Plan Review Stops For Permit 19100703 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-01-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-01-07 |
Time |
06:44 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-07 |
Time |
06:44 |
Sent To |
|
|
Notes |
2020-01-07 06:45:33 | SIGNED AND SEALED HARD COPIES WERE SUBMITTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-12-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-12-04 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-12-04 |
Time |
17:56 |
Sent To |
|
|
Notes |
2019-12-04 17:56:02 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE DRAWINGS IN ELECTRONIC FORMAT FROM THE DELEGATE | | ENGINEER, CHRISTOPHER STANTON, FOR THE STOREFRONT | | ASSEMBLIES DO NOT HIS DIGITAL SIGNATURE AS REQUIRED BY | | FS 471 & FAC 61G-15 | | | | 2) THE STOREFRONT DRAWINGS ARE REQUIRED TO BE REVIEWED | | AND APPROVED FOR COMPATIBILITY WITH THE DESIGN OF THE | | BUILDING IN WRITING BY THE DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE PER FBC 107.3.4. | | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL | | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE | | ENGINEER OF RECORD FOR REVIEW. | | | | 3) THE PRODUCT APPROVALS FOR THE STOREFRONTS AND THE | | EXTERIOR DOORS DO NOT HAVE THE ENGINEER'S REVIEW STAMP | | ON THEM. 107.3.4 PRODUCT APPROVALS. THOSE PRODUCTS | | WHICH ARE REGULATED BY FAC 61G20 SHALL BE REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-10-28 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-10-28 |
Time |
13:20 |
Sent To |
|
|
Notes |
2019-10-28 13:25:51 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE DRAWINGS ARE NOT DIGITALLY SIGNED BY THE | | ENGINEER. 61G15-23.003 PROCEDURES FOR PHYSICALLY | | SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR | | OTHER DOCUMENTS. | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | USED. | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-01-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-01-07 |
Time |
06:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-06 |
Time |
13:32 |
Sent To |
|
|
Notes |
2020-01-06 13:33:06 | SUBMITTAL ROUTED TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-12-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-12-04 |
Time |
17:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-11-22 |
Time |
10:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-10-28 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-10-15 |
Time |
11:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-01-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-01-07 |
Time |
06:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-01-07 |
Time |
06:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2019-12-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-12-04 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-12-04 |
Time |
17:56 |
Sent To |
|
|
Notes |
2019-12-04 17:59:29 | THE WINDOW COMPANY'S ENGINEER DID NOT DIGITALLY SIGN | | THE ELECTRONICALLY SUBMITTED PLANS AS REQUIRED. SEE | | BUILDING COMMENTS. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-10-28 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-10-28 |
Time |
13:26 |
Sent To |
|
|
Notes |
2019-10-28 13:28:47 | 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS. | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | USED. | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | |
|
|