Plan Review Details - Permit 19101063
Plan Review Stops For Permit 19101063
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-01 Cont ID  
Sent By cthroop Date 2020-02-01 Time 09:49 Rev Time 0.00
Received By cthroop Date 2020-01-29 Time 14:35 Sent To  
Notes
2020-10-26 14:42:28A C/O HOLD HAS BEEN PLACED ON THE PERMIT FOR FINAL
 ELEVATION CERTIFICATE. CT
2020-02-05 12:08:19*********************************ZONING
 PROVISIO**********************************
  
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-17 Cont ID  
Sent By cthroop Date 2020-01-17 Time 07:12 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 10:31 Sent To  
Notes
2020-01-17 07:13:30PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 1. SEE COMMENTS UNDER 2ND NFIP REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 11:00 Rev Time 0.00
Received By cthroop Date 2019-11-14 Time 07:38 Sent To  
Notes
2019-11-19 11:13:56PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 3. PROVIDE DESIGN AND INSTALLATION INSTRUCTIONS FOR THE
 HOLLOW CORE FLOOR SYSTEM.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 4. PROVIDE ICC EVALUATION REPORT FOR THE PROPOSED
 ICYNENE SPRAY FOAM INSULATION.
 INSTALLATION REQUIREMENTS SHALL BE ON-SITE AT TIME OF
 INSPECTION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY,
 INSERT CORRECTED PAGES INTO
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS
 DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By jpearson Date 2020-01-13 Time 13:32 Rev Time 0.00
Received By jpearson Date 2020-01-08 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By jpearson Date 2019-11-21 Time 10:09 Rev Time 0.00
Received By jpearson Date 2019-11-21 Time 10:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By fgiaquin Date 2019-11-02 Time 06:56 Rev Time 0.00
Received By fgiaquin Date 2019-11-01 Time 06:56 Sent To  
Notes
2019-11-04 07:00:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE NOTE ON PLAN STATING, LOW VOLTAGE,
 GENERATOR, POOL, AND ELEVATOR REQUIRE SEPARATE PERMITS.
 FBC 105.1 FBC 107.2.1
  
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (LETTER FROM POWER COMPANY ALREADY ON
 PLAN).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By cthroop Date 2020-01-17 Time 10:37 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 10:31 Sent To  
Notes
2020-01-17 10:38:39DEFERRAL: MANUF. SPECS. AND GAS REGULATORS SHALL BE
 SUBMITTED PRIOR TO INSTALLTION. DESIGNER SHALL REVIEW
 AND APPROVE IN WRITING.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-11-27 Cont ID  
Sent By gjohnson Date 2019-11-27 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2019-11-27 Time 10:16 Sent To  
Notes
2019-11-27 10:25:431ST REVIEW: 19101063
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. PROVIDE DETAIL FOR SLEEVE UNDER SLAB FOR STEEL SCH
 40 PIPE IT SHALL COMPLY WITH FBC FG 404.8.1
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2017 FUEL GAS CODE SEC. 304.
  
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL
 GAS CODE SEC. 502 THRU 505.
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSILLATION GUIDE FOR ALL GAS EQUIPMENT AND REGULATORS
 TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58,
 AND FBC-2017 FUEL GAS SEC. 402.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-05 Cont ID  
Sent By lmarchan Date 2020-02-05 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2020-01-29 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-27 Cont ID  
Sent By lmarchan Date 2020-01-27 Time 09:49 Rev Time 0.00
Received By lmarchan Date 2020-01-06 Time 13:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-27 Cont ID  
Sent By lmarchan Date 2019-11-27 Time 11:13 Rev Time 0.00
Received By lmarchan Date 2019-11-13 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-04 Cont ID  
Sent By lmarchan Date 2019-11-04 Time 16:04 Rev Time 0.00
Received By lmarchan Date 2019-10-30 Time 12:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By lmarchan Date 2020-02-05 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2020-01-17 Time 10:42 Sent To  
Notes
2020-02-03 08:40:15RECEIPT 2020-0203-259 - $21.91 - PAID

