Plan Review Details - Permit 19100548
Plan Review Stops For Permit 19100548
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By cpuell Date 2022-08-01 Time 10:37 Rev Time 0.00
Received By cpuell Date 2022-08-01 Time 10:37 Sent To  
Notes
2022-08-01 10:37:44WORK TO BE DONE ON THE NORTH DOWNSTAIRS UNIT WITH THE
 ADDRESS OF 416 42ND ST # A, UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-06-09 Cont ID  
Sent By cpuell Date 2021-06-09 Time 16:56 Rev Time 0.00
Received By cpuell Date 2021-06-09 Time 16:56 Sent To  
Notes
2021-06-09 16:57:17PREVIOUS COMMENTS NOT ADDRESSED, PLEASE CONTACT
 [email protected] TO DISCUSS ADDRESSING ISSUES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-09 Cont ID  
Sent By cpuell Date 2021-03-09 Time 15:07 Rev Time 0.00
Received By cpuell Date 2021-03-09 Time 15:07 Sent To  
Notes
2021-03-09 15:07:53PARCEL CURRENTLY HAS 4 UNITS IDENTIFIED, PLEASE SPECIFY
 THE UNITS EFFECTED BY THIS PERMIT. PLEASE EMAIL
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2022-08-15 Cont ID  
Sent By jgomez Date 2022-08-15 Time 13:50 Rev Time 0.00
Received By jgomez Date 2022-08-12 Time 18:14 Sent To  
Notes
2022-08-15 13:51:50RESIDENTIAL (R3) ALTERATION SEVENTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #:19100548 416 42ND ST # A
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 505 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 ADDITIONS SEC. 507 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 A)FORM R405-2020 SUBMITTED IS THE WRONG FORM. THIS
 PROJECT IS REVIEWED UNDER THE 2017 CODE. PROVIDE
 CORRECT FORM R405-2017 AS DONE ON PREVIOUS SUBMITTAL.
  
 B) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF
 FORM THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE,
 AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 C)CONDITIONED FLOOR AREA ON PAGE ONE DOESN'T MATCH AREA
 SHOWN ON PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: IT IS NOT CLEAR IF THE ENERGY CALCULATIONS ARE
 DONE FOR ENTIRE FIRST FLOOR OR JUST THE REBUILT FIRST
 FLOOR BEDROOM. REVISE AS REQUIRED.
 ENERGY CALCULATIONS MAY DONE JUST FOR THE NEW
 CONSTRUCTION OF THE BEDROOM AS SHOWN ON PLANS TO AVOID
 MORE CONFLICTS/DELAYS.
  
 D)REVISE WALL TYPE INFORMATION ON PAGE ONE. COORDINATE
 WITH ITEM #1(B) ABOVE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) REVISE BLOCKS, SPACES, FLOORS, ROOF AND ATTIC
 INFORMATION ON PAGE 2. COORDINATE WITH ITEM #1(B)
 ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE CEILING, WALL, DOORS, WINDOWS AND HEATING
 SYSTEM INFORMATION ON PAGE 3. COORDINATE WITH ITEM
 #1(B) ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC-
 ENERGY CONSERVATION.
  
 2- OK.
  
  
 NOTE:
 ARCHITECTURAL PLANS SUBMITTED ARE OLD PLANS. THEY WERE
 SIGNED AND SEALED BY THE ARCHITECT OF RECORD ON
 7/21/20. THE FOLLOWING COMMENTS ARE BASED ON THESE OLD
 PLANS.
  
  
 3- SHEET 1.1: NEED TO SPECIFY MIN. 5/8" ROOF SHEATHING
 AS REQUIRED BY SEC. TABLE R803.1 FBC-RESIDENTIAL.
 NOTE: THIS COMMENT APPLIES TO TYPICAL WOOD FRAME WALL
 SECTION ON SHEET 3.1 ALSO.
  
 4- OK
  
 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1
 ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2)
 FBC-RESIDENTIAL AND HEIGHT AND EXPOSURE ADJUSTMENT
 TABLE R301.2(3) FBC-RESIDENTIAL. REVISE AS REQUIRED.
 USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA
 AS REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR
 PROVIDE CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED
 ON THE LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHT
 AND BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 6- SHEET 3.1: NEED TO SPECIFY TOP AND THE BOTTOM
 CONNECTORS AT THE STRUCTURAL FRAME MEMBERS OF THE
 SECTION AT WOOD FRAME IN-FILL DETAIL. SEC. R301.1
 FBC-RESIDENTIAL.
  
