Plan Review Details - Permit 19100678
Plan Review Stops For Permit 19100678
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-02 Cont ID  
Sent By jleahy Date 2019-12-02 Time 08:12 Rev Time 0.00
Received By jleahy Date 2019-12-02 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By jleahy Date 2019-11-05 Time 11:39 Rev Time 0.00
Received By jleahy Date 2019-11-05 Time 11:39 Sent To  
Notes
2019-11-05 11:48:14FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF THE WORK IS LOW PLEASE SUBMIT A SIGNED
 CONTRACT WITH THE CUSTOMER FOR THE WORK INCLUDING
 LABOR, AND FIXTURES.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-02 Cont ID  
Sent By jleahy Date 2019-12-02 Time 08:12 Rev Time 0.00
Received By jleahy Date 2019-11-19 Time 14:17 Sent To  
Notes
2019-11-20 14:17:24RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-05 Cont ID  
Sent By jleahy Date 2019-11-05 Time 11:48 Rev Time 0.00
Received By jleahy Date 2019-10-11 Time 13:17 Sent To  
Notes
2019-10-15 13:17:47ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-11-27 Cont ID  
Sent By jroach Date 2019-11-27 Time 11:29 Rev Time 0.00
Received By jroach Date 2019-11-27 Time 11:29 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-10-29 Cont ID  
Sent By jroach Date 2019-10-29 Time 12:04 Rev Time 0.00
Received By jroach Date 2019-10-29 Time 12:04 Sent To E
Notes
2019-10-29 12:05:15ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10.29.2019
 PERMIT NO.: 19100678
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED] - PHOTOMETRIC PLANS ARE DIFFICULT TO
 READ AND IDENTIFY THE LOCATIONS WHERE THE REPLACEMENTS
 FIXTURES ARE BEING INSTALLED. PLEASE CLEARLY HIGHLIGHT
 ALL LOCATIONS.
  
 2. [ NOT SATISFIED] - THE PHOTOMETRIC LEVELS SHALL BE
 IDENTIFIED AT THE PROPERTY LINE. LEVELS SHALL NOT
 EXCEED 0.5 FOOTCANDLES AT THE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-25 Cont ID  
Sent By jroach Date 2019-10-25 Time 09:48 Rev Time 0.00
Received By jroach Date 2019-10-25 Time 09:48 Sent To Z
Notes
2019-10-25 09:48:24ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10.25.2019
 PERMIT NO.: 19100678
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PHOTOMETRIC PLANS ARE DIFFICULT TO READ AND IDENTIFY
 THE LOCATIONS WHERE THE REPLACEMENTS FIXTURES ARE BEING
 INSTALLED. PLEASE CLEARLY HIGHLIGHT ALL LOCATIONS.
  
 2. THE PHOTOMETRIC LEVELS SHALL BE IDENTIFIED AT THE
 PROPERTY LINE. LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES
 AT THE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved