Plan Review Details - Permit 19100813
Plan Review Stops For Permit 19100813
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By dbattles Date 2019-11-20 Time 07:58 Rev Time 0.00
Received By dbattles Date 2019-11-20 Time 07:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-28 Cont ID  
Sent By dbattles Date 2019-10-28 Time 11:02 Rev Time 0.00
Received By dbattles Date 2019-10-28 Time 08:54 Sent To  
Notes
2019-10-28 13:32:45BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19100813
 REVIEWED: OCTOBER 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
  
 1) 107.5.3 FBC[AMENDED]PLEASE SHOW THE GENERATOR WITH
 ENCLOSURE IMPOSED ON A FLOOR PLAN TO SHOW HOW EGRESS
 WILL WORK. THE ENCLOSURE SHOWN ON THE GENERATOR
 SUBMITTAL IN PERMIT 19100815 SHOWS DIMENSIONS OF 10
 FEET WIDE BY 28 FOOT 4 INCHES LONG. THE SUBMITTAL ALSO
 SHOWS THE ACCESS DOORS ARE 4 FOOT OUTSWING.
 SHEET C-400 APPEARS TO SHOW OUTLNE WITH 3 FEET AROUND
 THE UNIT FOR ACCESS.
 IS THE INTENTION TO HAVE ACCESS DOORS SWING ALL THE WAY
 OPEN?
 PLEASE VERIFY THE SIZE OF ACCESS DOORS AND IF THEY WILL
 BE OBSTRUCTED FROM FULL OPEN BY THE MASONRY WALL.
  
 2) 107.2.1.1 FBC[AMENDED]PROVIDE PRODUCT APPROVAL FOR
 THE ROLLING DOOR ATTACHED TO WALL THAT IS BEING USED
 FOR ACCESS TO THE GENERATOR.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By rrossano Date 2019-11-20 Time   Rev Time 0.00
Received By rrossano Date 2019-11-20 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By rrossano Date 2019-11-05 Time   Rev Time 0.00
Received By rrossano Date 2019-11-05 Time   Sent To  
Notes
2019-11-05 15:15:501) SHOW PROPOSED DUMPSTER ENCLOSURE TO BE COMPLIANT
 WITH CITY OF WPB STANDARD DETAIL GC-8.
 2) PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 3) PLEASE RESPOND TO ALL COMMENTS IN WRITING.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX:
 (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-20 Cont ID  
Sent By cpuell Date 2019-11-20 Time 10:15 Rev Time 0.00
Received By cpuell Date 2019-11-14 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-05 Cont ID  
Sent By shill Date 2019-11-05 Time 18:09 Rev Time 0.00
Received By shill Date 2019-10-17 Time 13:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By dbattles Date 2019-11-20 Time 07:59 Rev Time 0.00
Received By dbattles Date 2019-11-20 Time 07:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-10-28 Cont ID  
Sent By dbattles Date 2019-10-28 Time 09:04 Rev Time 0.00
Received By dbattles Date 2019-10-28 Time 09:04 Sent To  
Notes
2019-10-28 09:05:04OK-INITIAL REVIEW SHEETS.
 IF ANY ADDITIONAL SHEETS ARE PROVIDED THEY WILL NEED TO
 BE DIGITALLY SIGNED.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By ajones Date 2019-11-20 Time 10:08 Rev Time 0.00
Received By ajones Date 2019-11-20 Time 10:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By avann Date 2019-11-05 Time 16:16 Rev Time 0.00
Received By ajones Date 2019-11-05 Time 16:16 Sent To  
Notes
2019-11-05 16:18:5911/5/19- FAILED. 1. IS PARKING BEING REMOVED REQUIRED
 PARKING? 2. A FIVE (5) FOOT LANDSCAPE BUFFER IS
 REQUIRED AROUND THE DUMPSTER AND GENERATOR ENCLOSURES.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]