 7- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)OUTSWING ENTRY DOOR AND ENLARGED BEDROOM EXTERIOR
 DOOR AS SHOWN ON PLANS.
 DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT
 APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS
 THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO
 COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5
 ABOVE.
  
 B)HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT APPROVALS
 DON'T HAVE IMPACT GLAZING.
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE.
  
 C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (NOTE:
 INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS
 TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. DESIGNER
 OF RECORD NEEDS TO PROVIDE THE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE STAIRS.
 ALSO, DESIGNER OF RECORD NEEDS TO PROVIDE THE DETAILS
 AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 HANDRAILS AND GUARDRAILS AS REQUIRED BY TABLE R301.5,
 SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT HANDRAIL/GUARDRAIL SHOP DRAWINGS ARE
 TO CONFIRM THAT DESIGN DETAILS AND SPECIFICATIONS ARE
 MET.
  
 10- ORIGINAL STAIRWAY WAS LOCATED IN THE MIDDLE OF THE
 BUILDING. NEW STAIRWAY IS LOCATED ON THE EXTERIOR SIDE
 OF THE BUILDING. ARCHITECT OF RECORD NEEDS TO SHOW HOW
 THE SECOND FLOOR WAS AFFECTED TO ALLOW THE NEW
 STAIRWAY. SHOW ALL REQUIRED CONSTRUCTION TO ALLOW NEW
 STAIRWAY TO SERVE THE SECOND FLOOR ENTRY TO THE
 APARTMENT. SHOW ALL EXTERIOR CONSTRUCTION SHOWN ON THE
 WEST ELEVATION. ON SHEET 2.1. SEC. 107.2.1 CITY
 AMENDMENTS. THIS WAS REMOVED TO ALLOW FOR FIRST FLOOR
 BEDROOM RECONSTRUCTION.
  
 11- ROOF FRAMING PLAN AND TYPICAL WALL SECTION DON'T
 SPECIFY THE CONNECTION OF THE 2X12 ROOF JOIST. SPECIFY
 CONNECTOR. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 12- TYPICAL WALL SECTION ON SHEET 3.1:
 A) SPECIFY CEILING INSULATION. SEC. R103.2.1 FBC-ENERGY
 CONSERVATION.
  
 B)SPECIFIED VENT 6"X26" SCREEN VENT AT 6'-0" DOESN'T
 PROVIDE CROSS VENTILATION. THIS IS A FLAT ROOF. REVISE
 AS REQUIRED. SEC. R806 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 15:43 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 13:35 Sent To  
Notes
2021-06-24 15:44:41RESIDENTIAL (R3) ADDITION/ALTERATION, SIXTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT # 19100548
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
  
 NOTE:
 FORM R405-2020 SUBMITTED NOW IS THE WRONG FORM. THIS
 PROJECT IS REVIEWED UNDER THE 2017 CODE. PROVIDE
 CORRECT FORM R405-2017 AS DONE ON PREVIOUS SUBMITTAL.
  
 REPEAT COMMENT (THREE TIMES):
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 B) OK.
 C) OK.
  
 REPEAT COMMENT.
 D) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4
 TO MATCH PLANS. THIS IS FOR ENTIRE FIRST FLOOR. SEE
 PLANS/ELEVATIONS AND REVISE AS REQUIRED. CHECK WINDOWS
 OVERHANG AND SEPARATION ALSO. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)OK.
  
 REPEAT COMMENT.
 F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC-
 ENERGY CONSERVATION.
  
 NEW COMMENTS:
 G) ITEM #3 IS INCORRECT. COORDINATE WITH ITEM 1(G)
 ABOVE AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 2- OK.
 3- OK
 4- OK.
 5- OK.
 6- OK
  
 ORIGINAL COMMENT.
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT.
 DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT
 APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS
 THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO
 COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5
 ABOVE.
  