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-03 Cont ID  
Sent By cthroop Date 2019-12-03 Time 15:37 Rev Time 0.00
Received By cthroop Date 2019-12-03 Time 15:37 Sent To  
Notes
2019-12-03 15:43:49PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 IMPACT FEE QUESTIONAIRE ON-FILE. PALM BEACH COUNTY WILL
 BE NOTIFIED AT A LATER DATE. CT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By cthroop Date 2020-01-17 Time 08:20 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 11:53 Rev Time 0.00
Received By cthroop Date 2019-11-14 Time 07:38 Sent To  
Notes
2019-11-19 12:00:14PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFICATION AND LOCATION OF ACU'S ON MECH. PLAN
 ARE IN CONFLICT WITH IDENTIFICATION AND LOCATION OF
 ACU'S ON PLAN PAGE A-1 FLOOR PLAN. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE DETAIL AND PRODUCT APPROVAL OF MECHANICAL
 STANDS TO BE USED TO ELEVATE MECH. EQUIPMENT ABOVE DFE.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE MECHANICAL STAND SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY,
 INSERT CORRECTED PAGES INTO
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS
 DETACHED.
  
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2020-02-01 Cont ID  
Sent By cthroop Date 2020-02-01 Time 09:46 Rev Time 0.00
Received By cthroop Date 2020-01-29 Time 14:35 Sent To  
Notes
2020-02-01 09:50:05UNDER CONSTRUCTION EC COLLECTED BY JV. SUBMITTAL OPENED
 BY SHILL - 20070861. NO REVIEW. UPLOADED TO FILE NET.
 C/O HOLD FOR FINAL EC. CT
 FLOOD ZONE AE WITH BFE OF 7.0 FEET AND 8.0 FEET.
 PROPOSED FINISH FLOOR ELEVATION ON CONSTRUCTION DRAWING
 EC - 10.0 FEET NAVD. CT
 FLOOR PLAN A1 SHOWS 5 SMART VENTS AT 200 SQ FT EACH.
 GARAGE IS 1200 SQ FT. EC CALLS FOR 6 SMART VENTS. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2020-01-17 Cont ID  
Sent By cthroop Date 2020-01-17 Time 06:49 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 10:31 Sent To  
Notes
2020-01-17 07:01:08PLAN REVIEW - NFIP
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 PLEASE REFERENCE 2ND ELEVATION CERTIFICATE SUBMITTED
 FOR REVIEW ON 12/30/2019
  
 1. SECTION A9 (B) - STATE NUMBER OF FLOOD VENTS.
  
 2. SECTION A9 (C) - PROVIDE NET AREA OF FLOOD OPENINGS
 IN A9 (B) ABOVE.
  
 3. SECTION A9 (D) - ENGINEERED FLOOD OPENINGS - NO
 SEE NOTE ON PLAN PAGE A-1 - SMART VENT MODEL 1540-520
 TO BE INSTALLED.
 IF SMART VENT'S ARE INSTALLED, PROVIDE EVALUATION
 REPORT ISSUED BY THE INTERNATIONAL CODE COUNCIL
 EVALUATION SERVICE. (ICC ES)
  
 IF NON-ENGINEERED VENTS ARE INSTALLED, PROVIDE DETAIL
 REVIEWED AND APPROVED BY DESIGNER OF RECORD.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 09:35 Rev Time 0.00
Received By cthroop Date 2019-11-19 Time 09:35 Sent To  
Notes
2019-11-19 09:47:17PLAN REVIEW - NFIP
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE SUBMITTED SITE PLAN, THIS LOT AND
 PROPOSED IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE
 WITH BASE FLOOD ELEVATIONS (BFE) OF 7.0 AND 8.0 FEET
 NAVD.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 4. YOU MAY SUBMIT AN ELEVATION CERTIFICATE SHOWING ALL
 EXISTING AND PROPOSED ELEVATIONS BASED ON NAVD88 DATUM
 PLUS TWO FEET OF FREEBOARD OR THE ENGINEER OF RECORD
 (EOR) MAY ADD A STATEMENT TO THE STRUCTURAL PLAN THAT
 THE DESIGN FLOOD ELEVATION (DFE) WILL BE 10.0 FEET
 NAVD88 BASED ON THE (BFE) OF 8.00 FEET FOR FLOOD ZONE
 AE.
  
