Plan Review Details - Permit 19101061
Plan Review Stops For Permit 19101061
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-05-24 Cont ID  
Sent By jwitmer Date 2022-05-24 Time 07:50 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-05-24 07:50:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101061
 ADD: 1101 N. CONGRESS AVE. WEST PALM BEACH LIFT STATION
 # 76
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-494-1040 (1111)
 CONTACT: RANDY ERYSTHEE/ PUBLIC UTILITIES DIR.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5H REVIEW
 DATE: TUES. MAY 24TH/2022
 ACTION: DENIED
  
 1) THIS REVIEW RESIDENT INSPECTOR FORMS COMPLETED WITH
 EXCEPTION NO CONTRACTOR SIGNATURE ON FORMS NOR NO CGC
 CONTRACTOR SIGNED ONTO THE PERMIT APPLICATION.
  
 3RD REVIEW. NOTED RESPONSE THAT ONCE A CONTRACTOR IS
 HIRED/ CONTRACTED WITH BY THE CITY OF WEST PALM BEACH
 THE RESIDENT INSPECTOR FORMS WILL BE SIGNED AND
 RETURNED TO THE BUILDING DEPARTMENT AND REVIEWED AND
 APPROVED BEFORE PERMIT ISSUANCE. THE TYPE OF STRUCTURAL
 REPAIRS ON THE LIFT STATION AND WET WELL WILL LEND
 ITSELF BETTER FOR A RESIDENT INSPECTOR. MONDAY FEB.
 03/2020, I SPOKE WITH OUR ASSISTANT BUILDING OFFICIAL
 RICHARD GATHRIGHT AFTER SPEAKING WITH MR. RANDY
 ERYSTHEE ABOUT 3RD PARTY INSPECTIONS. MR. ERYSTHEE
 ASKED IF THE CITY INSPECTORS COULD DO THE STRUCTURAL
 INSPECTIONS. MR. GATHRIGHT AND I MET WITH THE CHIEF
 BUILDING INSPECTOR THIS MORNING ABOUT CITY INSPECTORS
 DOING THIS TYPE OF INSPECTIONS. BOTH THE CHIEF BUILDING
 INSPECTOR AND MR. GATHRIGHT AGREED THAT THIS TYPE OF
 RESTORATION WORK WOULD REQUIRE A 3RD PARTY INSPECTION
 SERVICE (RESIDENT INSPECTOR) THAT COULD STAY ONSITE
 THROUGHOUT THE DURATION OF THE RESTORATION WORK. THE
 FORMS SENT TO MR. RANDY ERYSTHEE WILL NEED TO BE
 COMPLETED SIGNED BY ALL PARTIES AND RETURNED TO THE
 BUILDING DEPARTMENT BEFORE THE PERMIT CAN BE ISSUED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 110.3.9. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE
 MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 110. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 BOOKLET: GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 BOOKLET AND FORMS FOR RESIDENT INSPECTOR WERE E-MAILED
 TO:
 E-MAIL: [email protected] SENT ON 11/25 & 26/2019 FOR
 LIFT STATIONS 47 & 76.
 PAGES 9-13 DEAL WITH RESIDENT INSPECTORS
 PAGES 14-16 RESIDENT INSPECTOR FORMS. FORMS WILL NEED
 TO BE SIGNED BY ALL INTERESTED PARTIES AND SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE.
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL AND INCLUDING A CODE COMPLIANCE OPINION OF THE
 RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 2A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2B) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & ROOF HATCHES.
  
 3) 4TH REVIEW. SHEET S-3 LIST THE PRODUCTS TO BE USED
 IN THE STRUCTURAL REPAIRS. PLEASE PROVIDE THE PRODUCT
 DATA SHEETS AND MSDS SHEETS FOR ALL OF THE PRODUCTS
 THAT ARE GOING TO BE USED IN THE STRUCTURAL REPAIRS
 PRIORITIES AND PROCEDURES.
 PLEASE PROVIDE HOW THESE CHEMICALS ARE GOING TO BE
 STORED. HOW THE TOOLS WILL BE CLEANED AND HOW THE
 CHEMICAL WASTE FROM THE SIKA SYSTEM WILL BE DISPOSED.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2022-03-01 Time 11:03 Sent To  
Notes
2022-03-01 11:08:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101061
 ADD: 1101 N. CONGRESS AVE. WEST PALM BEACH LIFT STATION
 # 76
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-494-1040 (1111)
 CONTACT: RANDY ERYSTHEE/ PUBLIC UTILITIES DIR.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. MARCH 01/2022
 ACTION: DENIED
  
 1) THIS REVIEW RESIDENT INSPECTOR FORMS COMPLETED WITH
 EXCEPTION NO CONTRACTOR SIGNATURE ON FORMS NOR NO CGC
 CONTRACTOR SIGNED ONTO THE PERMIT APPLICATION.
  
 3RD REVIEW. NOTED RESPONSE THAT ONCE A CONTRACTOR IS
 HIRED/ CONTRACTED WITH BY THE CITY OF WEST PALM BEACH
 THE RESIDENT INSPECTOR FORMS WILL BE SIGNED AND
 RETURNED TO THE BUILDING DEPARTMENT AND REVIEWED AND
 APPROVED BEFORE PERMIT ISSUANCE. THE TYPE OF STRUCTURAL
 REPAIRS ON THE LIFT STATION AND WET WELL WILL LEND
 ITSELF BETTER FOR A RESIDENT INSPECTOR. MONDAY FEB.
 03/2020 I SPOKE WITH OUR ASSISTANT BUILDING OFFICIAL
 RICHARD GATHRIGHT AFTER SPEAKING WITH MR. RANDY
 ERYSTHEE ABOUT 3RD PARTY INSPECTIONS. MR. ERYSTHEE
 ASKED IF THE CITY INSPECTORS COULD DO THE STRUCTURAL
 INSPECTIONS. MR. GATHRIGHT AND I MET WITH THE CHIEF
 BUILDING INSPECTOR THIS MORNING ABOUT CITY INSPECTORS
 DOING THIS TYPE OF INSPECTIONS. BOTH THE CHIEF BUILDING
 INSPECTOR AND MR. GATHRIGHT AGREED THAT THIS TYPE OF
 RESTORATION WORK WOULD REQUIRE A 3RD PARTY INSPECTION
 SERVICE (RESIDENT INSPECTOR) THAT COULD STAY ONSITE
 THROUGHOUT THE DURATION OF THE RESTORATION WORK. THE
 FORMS SENT TO MR. RANDY ERYSTHEE WILL NEED TO BE
 COMPLETED SIGNED BY ALL PARTIES AND RETURNED TO THE
 BUILDING DEPARTMENT BEFORE THE PERMIT CAN BE ISSUED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 110.3.9. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE
 MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 110. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 BOOKLET: GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 BOOKLET AND FORMS FOR RESIDENT INSPECTOR WERE E-MAILED
 TO:
 E-MAIL: [email protected] SENT ON 11/25 & 26/2019 FOR
 LIFT STATIONS 47 & 76.
 PAGES 9-13 DEAL WITH RESIDENT INSPECTORS
 PAGES 14-16 RESIDENT INSPECTOR FORMS. FORMS WILL NEED
 TO BE SIGNED BY ALL INTERESTED PARTIES AND SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE.
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 2A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2B) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & ROOF HATCHES.
  
 3) 4TH REVIEW. SHEET S-3 LIST THE PRODUCTS TO BE USED
 IN THE STRUCTURAL REPAIRS. PLEASE PROVIDE THE PRODUCT
 DATA SHEETS AND MSDS SHEETS FOR ALL OF THE PRODUCTS
 THAT ARE GOING TO BE USED IN THE STRUCTURAL REPAIRS
 PRIORITIES AND PROCEDURES.
 PLEASE PROVIDE HOW THESE CHEMICALS ARE GOING TO BE
 STORED. HOW THE TOOLS WILL BE CLEANED AND HOW THE
 CHEMICAL WASTE FROM THE SIKA SYSTEM WILL BE DISPOSED.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-08-10 Cont ID  
Sent By jwitmer Date 2020-08-10 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2020-08-10 Time 14:59 Sent To  
Notes
2020-08-10 15:08:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101061
 ADD: 1101 N. CONGRESS AVE. WEST PALM BEACH LIFT STATION
 # 76
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-494-1040 (1111)
 CONTACT: RANDY ERYSTHEE/ PUBLIC UTILITIES DIR.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. AUGUST 10TH/2020
 ACTION: DENIED
  