 B)OK
  
 C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT
 APPROVALS DON'T HAVE IMPACT GLAZING.
 PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING
  
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE
  
 REPEAT COMMENT:
 D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS
 TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THIS STAIRWAY
 OR CLARIFY IF SUBMITTING THIS INFORMATION UNDER A
 SEPARATE PERMIT.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 DESIGNER OF RECORD TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS OR INDICATE IF THIS WORK IS
 UNDER A SEPARATE PERMIT.
  
 10- OK.
  
 11- OK.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-03-12 Cont ID  
Sent By jgomez Date 2021-03-12 Time 12:04 Rev Time 0.00
Received By jgomez Date 2021-03-11 Time 17:41 Sent To  
Notes
2021-03-12 12:05:42RESIDENTIAL (R3) ADDITION/ALTERATION, FIFTH BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT # 19100548
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
  
 REPEAT COMMENT.
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 REPEAT COMMENT.
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 REPEAT COMMENT.
 C) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 IS
 INCORRECT. IT DOESN'T MATCH PLANS. SEE PLANS AND REVISE
 AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 REPEAT COMMENT.
 D) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4
 TO MATCH PLANS. THIS IS FOR ENTIRE FIRST FLOOR. SEE
 PLANS/ELEVATIONS AND REVISE AS REQUIRED. CHECK WINDOWS
 OVERHANG AND SEPARATION ALSO. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 3 OF 4
 DOESN'T MATCH PLANS/ELEVATIONS. PLANS SHOW FLAT ROOF NO
 HIP. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD SUBMITTED SEC. R405.4.3 FBC-
 ENERGY CONSERVATION.
  
 2- OK.
 3- OK
 4- OK.
  
 ORIGINAL COMMENT:
 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1
 ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2)
 FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE
 R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE
 THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS
 REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE
 CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE
 LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHT AND
 BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 REVISE DESIGN PRESSURES AGAIN. PRESSURES GIVEN ARE
 TAKING FROM TABLE R301.2(2) FBC-RESIDENTIAL. THIS
 BUILDING IS IN EXPOSURE "C". NEED TO MULTIPLE PRESSURES
 BY COEFFICIENT SHOWN ON TABLE R301.2(3) FBC-RESIDENTIAL
 BASED ON THE HEIGHT OF THE BUILDING. REVISE AS
 REQUIRED. NOTE: THIS IS A TWO STORY BUILDING.
  
 6- OK
  
 ORIGINAL COMMENT.
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 DESIGN PRESSURES (+/- 35) SHOWN ON DOOR FLORIDA PRODUCT
 APPROVAL FL11861-R8 SUBMITTED DON'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 NEED TO PROVIDE PRODUCT APPROVAL FOR DOOR THAT MEETS
 THE CALCULATED DESIGN PRESSURES. NOTE: NEED TO
 COORDINATE WITH REVISED DESIGN PRESSURES ON ITEM #5
 ABOVE.
  
 B)SINGLE HUNG WINDOWS. OK
  
 C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT
 APPROVALS DON'T HAVE IMPACT GLAZING.
 PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING
  
 RESPONSE:
 SWING DOOR PRODUCT APPROVAL SUBMITTED DON'T HAVE IMPACT
 GLAZING. COORDINATE WITH ITEM # 7.A) ABOVE.
  
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE
  
 D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. CONTRACTOR DIDN'T
 EVEN SPECIFIED IF SUBMITTING LATER AS A DEFERRED
 SUBMITTAL.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- FLOOR PLANS AND ELEVATIONS STATE THAT THE NEW STAIRS
 TO THE SECOND FLOOR ARE TO BE DONE BY OTHERS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THIS STAIRWAY
 OR CLARIFY IF SUBMITTING THIS INFORMATION UNDER A
 SEPARATE PERMIT.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- ALL DRAWINGS SUBMITTED ARE NOT SIGNED AND SEALED BY
 THE ARCHITECT OF RECORD. ARCHITECT TO SIGN AND SEAL
 DRAWING AS REQUIRED BY 61G1-16.001FAC AND CHAPTER 481
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
 11- ARCHITECT TO REVISE TYPICALLY WALL SECTION ON SHEET
 3.1.
 SCREEN VENTS SPACED AT 6'-0" O.C. DON'T PROVIDE CROSS
 VENTILATION AS REQUIRED BY SEC. R806 FBC-RESIDENTIAL.
 THIS IS A FLAT ROOF WITH SOLID 2X12 ROOF JOISTS.
 TYPICALLY, A CONTINUOUS VENT IS INSTALLED IN THIS TYPE
 OF ROOFS. REVISE AS REQUIRED. SPECIFY VENT TYPE AND
 SIZE THAT WILL PROVIDE REQUIRED CROSS VENTILATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-09-29 Cont ID  
Sent By cthroop Date 2020-09-29 Time 13:38 Rev Time 0.00
Received By cthroop Date 2020-09-29 Time 11:39 Sent To  
Notes
2020-09-29 13:36:57PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 4TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BELOW ARE THE COMMENTS FROM THE 2ND REVIEW. NO 3RD
 REVIEW WAS PERFORMED DUE TO FEES NOT BEING PAID.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 RESIDENTIAL (R3) ALTERATION LEVEL 3, SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ****IMPORTANT*****
 ENERGY CALCULATIONS NEED TO BE SIGNED/DATED BY THE
 OWNER PRIOR TO PASSING THE BUILDING REVIEW WITH
 PROVISO.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
  