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A TWO
 FOOT FREEBOARD ABOVE THE (BFE).
  
 5. PROTECTION OF MECHANICAL EQUIPMENT.
  
 CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE).
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
  
 6. FLOOD VENTS SHALL BE REQUIRED IN ATTACHED GARAGE.
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY WAVE
 ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS TO
 ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
 PLEASE RE-SUBMIT A CORRECTED ELEVATION CERTIFICATE.
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By cthroop Date 2020-01-17 Time 10:19 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 10:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-27 Cont ID  
Sent By gjohnson Date 2019-11-27 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2019-11-27 Time 10:25 Sent To  
Notes
2019-11-27 10:41:231ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-4 IS DUPLICATED PLEASE REMOVE THE ONE THAT IS
 NOT VALID. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. P-4 THE SANITARY ISOMETRIC SHOWS A SHOWER IN
 THE SECOND FLOOR GUEST BATHROOM AND THE FLOOR PLAN
 SHOWS A TUB PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 09:34 Rev Time 0.00
Received By cthroop Date 2019-11-14 Time 07:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By cthroop Date 2020-01-17 Time 10:40 Rev Time 0.00
Received By cthroop Date 2020-01-08 Time 10:31 Sent To  
Notes
2020-01-14 15:46:191/14/20 DIGITALLY SIGNED SHEETS UPLOADED INTO
 "SIGNATURES" FOLDER. LEM
2020-01-13 13:30:39ELECTRICAL SHEETS: ADVISED ENGINEER PER EMAIL THAT THE
 CURRENT DIGITAL SIGNATURE IS NOT ACCEPTABLE, ENGINEERS
 ARE NOT PERMITTED TO SELF-CERTIFY. PER THE WPB
 AMENDMENTS TO THE FBC, EACH SHEET OF PLAN IS REQUIRED
 TO BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION.
 SELF-CERTIFICATION IS NOT ACCEPTABLE FOR ENGINEERS.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 09:34 Rev Time 0.00
Received By cthroop Date 2019-11-14 Time 07:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2020-02-05 Time   Rev Time 0.00
Received By   Date 2020-02-05 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-01-21 Cont ID  
Sent By awooten Date 2020-01-21 Time   Rev Time 0.00
Received By awooten Date 2020-01-21 Time   Sent To  
Notes
2020-01-21 15:08:37*****************************ZONING REVIEW
 FAILED***********************************
  
 NEW SINGLE FAMILY CONSTRUCTION TRIGGERS THE LANDSCAPING
 CODE. PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING (REPEAT COMMENTS):
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-11-20 Cont ID  
Sent By awooten Date 2019-11-20 Time   Rev Time  
Received By awooten Date 2019-11-20 Time   Sent To  
Notes
2019-11-20 16:20:48*************************************ZONING REVIEW
 FAILED*************************************
  
 NEW SINGLE FAMILY CONSTRUCTION TRIGGERS THE LANDSCAPING
 CODE. PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ONLY ONE KITCHEN IS PERMITTED IN A SINGLE FAMILY HOME.
 YOU CAN HAVE A KITCHENETTE WITH A SINK AND A SMALL
 REFRIDGERATOR AND MICROWAVE IN THE GUEST SUITE. THE
 STOVE/OVEN RANGE WILL NEED TO BE REMOVED.
  
 MECHANICAL EQUIPMENT, POOLS, PATIO, FENCES/WALLS AND
 DRIVEWAYS REQUIRE A SEPARATE PERMIT.
  
 PLEASE DIMENSION THE BALCONY PROJECTION INTO THE
 SETBACKS. DIMENSION THE OVERHANGS. STRUCTURAL
 INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING BUT NOT
 LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES, AND
 ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER THAN
 THREE FEET INTO ANY SETBACK.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]