Plan Review Details - Permit 19100970
Plan Review Stops For Permit 19100970
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2019-12-03 Cont ID  
Sent By rmcdouga Date 2019-12-03 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2019-12-03 Time 16:29 Sent To  
Notes
2019-12-03 16:31:05LETTER OF ASBESTOS COMPLIANCE HAS BEEN RECEIVED FROM
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By rmcdouga Date 2019-12-10 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2019-12-10 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-06 Cont ID  
Sent By rmcdouga Date 2019-11-06 Time 17:40 Rev Time 0.00
Received By rmcdouga Date 2019-11-06 Time 17:40 Sent To I
Notes
2019-11-06 17:40:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN THE
 SUBJECT LINE.
  
 2) THE PAPER PLANS THAT WERE SUBMITTED ARE DIGITALLY
 SIGNED AND SEALED BY THE ARCHITECT AND THE ENGINEER.
 ONLY ELECTRONICALLY SUBMITTED PLANS ARE ALLOWED TO BE
 SIGNED DIGITALLY. PLANS SUBMITTED ON PAPER ARE REQUIRED
 TO HAVE ORIGINAL HANDWRITTEN SIGNATURES.
 2A) ENGINEERS: FAC 61G15-23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS. ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH MUST
 BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2B) ARCHITECTS: 61G1-16.003 USE OF SEAL.
 (1) THE PERSONAL SEAL, SIGNATURE AND DATE OF THE
 ARCHITECT OR INTERIOR DESIGNER SHALL APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD AND SHALL BE CONSTRUED TO OBLIGATE
 HIS PARTNERS OR HIS CORPORATION. A CORPORATE SEAL ALONE
 IS INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY
 AND SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
  
 3) THE PLANS ARE REQUIRED TO BE REVIEWED AND APPROVED
 BY CITY PLACE. THERE STAMP IS REQUIRED ON THE PLANS.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-18 Cont ID  
Sent By cpuell Date 2019-12-18 Time 09:58 Rev Time 0.00
Received By cpuell Date 2019-11-27 Time 14:36 Sent To  
Notes
2019-12-02 14:36:18RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-06 Cont ID  
Sent By rmcdouga Date 2019-11-06 Time 17:40 Rev Time 0.00
Received By rmcdouga Date 2019-10-18 Time 13:41 Sent To  
Notes
2019-10-21 13:42:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-12-17 Cont ID  
Sent By eschneid Date 2019-12-17 Time 16:12 Rev Time 0.25
Received By eschneid Date 2019-12-17 Time 16:10 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-29 Cont ID  
Sent By eschneid Date 2019-10-29 Time 14:00 Rev Time 0.25
Received By eschneid Date 2019-10-29 Time 14:00 Sent To B
Notes
2019-10-29 14:02:56FAILED
  
 1) THE CITYPLACE RETAIL LLC APPROVAL IS REQUIRED ON THE
 PLANS OR AS A SEPARATE LETTER REFERENCING THE PLANS.
  
 2) THE PLANS THEMSELVES MEET ZONING.
  
  