Plan Review Details - Permit 19100586
Plan Review Stops For Permit 19100586
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-10 Cont ID  
Sent By jgomez Date 2020-02-10 Time 15:34 Rev Time 0.00
Received By jgomez Date 2020-02-10 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By jgomez Date 2020-01-14 Time 17:33 Rev Time 0.00
Received By jgomez Date 2020-01-14 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By jgomez Date 2019-11-15 Time 14:02 Rev Time 0.00
Received By jgomez Date 2019-11-15 Time 08:09 Sent To  
Notes
2019-11-15 14:02:00RESTAURANT REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS NEED THE CITY PLACE STAMP ON ALLL DRAWINGS AS
 REQUIRED BY CITY POLICY FOR ALL WORK IN CITY PLACE.
  
 2- SHEET A1.1.1:
 A) PLAN KEY NOTE #8 CALLS FOR GLASS IN EXISTING
 STOREFRONT THAT IS PAINTED BLACK TO BE REPLACED WITH
 NEW CLEAR GLASS TO MATCH EXISTING. DESIGNER OF RECORD
 NEED TO PROVIDE MORE SPECIFICATIONS FOR THE TYPE OF
 GLASS TO BE REPLACED.
 SEC. 602.2 FBC-EXISTING BUILDING AND SPECIFY ALL THE
 WIND DESIGN CRITERIA REQUIRED BY SEC. 1603.1.4
 FBC-BUILDING.
  
 B) CLEARLY IDENTIFY IF GLAZING IS LOCATED IN A
 HAZARDOUS LOCATION AND PROVIDE SPECIFICATIONS. SEC.
 602.2 FBC-EXISTING BUILDING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-02-18 Cont ID  
Sent By jpearson Date 2020-02-18 Time 08:50 Rev Time 0.00
Received By jleahy Date 2020-02-18 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-01-15 Cont ID  
Sent By jpearson Date 2020-01-15 Time 14:49 Rev Time 0.00
Received By jpearson Date 2020-01-15 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-11-14 Cont ID  
Sent By jpearson Date 2019-11-14 Time 13:30 Rev Time 0.00
Received By jpearson Date 2019-11-14 Time 12:41 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-02-12 Cont ID  
Sent By pleduc Date 2020-02-12 Time   Rev Time 0.00
Received By pleduc Date 2020-02-12 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By pleduc Date 2020-01-14 Time   Rev Time 0.00
Received By pleduc Date 2020-01-14 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-11-15 Cont ID  
Sent By pleduc Date 2019-11-15 Time   Rev Time 0.00
Received By pleduc Date 2019-11-15 Time 11:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-01-15 Cont ID  
Sent By gjohnson Date 2020-01-15 Time 13:21 Rev Time 0.00
Received By gjohnson Date 2020-01-15 Time 13:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-18 Cont ID  
Sent By jleahy Date 2020-02-18 Time 08:56 Rev Time 0.00
Received By jleahy Date 2020-02-06 Time 14:56 Sent To  
Notes
2020-02-07 14:56:42C07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-22 Cont ID  
Sent By hmoser Date 2020-01-22 Time 10:56 Rev Time 0.00
Received By hmoser Date 2020-01-09 Time 13:22 Sent To  
Notes
2020-01-17 16:15:53TO HM DESK
  
2020-01-10 13:22:50C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-15 Cont ID  
Sent By jgomez Date 2019-11-15 Time 14:02 Rev Time 0.00
Received By jgomez Date 2019-10-10 Time 14:53 Sent To  
Notes
2019-11-14 16:22:09ROUTED TO JGOMEZ
2019-10-10 14:53:16C11

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-02-11 Cont ID  
Sent By hmoser Date 2020-02-11 Time 10:12 Rev Time 0.00
Received By hmoser Date 2020-02-11 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-01-22 Cont ID  
Sent By cmontell Date 2020-01-22 Time 10:55 Rev Time 0.00
Received By hmoser Date 2020-01-22 Time 10:51 Sent To I
Notes
2020-01-22 10:55:34REVISION DENIED
 REFER TO SECTION 309.1 SPACE HEATING SYSTEMS.
 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By hmoser Date 2019-11-14 Time 14:31 Rev Time 0.00
Received By cmontell Date 2019-11-14 Time 14:31 Sent To P
Notes
2019-11-14 14:32:22MISSING PG M.1.1.1 ON 2ND SET OF PLANS
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-15 Cont ID  
Sent By jesmith Date 2020-01-15 Time 13:20 Rev Time 0.00
Received By gjohnson Date 2020-01-15 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By tklarge Date 2019-11-14 Time 16:18 Rev Time 0.00
Received By jesmith Date 2019-11-14 Time 15:56 Sent To  
Notes
2019-11-14 16:18:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. ADDRESS ON THE PLANS DO NOT MATCH ADDRESS ON THE
 PERMIT APPLICATION OR THE ADDRESS ON THE NARRATIVE. IS
 THIS UNIT 232 OR 236? PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
 2. REGARDING PLAN SHEET P3.1.1 AND P2.1.1, SANITARY KEY
 NOTE 10, IN ACCORDANCE WITH THE PROVISIONS OF FBC PL
 CHAPTER 7, CHAPTER 8 AND CHAPTER 11, THE FLOOR DRAINS
 AND ANY WASTE DISCHARGED INTO THEM SHALL CONNECT TO
 SANITARY NOT STORM DRAINS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19100586 550 S ROSEMARY AVE
 MP 19050710

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-14 Cont ID  
Sent By eschneid Date 2020-02-14 Time 15:44 Rev Time 0.25
Received By eschneid Date 2020-02-14 Time 15:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-15 Cont ID  
Sent By eschneid Date 2020-01-15 Time 16:29 Rev Time 0.50
Received By eschneid Date 2020-01-15 Time 15:52 Sent To  
Notes
2020-01-15 16:37:09FAILED
  
 SHEET M1.1.2 SHOWS A NEW MAU UNIT (NOTE 1) STATING THAT
 IT IS FOR REFERENCE ONLY AND THAT IT IS SHOWN ON THE
 HOOD DRAWINGS, WHICH ARE NOT INCLUDED IN THIS PACKAGE.
 IN ACCORDANCE WITH THE CITYPLACE DRI REQUIREMENTS,
 PROVIDE DRAWINGS TO VERIFY THAT THE NEW MAU MEETS THE
 DRI SCREENING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]