 1) NOTED RESPONSE THAT ONCE A CONTRACTOR IS HIRED/
 CONTRACTED WITH BY THE CITY OF WEST PALM BEACH THE
 RESIDENT INSPECTOR FORMS WILL BE SIGNED AND RETURNED TO
 THE BUILDING DEPARTMENT AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE. THE TYPE OF STRUCTURAL REPAIRS
 ON THE LIFT STATION AND WET WELL WILL LEND ITSELF
 BETTER FOR A RESIDENT INSPECTOR. MONDAY FEB. 03/2020 I
 SPOKE WITH OUR ASSISTANT BUILDING OFFICIAL RICHARD
 GATHRIGHT AFTER SPEAKING WITH MR. RANDY ERYSTHEE ABOUT
 3RD PARTY INSPECTIONS. MR. ERYSTHEE ASKED IF THE CITY
 INSPECTORS COULD DO THE STRUCTURAL INSPECTIONS. MR.
 GATHRIGHT AND I MET WITH THE CHIEF BUILDING INSPECTOR
 THIS MORNING ABOUT CITY INSPECTORS DOING THIS TYPE OF
 INSPECTIONS. BOTH THE CHIEF BUILDING INSPECTOR AND MR.
 GATHRIGHT AGREED THAT THIS TYPE OF RESTORATION WORK
 WOULD REQUIRE A 3RD PARTY INSPECTION SERVICE (RESIDENT
 INSPECTOR) THAT COULD STAY ONSITE THROUGHOUT THE
 DURATION OF THE RESTORATION WORK. THE FORMS SENT TO MR.
 RANDY ERYSTHEE WILL NEED TO BE COMPLETED SIGNED BY ALL
 PARTIES AND RETURNED TO THE BUILDING DEPARTMENT BEFORE
 THE PERMIT CAN BE ISSUED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 110.3.9. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE
 MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 110. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 BOOKLET: GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 BOOKLET AND FORMS FOR RESIDENT INSPECTOR WERE E-MAILED
 TO:
 E-MAIL: [email protected] SENT ON 11/25 & 26/2019 FOR
 LIFT STATIONS 47 & 76.
 PAGES 9-13 DEAL WITH RESIDENT INSPECTORS
 PAGES 14-16 RESIDENT INSPECTOR FORMS. FORMS WILL NEED
 TO BE SIGNED BY ALL INTERESTED PARTIES AND SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE.
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
 2A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2B) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & ROOF HATCHES.
 3) SHEET S-3 LIST THE PRODUCTS TO BE USED IN THE
 STRUCTURAL REPAIRS. PLEASE PROVIDE THE PRODUCT DATA
 SHEETS AND MSDS SHEETS FOR ALL OF THE PRODUCTS THAT ARE
 GOING TO BE USED IN THE STRUCTURAL REPAIRS PRIORITIES
 AND PROCEDURES.
 PLEASE PROVIDE HOW THESE CHEMICALS ARE GOING TO BE
 STORED. HOW THE TOOLS WILL BE CLEANED AND HOW THE
 CHEMICAL WASTE FROM THE SIKA SYSTEM WILLBE DISPOSED.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 08:52 Rev Time 0.00
Received By rrossano Date 2020-02-03 Time 11:42 Sent To  
Notes
2020-02-04 08:51:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101061
 ADD: 1101 N. CONGRESS AVE. WEST PALM BEACH LIFT STATION
 # 76
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-494-1040 (1111)
 CONTACT: RANDY ERYSTHEE/ PUBLIC UTILITIES DIR.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 04/2020
 ACTION: DENIED
  
