Plan Review Details - Permit 19101143
Plan Review Stops For Permit 19101143
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By jleahy Date 2019-12-19 Time 11:47 Rev Time 0.00
Received By jleahy Date 2019-12-19 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-06 Cont ID  
Sent By jleahy Date 2019-11-06 Time 13:02 Rev Time 0.00
Received By jleahy Date 2019-11-06 Time 13:02 Sent To  
Notes
2019-11-06 13:03:44FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 HOW DOES CONTROLER GET ITS POWER? 110 VOLT SUPPLY????
  
 PLUG IN OR HARD WIRE?????

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-12-16 Cont ID  
Sent By pleduc Date 2019-12-16 Time   Rev Time 0.00
Received By pleduc Date 2019-12-16 Time 14:45 Sent To E
Notes
2019-12-16 14:47:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL COMPLY WITH NFPA 101, CH 7,
 MEANS OF EGRESS.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE
 ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, LISTED
 HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN
 THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY IN
 THE DIRECTION OF EGRESS.
 (5) *LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF
 EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
 7.2.1.5.7 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 KEY
 OPERATION SHALL BE PERMITTED, PROVIDED THAT THE KEY
 CANNOT BE
 REMOVED WHEN THE DOOR LEAF IS LOCKED FROM THE SIDE FROM
 WHICH
 EGRESS IS TO BE MADE.
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE
 THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2,
 SHALL MEET ONE
 OF THE FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE
 BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF
 THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO
 UNLOCK ALL
 STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH 7.2.1.5.8.1
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-28 Cont ID  
Sent By pleduc Date 2019-10-28 Time   Rev Time 0.00
Received By pleduc Date 2019-10-28 Time 12:20 Sent To E
Notes
2019-10-28 12:27:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IT IS UNCLEAR IF THE PROPOSED DOORS ARE WITHIN A
 REQUIRED MEANS OF EGRESS AND HOW THEY WILL FUNCTION
 UNDER NORMAL REQUIRED EXITING.
  
 PLEASSE REVIEW, PROVIDE GREATER DETAIL AND ENSURE
 COMPLAINCE WITH NFPA 101, CH 7, MEANS OF EGRESS.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE
 ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, LISTED
 HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN
 THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY IN
 THE DIRECTION OF EGRESS.
 (5) *LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF
 EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
 7.2.1.5.7 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 KEY
 OPERATION SHALL BE PERMITTED, PROVIDED THAT THE KEY
 CANNOT BE
 REMOVED WHEN THE DOOR LEAF IS LOCKED FROM THE SIDE FROM
 WHICH
 EGRESS IS TO BE MADE.
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE
 THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2,
 SHALL MEET ONE
 OF THE FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE
 BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF
 THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO
 UNLOCK ALL
 STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH 7.2.1.5.8.1
  
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-19 Cont ID  
Sent By jleahy Date 2019-12-19 Time 11:47 Rev Time 0.00
Received By jleahy Date 2019-12-13 Time 13:10 Sent To  
Notes
2019-12-16 13:10:36RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-06 Cont ID  
Sent By jleahy Date 2019-11-06 Time 13:03 Rev Time 0.00
Received By jleahy Date 2019-10-22 Time 11:11 Sent To  
Notes
2019-10-23 11:11:12ROUTED TO FIRE INBOX