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C) ITEM #1 ON PAGE 1 OF 4 IS INCORRECT. THIS IS NOT NEW
 CONSTRUCTION. THIS IS EXISTING BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 IS
 INCORRECT. REVISE AS REQUIRED. CLARIFY WHY THE AREAS
 DON'T MATCH AREAS SHOWN ON THE PROPERTY APPRAISER
 WEBSITE IF THE FOOTPRINT SEEMS TO BE THE SAME. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4
 TO MATCH PLANS. REVISE OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NEW COMMENT: 4TH REVIEW
  
 ENERGY SUBMITTAL MISSING FROM SUBMITTAL.
  
 2- OK.
  
 3- OK
  
 4- OK.
  
 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1
 ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2)
 FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE
 R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE
 THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS
 REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE
 CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE
 LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHTT AND
 BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 REVISE DESIGN PRESSURES AGAIN. PRESSURES GIVEN ARE
 TAKING FROM TABLE R301.2(2) FBC-RESIDENTIAL. THIS TABLE
 IS BASED ON BUILDING EXPOSURE "B". THIS BUILDING IS IN
 EXPOSURE "C". NEED TO MULTIPLE PRESSURES BY COEFFICIENT
 SHOWN ON TABLE R301.2(3) FBC-RESIDENTIAL BASED ON THE
 HEIGH OF THE BUILDING.. REVISE AS REQUIRED. NOTE: THIS
 IS A TWO STORY BUILDING.
  
 NEW COMMENT: 4TH REVIEW
  
 PRESSURES FROM TABLE R301.2(2) HAVE NOT BEEN ADJUSTED
 BY CO-EFFIEIENT SHOWN ON TABLE R301.2(3)
  
 6- OK
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
 NOTE: NOA 16-0617.02 SUBMITTED IS FOR SLIDING GLASS
 DOORS. THERE ARE NOT SLIDING GLASS DOORS ON THIS
 PROJECT.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T
 SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 B)SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T
 SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT
 APPROVALS DON'T HAVE IMPACT GLAZING.
 PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T
 SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE
  
 D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NEW COMMENT: 4TH REVIEW
  
 PRODUCT APPROVALS ARE MISSING FROM SUBMITTAL
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-14 Cont ID  
Sent By jgomez Date 2020-01-14 Time 11:29 Rev Time 0.00
Received By jgomez Date 2020-01-14 Time 11:14 Sent To  
Notes
2020-01-14 11:30:36PLAN REVIEW FEES ARE NO PAID. REVIEW NO DONE. UNTIL
 FEES ARE PAID. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By jgomez Date 2019-12-10 Time 15:16 Rev Time 0.00
Received By jgomez Date 2019-12-10 Time 10:15 Sent To  
Notes
2019-12-10 10:47:23RESIDENTIAL (R3) ALTERATION LEVEL 3, SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT # 19100548
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ****IMPORTANT*****
 ENERGY CALCULATIONS NEED TO BE SIGNED/DATED BY THE
 OWNER PRIOR TO PASSING THE BUILDING REVIEW WITH
 PROVISO.
  
