Plan Review Details - Permit 19100552
Plan Review Stops For Permit 19100552
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By dbattles Date 2019-11-05 Time 13:32 Rev Time 0.00
Received By dbattles Date 2019-11-05 Time 13:32 Sent To  
Notes
2019-11-05 13:31:56PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By dbattles Date 2019-11-05 Time 13:29 Rev Time 0.00
Received By dbattles Date 2019-11-04 Time 16:31 Sent To  
Notes
2019-11-05 13:29:52BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19100552
 REVIEWED: NOVEMBER 5, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 107.5.3 FBC[AMENDED]PLEASE ADD EXPOSURE CATEGORY TO
 SHEET S-101.
  
 2) 107.5.3 FBC[AMENDED]SHEET A-3.01 AND A-3.02 STATE
 THAT THE ROOF DECK WILL BE 2X6 WOOD STRUCTURAL T&G
 DECKING. STRUCTURAL SHEETS CALL FOR PLYWOOD DECKING.
 PLEASE CO-ORDINATE ROOF DECKING TO MATCH SINCE THERE IS
 A DISCREPENCY WITH WEIGHT.
  
 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS AT CUPOLA AND FIBERGLASS DOOR, OR INDICATE THAT
 THEY WILL BE A DEFERRED SUBMITTAL.
  
 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 METAL ROOFING AND FLAT ROOF, OR INDICATE THAT ROOFING
 WILL BE A DEFERRED SUBMITTAL.
  
 5) 1507.4.2 FBC[B] DECK SLOPE. MINIMUM SLOPES FOR METAL
 ROOF PANELS SHALL COMPLY WITH THE FOLLOWING:
 1. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOF PANELS WITHOUT APPLIED LAP SEALANT SHALL BE THREE
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (25-PERCENT
 SLOPE).
 2. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOF PANELS WITH APPLIED LAP SEALANT SHALL BE ONE-HALF
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (4-PERCENT SLOPE).
 LAP SEALANTS SHALL BE APPLIED IN ACCORDANCE WITH THE
 APPROVED MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 3. THE MINIMUM SLOPE FOR STANDING-SEAM METAL ROOF PANEL
 SYSTEMS SHALL BE ONE-QUARTER UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).
 -ADD NOTE 1-3 THAT APPLIES TO THE SLOPE BEING PROPOSED
 ON METAL ROOFING.
  -PROVIDE ENGINEERING FOR FLAT ROOFING ENHANCED NAILING
 IF APPLICABLE.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-28 Cont ID  
Sent By jleahy Date 2019-10-28 Time 10:03 Rev Time 0.00
Received By jleahy Date 2019-10-28 Time 10:03 Sent To  
Notes
2019-10-28 10:09:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PAGES NOT INCLUDED IN DOWNLOAD JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-10-21 Cont ID  
Sent By fstal Date 2019-10-21 Time   Rev Time  
Received By fstal Date 2019-10-21 Time   Sent To  
Notes
2019-10-21 13:58:21PERMIT# 19100552: DIGITAL PLAN REVIEW PASS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-05 Cont ID  
Sent By dbattles Date 2019-11-05 Time 14:19 Rev Time 0.00
Received By dbattles Date 2019-10-18 Time 09:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-11-05 Cont ID  
Sent By dbattles Date 2019-11-05 Time 13:32 Rev Time 0.00
Received By dbattles Date 2019-11-05 Time 13:30 Sent To  
Notes
2019-11-05 13:32:51NO ADDED SQ. FOOTAGE AND NO CHANGE OF OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-11-05 Cont ID  
Sent By ccole Date 2019-11-05 Time 10:12 Rev Time 0.00
Received By ccole Date 2019-11-04 Time 17:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-11-05 Cont ID  
Sent By dbattles Date 2019-11-05 Time 14:19 Rev Time 0.00
Received By dbattles Date 2019-11-05 Time 14:19 Sent To  
Notes
2019-11-05 14:23:12DRAWINGS ARE NOT DIGITALLY SIGNED AND SEALED.
  
 PLACE A DIGITALLY CREATED IMAGE OF YOUR SEAL AND THE
 FOLLOWING SENTENCES WHERE AN ORIGINAL SIGNATURE WOULD
 APPEAR IF THE ITEM WERE BEING PHYSICALLY SIGNED, DATED
 AND SEALED. THE SENTENCES CAN BE PART OF THE DIGITAL
 SIGNATURE CUSTOM APPEARANCE AVAILABLE IN THE SIGNING
 TOOL, OR THEY CAN BE PLACED ON THE DOCUMENT OUTSIDE OF
 THE DIGITAL SIGNATURE BLOCK. THIS ITEM HAS BEEN
 ELECTRONICALLY SIGNED AND SEALED BY [LICENSEE, RA, OR
 LS] ON THE DATE AND/OR TIME STAMP SHOWN USING A DIGITAL
 SIGNATURE. NOTE: PRINTED COPIES OF THIS DOCUMENT ARE
 NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST
 BE VERIFIED ON ANY ELECTRONIC COPIES.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  
2019-10-10 16:23:1810/10/19 ONE SET OF HARD COPY PLANS LOCATED IN LARGE
 DENIED "TBD6"

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-30 Cont ID  
Sent By llouie Date 2019-10-30 Time   Rev Time  
Received By llouie Date 2019-10-30 Time   Sent To  
Notes
***NONE***