Plan Review Details - Permit 19100760
Plan Review Stops For Permit 19100760 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-12-11 |
Time |
07:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-12-11 |
Time |
06:48 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-10-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-10-31 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-10-31 |
Time |
14:01 |
Sent To |
I |
|
Notes |
2019-10-31 13:32:11 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE TWO SETS OF A FLOOR PLAN THAT INDICATES THE | | LOCATION OF THE PROPOSED WALL AND DOOR. FBC CITY | | AMENDMENTS 107.2 | | | | 2) SHOW ON THE PLANS THAT THE NEW DOOR WILL COMPLY WITH | | FBC ACCESSIBILITY SECTION 404.2.4.1 MANEUVERING | | CLEARANCES THAT REQUIRE A MINIMUM OF 18" CLEARANCE ON | | THE PULL SIDE OF THE DOOR. | | | | 3) INDICATE THE EXIT SIGN LOCATIONS ON THE PLANS. FBC | | 1013.1 | | | | 4) FBC 602.2 TYPE I AND II CONSTRUCTION REQUIRES | | INTERIOR WALLS TO BE CONSTRUCTED OF NONCOMBUSTIBLE | | MATERIALS EXCEPT AS PERMITTED IN SECTION 603. THIS | | BUILDING IS TYPE I-B. SPECIFY THE MATERIALS THAT WILL | | BE USED TO CONSTRUCT THE WALL. | | | | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2019-12-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-12-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-12-03 |
Time |
15:30 |
Sent To |
B |
|
Notes |
2019-12-03 15:32:09 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS | | AND SHOP DRAWINGS. | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD. | | | | 4) EXIT HARDWARE SHALL COMPLY WITH NFPA 101, CH 7, | | MEANS OF EGRESS. | | | | 5) PROVIDE EXIT SIGNS AS REQUIRED FOR PATH OF TRAVEL TO | | AN EXIT. | | | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2019-10-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-10-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-10-21 |
Time |
11:53 |
Sent To |
B |
|
Notes |
2019-10-21 11:54:51 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS | | AND SHOP DRAWINGS. | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD. | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-12-11 |
Time |
07:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-11-26 |
Time |
12:57 |
Sent To |
|
|
Notes |
2019-11-27 12:57:25 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-10-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-10-31 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-10-15 |
Time |
14:49 |
Sent To |
|
|
Notes |
2019-10-16 14:49:21 | ROUTED TO FIRE INBOX |
|
|
|