  
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C) ITEM #1 ON PAGE 1 OF 4 IS INCORRECT. THIS IS NOT NEW
 CONSTRUCTION. THIS IS EXISTING BUILDING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4 IS
 INCORRECT. REVISE AS REQUIRED. CLARIFY WHY THE AREAS
 DON'T MATCH AREAS SHOWN ON THE PROPERTY APPRAISER
 WEBSITE IF THE FOOTPRINT SEEMS TO BE THE SAME. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4
 TO MATCH PLANS. REVISE OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 2- OK.
  
 3- OK
  
 4- OK.
  
 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1
 ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2)
 FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE
 R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE
 THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS
 REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE
 CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE
 LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHTT AND
 BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 REVISE DESIGN PRESSURES AGAIN. PRESSURES GIVEN ARE
 TAKING FROM TABLE R301.2(2) FBC-RESIDENTIAL. THIS TABLE
 IS BASED ON BUILDING EXPOSURE "B". THIS BUILDING IS IN
 EXPOSURE "C". NEED TO MULTIPLE PRESSURES BY COEFFICIENT
 SHOWN ON TABLE R301.2(3) FBC-RESIDENTIAL BASED ON THE
 HEIGH OF THE BUILDING.. REVISE AS REQUIRED. NOTE: THIS
 IS A TWO STORY BUILDING.
  
 6- OK
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
 NOTE: NOA 16-0617.02 SUBMITTED IS FOR SLIDING GLASS
 DOORS. THERE ARE NOT SLIDING GLASS DOORS ON THIS
 PROJECT.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T
 SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 B)SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T
 SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT
 APPROVALS DON'T HAVE IMPACT GLAZING.
 PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR DIDN'T
 SPECIFIED IF SUBMITTING LATER AS A DEFERRED SUBMITTAL.
  
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE
  
 NEW COMMENT BASED ON REVISED PLANS.
 D) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-24 Cont ID  
Sent By jgomez Date 2019-10-24 Time 17:26 Rev Time 0.00
Received By jgomez Date 2019-10-24 Time 09:14 Sent To  
Notes
2019-10-24 17:27:05RESIDENTIAL (R3) ALTERATION LEVEL 3, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 908 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- PLANS SHOW REMOVING ONE EXTERIOR DOOR FROM THE
 BEDROOM. NONE OF THE PROPOSED WINDOWS SEEM TO COMPLY
 WITH THE EGRESS REQUIREMENTS. SEC. 702.5 FBC-BUILDING.
 REVISE AS REQUIRED. AND, CLEARLY SPECIFY THE ACTUAL
 SIZE OF THE PROPOSED EGRESS WINDOW AND PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE SPECIFIED
 WINDOW COMPLIES WITH ALL THE EGRESS REQUIREMENTS.
  
 3- SHEET 1.1:
 A)BASED ON DRAWINGS SUBMITTED, THIS IS AN ALTERATION
 LEVEL 3 NOT LEVEL 2. SEE SEC. 505 FBC-EXISTING
 BUILDING. REVISE INFORMATION GIVEN UNDER "PROJECT
 DATA".
  
 B) REVISE THE "PLYWOOD SHEATHING NAILING SCHEDULE".
 NEED TO SPECIFY RING SHANK NAILS AS REQUIRED BY SEC.
 801.3 FBC-EXISTING BUILDING AND SEC. R803.2.3.1
 FBC-RESIDENTIAL.
 NOTE: NEED TO COORDINATE THIS INFORMATION WITH
 INFORMATION SHOWN ON THE "TYPICAL WOOD FRAME WALL
 SECTION" ON SHEET 3.1 TO AVOID CONFLICTS/DELAYS.
  
 C) REVISE THE "A" DIMENSION SPECIFIED ON THE PLAN SHOWN
 ABOVE THE "PLYWOOD SHEATHING NAILING SCHEDULE". NEED TO
 SPECIFY 4 FEET MIN. AS REQUIRED BY FIGURE R301.2(7)
 FBC-RESIDENTIAL AND SEC. 801.3 FBC-EXISTING BUILDING
  
 4- PLANS SHOW NEW ROOF WITH A ROOF PITCH OF 2.5 PER
 FOOT. NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT AS
 REQUIRED BY SEC. R905.2.2 FBC-RESIDENTIAL. SEC. 801.3
 FBC-EXISTING BUILDING
  