 1) THE TYPE OF STRUCTURAL REPAIRS ON THE LIFT STATION
 AND WET WELL WILL LEND ITSELF BETTER FOR A RESIDENT
 INSPECTOR. MONDAY FEB. 03/2020 I SPOKE WITH OUR
 ASSISTANT BUILDING OFFICIAL RICHARD GATHRIGHT AFTER
 SPEAKING WITH MR. RANDY ERYSTHEE ABOUT 3RD PARTY
 INSPECTIONS. MR. ERYSTHEE ASKED IF THE CITY INSPECTORS
 COULD DO THE STRUCTURAL INSPECTIONS. MR. GATHRIGHT AND
 I MET WITH THE CHIEF BUILDING INSPECTOR THIS MORNING
 ABOUT CITY INSPECTORS DOING THIS TYPE OF INSPECTIONS.
 BOTH THE CHIEF BUILDING INSPECTOR AND MR. GATHRIGHT
 AGREED THAT THIS TYPE OF RESTORATION WORK WOULD REQUIRE
 A 3RD PARTY INSPECTION SERVICE (RESIDENT INSPECTOR)
 THAT COULD STAY ONSITE THROUGHOUT THE DURATION OF THE
 RESTORATION WORK. THE FORMS SENT TO MR. RANDY ERYSTHEE
 WILL NEED TO BE COMPLETED SIGNED BY ALL PARTIES AND
 RETURNED TO THE BUILDING DEPARTMENT BEFORE THE PERMIT
 CAN BE ISSUED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 110.3.9. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE
 MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 110. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 BOOKLET: GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 BOOKLET AND FORMS FOR RESIDENT INSPECTOR WERE E-MAILED
 TO:
 E-MAIL: [email protected] SENT ON 11/25 & 26/2019 FOR
 LIFT STATIONS 47 & 76.
 PAGES 9-13 DEAL WITH RESIDENT INSPECTORS
 PAGES 14-16 RESIDENT INSPECTOR FORMS. FORMS WILL NEED
 TO BE SIGNED BY ALL INTERESTED PARTIES AND SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE.
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
 2A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2B) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & ROOF HATCHES.
 3) SHEET S-3 LIST THE PRODUCTS TO BE USED IN THE
 STRUCTURAL REPAIRS. PLEASE PROVIDE THE PRODUCT DATA
 SHEETS AND MSDS SHEETS FOR ALL OF THE PRODUCTS THAT ARE
 GOING TO BE USED IN THE STRUCTURAL REPAIRS PRIORITIES
 AND PROCEDURES.
 PLEASE PROVIDE HOW THESE CHEMICALS ARE GOING TO BE
 STORED. HOW THE TOOLS WILL BE CLEANED AND HOW THE
 CHEMICAL WASTE FROM THE SIKA SYSTEM WILLBE DISPOSED.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-26 Cont ID  
Sent By jwitmer Date 2019-11-26 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2019-11-26 Time 13:01 Sent To  
Notes
2019-11-26 13:35:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101061
 ADD: 1101 N. CONGRESS AVE. WEST PALM BEACH LIFT STATION
 # 76
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????
 CONTACT: RANDY ERYSTHEE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 26/2019
 ACTION: DENIED
  
