/3306.6 BARRIERS
 FBC B 3306.7 COVERED WALKWAYS
 FBC B 3307 PROTECTION OF ADJOINING PROPERTY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-03 Cont ID  
Sent By pleduc Date 2020-01-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-03 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By pleduc Date 2019-11-05 Time   Rev Time 0.00
Received By pleduc Date 2019-11-05 Time 16:40 Sent To  
Notes
2019-11-05 16:44:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF ACCESS GATES. FD
 REQUIRES SITE ACCESS FOR EMERGENCY OR OTHER APPLICABLE
 INCIDENTS.
  
 PER NFPA 1
  
 18.2.3.4 SPECIFICATIONS.
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT
  
  
 PLEASE PROVIDE A MINIMUM OF 2 - 10' GATES THAT IS
 EASILY ACCESSIBLE FROM A ROADWAY.
  
  
  
 2) KNOX PADLOCKS ARE RECOMMENDED FOR EACH GATE FOR EASE
 OF 24HR ENTRY AND SITE SECURITY.
  
  
  
 3) IT APPEARS THAT THE FENCE WILL RESTIRCT ACCESS TO
 FIRE HYDRANTS.
  
 FIRE HYDRANTS SHALL BE ACCESSIBLE FROM THE RAODWAY AT
 ALL TIMES.
  
 PLEASE PROVIDE DETAILS AND LOCATIONS OF ALL FIRE
 HYDRANTS AND PROVIDE FOR ACCESS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-13 Cont ID  
Sent By lmarchan Date 2020-01-13 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2019-12-30 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-06 Cont ID  
Sent By lmarchan Date 2019-12-06 Time 16:35 Rev Time 0.00
Received By lmarchan Date 2019-11-04 Time 15:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2019-11-22 Cont ID  
Sent By pvalenti Date 2019-11-22 Time 14:26 Rev Time 0.00
Received By pvalenti Date 2019-11-22 Time 14:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-01-10 Cont ID  
Sent By eschneid Date 2020-01-10 Time 11:49 Rev Time 0.25
Received By eschneid Date 2020-01-10 Time 11:41 Sent To  
Notes
2020-01-10 11:49:40FAILED
  
 1) UPDATED COMMENT: PROVIDE THE FENCE/GATE DETAIL, TO
 INCLUDE THE REQUIRED WINDSCREEN. THERE FENCE PANEL
 SHEET DOES NOT SPECIFICALLY STATE HOW TALL THE FENCE
 PROPOSED FOR THIS JOB SITE IS, NOR IS INFORMATION
 REGARDING THE WINDSCREEN PROVIDED.
  
 2) REPEAT COMMENT: PROVIDE THE EASEMENT RELEASE FROM
 BELLSOUTH (PROPOSED FENCE CROSSES THEIR EASEMENT) AND
 THE CITY'S WATER UTILITY.
  
 3) REPEAT COMMENT: THE FENCE LOCATION IS SHOWN IN THE
 ROSEMARY AVENUE AND HIBISCUS STREET RIGHTS-OF-WAY. THE
 FENCE MAY NOT ENCROACH PAST THE PROPERTY LINE.
  
 4) REPEAT COMMENT: YOU MUST SHOW A PROTECTED PATH FROM
 THE D GARAGE PEDESTRIAN ENTRANCE/EXIT TO THE ALLEY TO
 THE HIBISCUS STREET SIDEWALK THAT SEPARATES PEDESTRIANS
 FROM THE TRAVEL PATH. THE CURRENT FENCE PLAN REQUIRES
 PEDESTRIANS TO WALK IN THE TRAVEL LANE AT THE SOUTH END
 OF THE ALLEY.
  
 5) GRAPHICS OR TEXT ON THE FENCE SCREENING REQUIRES A
 PERMIT PRIOR TO INSTALLATION.
  
 6) PLEASE NOTE THAT THE CITY HAS STRICT TIME LINES FOR
 THE USE OF CONSTRUCTION FENCES. WITHIN 15 DAYS OF THE
 COMPLETION OF THE DEMOLITION, THE FENCE NEEDS TO BE
 REMOVED AND THE SITE WILL BE REQUIRED TO HAVE
 VEGETATIVE COVER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-12-06 Cont ID  
Sent By eschneid Date 2019-12-06 Time 15:43 Rev Time 0.50
Received By eschneid Date 2019-12-06 Time 15:43 Sent To  
Notes
2019-12-06 16:25:15FAILED
  
 1) THE REQUIRED CITYPLACE RETAIL APPROVAL (STAMP ON
 PLANS OR SEPARATE LETTER) IS MISSING.
  
 2) PROVIDE THE FENCE/GATE DETAIL, TO INCLUDE THE
 REQUIRED WINDSCREEN.
  
 3) PROVIDE THE EASEMENT RELEASE FROM BELLSOUTH
 (PROPOSED FENCE CROSSES THEIR EASEMENT) AND THE CITY'S
 WATER UTILITY.
  
 4) THE FENCE LOCATION IS SHOWN IN THE ROSEMARY AVENUE
 AND HIBISCUS STREET RIGHTS-OF-WAY. THE FENCE MAY NOT
 ENCROACH PAST THE PROPERTY LINE.
  
 5) YOU MUST SHOW A PROTECTED PATH FROM THE D GARAGE
 PEDESTRIAN ENTRANCE/EXIT TO THE ALLEY TO THE HIBISCUS
 STREET SIDEWALK THAT SEPARATES PEDESTRIANS FROM THE
 TRAVEL PATH. THE CURRENT FENCE PLAN REQUIRES
 PEDESTRIANS TO WALK IN THE TRAVEL LANE AT THE SOUTH END
 OF THE ALLEY.
  
 6) GRAPHICS OR TEXT ON THE FENCE SCREENING REQUIRES A
 PERMIT PRIOR TO INSTALLATION.
  
 7) PLEASE NOTE THAT THE CITY HAS STRICT TIME LINES FOR
 THE USE OF CONSTRUCTION FENCES. WITHIN 15 DAYS OF THE
 COMPLETION OF THE DEMOLITION, THE FENCE NEEDS TO BE
 REMOVED AND THE SITE WILL BE REQUIRED TO HAVE
 VEGETATIVE COVER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]