 5- DOOR AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET 2.1
 ARE TOO LOW IF THEY ARE DONE USING TABLE R301.2(2)
 FBC-RESIDENTIAL AS SPECIFIED ON PLANS. SEE TABLE
 R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED. USE
 THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA AS
 REQUIRED BY FOOTNOTE "B" OF THE SAME TABLE OR PROVIDE
 CALCULATIONS FOR THE ACTUAL WINDOW SIZE BASED ON THE
 LOCATION (INTERIOR/END ZONE), MEAN ROOF HEIGHT AND
 BUILDING EXPOSURE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 6- SHEET 3.1:
 A) NEED TO SPECIFY ALL THE CONNECTORS AT THE BOTTOM OF
 ALL STRUCTURAL FRAME MEMBERS OF THE TYPICAL WINDOW
 OPENING IN FRAME WALL DETAIL. SEC. 801.3 FBC-EXISTING
 BUILDING. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) NEED TO SPECIFY ALL THE CONNECTORS AT THE STRUCTURAL
 FRAME MEMBERS OF THE SECTION AT WOOD FRAME IN-FILL
 DETAIL. SEC. 801.3 FBC-EXISTING BUILDING. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: CLARIFY/REVISE THE FINISH MATERIALS ON THE
 INTERIOR AND EXTERIOR SIDE OF THE WALL. DETAIL PROVIDE
 IS SPECIFYING 5/8" DRYWALL ON BOTH SIDES. REVISE AS
 REQUIRED.
  
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
 NOTE: NOA 16-0617.02 SUBMITTED IS FOR SLIDING GLASS
 DOORS. THERE ARE NOT SLIDING GLASS DOORS ON THIS
 PROJECT.
  
 B)SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) HURRICANE SHUTTERS IF DOORS/WINDOWS PRODUCT
 APPROVALS DON'T HAVE IMPACT GLAZING.
 PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL. SEC. 801.3 FBC-EXISTING BUILDING
  
 NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE
 INSTALLATION SCHEDULE AS REQUIRED BY CITY
 IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY
 SAMPLE
  