 1) THE TYPE OF STRUCTURAL REPAIRS ON THE LIFT STATION
 AND WET WELL WILL LEND ITSELF BETTER FOR A RESIDENT
 INSPECTOR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 110.3.9. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE
 MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 110. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 BOOKLET: GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 BOOKLET AND FORMS FOR RESIDENT INSPECTOR WERE E-MAILED
 TO:
 E-MAIL: [email protected]
 PAGES 9-13 DEAL WITH RESIDENT INSPECTORS
 PAGES 14-16 RESIDENT INSPECTOR FORMS. FORMS WILL NEED
 TO BE SIGNED BY ALL INTERESTED PARTIES AND SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 2) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2) 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS & ROOF
 HATCHES.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-04 Cont ID  
Sent By jleahy Date 2022-03-04 Time 16:33 Rev Time 0.00
Received By jleahy Date 2022-03-04 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-26 Cont ID  
Sent By jleahy Date 2019-11-26 Time 14:19 Rev Time 0.00
Received By jleahy Date 2019-11-26 Time 14:19 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-02-14 Cont ID  
Sent By rrossano Date 2022-02-14 Time   Rev Time 0.00
Received By rrossano Date 2022-02-14 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2019-12-10 Cont ID  
Sent By rrossano Date 2019-12-10 Time   Rev Time 0.00
Received By rrossano Date 2019-12-10 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-14 Cont ID  
Sent By pleduc Date 2022-02-14 Time   Rev Time 0.00
Received By pleduc Date 2022-02-14 Time 12:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-19 Cont ID  
Sent By pleduc Date 2019-11-19 Time   Rev Time 0.00
Received By pleduc Date 2019-11-18 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-05-24 Cont ID  
Sent By jwitmer Date 2022-05-24 Time 07:52 Rev Time 0.00
Received By jwitmer Date 2022-05-21 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-04 Cont ID  
Sent By jleahy Date 2022-03-04 Time 16:33 Rev Time 0.00
Received By jleahy Date 2022-02-13 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-10 Cont ID  
Sent By jwitmer Date 2020-08-10 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2020-08-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-02-06 Time   Rev Time 0.00
Received By cpuell Date 2020-01-23 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-12-10 Cont ID  
Sent By cpuell Date 2019-12-10 Time 09:18 Rev Time 0.00
Received By cpuell Date 2019-11-12 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-02-23 Cont ID  
Sent By medwards Date 2022-02-23 Time 14:39 Rev Time 0.00
Received By medwards Date 2022-02-23 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By ccole Date 2020-02-06 Time 12:48 Rev Time 0.00
Received By ccole Date 2020-02-06 Time 12:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-05 Cont ID  
Sent By ccole Date 2019-12-05 Time 16:02 Rev Time 0.00
Received By ccole Date 2019-12-05 Time 15:49 Sent To  
Notes
2019-12-05 16:19:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101061
 12/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M4, M5, & M6: REFER TO SECTION 809.2 FBC EX
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES PER TABLE 403.3.1.1 FBC M .
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M5: PROVIDE AN EQUIPMENT SCHEDULE FOR THE AIR SUPPLY
 FAN- SECTION 107.2.1 WPB.
  
 3) M5: PROVIDE A GRAVITY OR MOTORIZED DAMPER FOR THE
 O/A INLET- SECTION C403.2.4.3 FBC EC.
  
 4) M5: SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL.
 PRODUCT APPROVAL AND/OR MIAMI-DADE NOA FOR THE LOUVERS-
 SECTION 401.5 FBC M AND RULE 9N-3 FAC.
  
 5) M5: PROVIDE MECHANICAL EXHAUST VENTILATION FOR THE
 TOILET ROOM PER SECTION 1203.5.2.1 FBC B AND TABLE
 403.3.1.1 FBC M.
  
 6) PLEASE SHOW COMPLIANCE WITH SECTION 309.1 FBC M
 PRINTED BELOW:
 INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE
 PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS
 CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT
 LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) ABOVE
 FLOOR ON THE DESIGN HEATING DAY. THE INSTALLATION OF
 PORTABLE SPACE HEATERS SHALL NOT BE USED TO ACHIEVE
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1.INTERIOR SPACES WHERE THE PRIMARY PURPOSE IS NOT
 ASSOCIATED WITH HUMAN COMFORT.
 2.GROUP F, H, S AND U OCCUPANCIES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-24 Cont ID  
Sent By jwitmer Date 2022-05-24 Time 07:52 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-04 Cont ID  
Sent By jleahy Date 2022-03-04 Time 16:33 Rev Time 0.00
Received By jleahy Date 2022-03-04 Time 16:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-12-13 Cont ID  
Sent By shill Date 2019-12-13 Time 07:37 Rev Time 0.00
Received By shill Date 2019-12-13 Time 07:29 Sent To  
Notes
2019-12-13 07:32:52EMAILED [email protected] AND
 [email protected] RE: SELF CERRTIFIED
 SIGNATURE; PROVISO, FUTURE SUBMITTALS WILL HAVE 3RD
 PARTY ISSUED DIGITAL SIGNATURE
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-24 Cont ID  
Sent By asangele Date 2022-02-24 Time 13:04 Rev Time 0.00
Received By asangele Date 2022-02-24 Time 13:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-26 Cont ID  
Sent By rcaranci Date 2019-11-26 Time 13:43 Rev Time 0.00
Received By ajones Date 2019-11-26 Time 13:43 Sent To  
Notes
***NONE***