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2022-08-15 Cont ID  
Sent By jleahy Date 2022-08-15 Time 11:50 Rev Time 0.00
Received By jleahy Date 2022-08-15 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 15:00 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-03-15 Cont ID  
Sent By jleahy Date 2021-03-15 Time 16:38 Rev Time 0.00
Received By jleahy Date 2021-03-15 Time 16:33 Sent To  
Notes
2021-03-15 16:39:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ALL ELECTRICAL PAGES ARE LOCKED I CAN NOT REVIEW A
 LOCKED PAGE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By jleahy Date 2020-09-21 Time 12:49 Rev Time 0.00
Received By jleahy Date 2020-09-21 Time 12:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-20 Cont ID  
Sent By jpearson Date 2019-12-20 Time 14:22 Rev Time 0.00
Received By jpearson Date 2019-12-20 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-31 Cont ID  
Sent By jpearson Date 2019-10-31 Time 14:20 Rev Time 0.00
Received By jpearson Date 2019-10-31 Time 06:37 Sent To  
Notes
2019-10-31 14:20:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION STATES THIS IS A FULL RENOVATION.
 THERE ARE NO ELECTRICAL PLANS FOR THE SECOND FLOOR.
 PROVIDE FULL SET OF PLANS FOR REVIEW. WPB FBC 107.2.1
 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 4. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2022-08-08 Cont ID  
Sent By ccole Date 2022-08-08 Time 07:22 Rev Time 0.00
Received By ccole Date 2022-08-08 Time 07:08 Sent To  
Notes
2022-08-08 07:24:05GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 14:39 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 14:39 Sent To  
Notes
2021-06-22 14:40:04GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-03-16 Cont ID  
Sent By abelisle Date 2021-03-16 Time 17:34 Rev Time 0.00
Received By abelisle Date 2021-03-16 Time 17:34 Sent To  
Notes
2021-03-16 17:35:43SEPERATE GAS PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2022-08-15 Cont ID  
Sent By jgomez Date 2022-08-15 Time 13:55 Rev Time 0.00
Received By jgomez Date 2022-08-02 Time 16:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 15:50 Rev Time 0.00
Received By jgomez Date 2021-06-08 Time 13:00 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-03-17 Cont ID  
Sent By medwards Date 2021-03-17 Time 07:11 Rev Time 0.00
Received By medwards Date 2021-03-08 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-09-29 Cont ID  
Sent By cthroop Date 2020-09-29 Time 13:42 Rev Time 0.00
Received By cthroop Date 2020-09-15 Time 14:36 Sent To  
Notes
2020-01-21 08:42:59VERIFY PLAN REVIEW FEES ARE PAID PRIOR TO ROUTING FOR
 REVIEW S.HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-14 Cont ID  
Sent By jgomez Date 2020-01-14 Time 11:33 Rev Time 0.00
Received By jgomez Date 2020-01-03 Time 13:23 Sent To I
Notes
2020-01-06 13:23:55RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-20 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-05 Time 15:29 Sent To  
Notes
2019-12-06 15:29:58R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-10-31 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-10 Time 16:15 Sent To  
Notes
2019-10-10 16:15:17R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-08-15 Cont ID  
Sent By jgomez Date 2022-08-15 Time 09:15 Rev Time 0.00
Received By jgomez Date 2022-08-15 Time 09:15 Sent To  
Notes
2022-08-15 09:15:58IMPACT FEES
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 15:49 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 15:48 Sent To  
Notes
2021-06-24 15:49:32IMPACT FEES
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2022-08-09 Cont ID  
Sent By medwards Date 2022-08-09 Time 10:01 Rev Time 0.00
Received By medwards Date 2022-08-09 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2021-06-16 Cont ID  
Sent By medwards Date 2021-06-16 Time 10:28 Rev Time 0.00
Received By medwards Date 2021-06-16 Time 10:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-03-10 Cont ID  
Sent By medwards Date 2021-03-10 Time 10:40 Rev Time 0.00
Received By medwards Date 2021-03-10 Time 10:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-09-17 Cont ID  
Sent By medwards Date 2020-09-17 Time 07:44 Rev Time 0.00
Received By medwards Date 2020-09-17 Time 07:37 Sent To  
Notes
2020-09-17 07:45:27PLEASE RESPOND TO COMMENTS FOR 3RD REVIEW DATED
 09/16/2020.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 13:48 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 13:15 Sent To  
Notes
2020-09-16 13:52:28PLEASE SEE 1ST CYCLE MECHANICAL REVIEWERS NOTES. I DO
 NOT SEE THE INFORMATION ASKED FOR IN CYCLE 1 REVIEW.
 PLEASE SUBMIT THE ENERGY AND MECHANICAL UNIT SIZING
 CALCULATIONS. PLEASE ALSO PROVIDE SPECIFICATIOONS FOR
 THE MINI SPLIT SYSTEMS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By jgomez Date 2019-12-10 Time 15:45 Rev Time 0.00
Received By jgomez Date 2019-12-10 Time 15:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-24 Cont ID  
Sent By jgomez Date 2019-10-24 Time 17:48 Rev Time 0.00
Received By jgomez Date 2019-10-24 Time 17:48 Sent To  
Notes
2019-10-24 17:50:22RESIDENTIAL (R3) ALTERATION LEVEL 3 MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE COMPLETE EQUIPMENT LOAD CALCULATIONS. SEC.
 801.3 FBC-EXISTING BUILDING AND SEC. R403.7 FBC-ENERGY
 CONSERVATION.
 NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS
 REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop P PLUMBING
Rev No 7 Status P Date 2022-08-08 Cont ID  
Sent By ccole Date 2022-08-08 Time 07:22 Rev Time 0.00
Received By ccole Date 2022-08-08 Time 06:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 14:40 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 14:40 Sent To  
Notes
2021-06-22 14:40:2906/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-03-16 Cont ID  
Sent By abelisle Date 2021-03-16 Time 17:34 Rev Time 0.00
Received By abelisle Date 2021-03-16 Time 17:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-09-21 Cont ID  
Sent By lcrespo Date 2020-09-21 Time 09:59 Rev Time 0.00
Received By lcrespo Date 2020-09-21 Time 09:59 Sent To  
Notes
2020-09-21 09:59:4809/21/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-09-16 Cont ID  
Sent By lcrespo Date 2020-09-16 Time 08:28 Rev Time 0.00
Received By lcrespo Date 2020-09-16 Time 08:27 Sent To  
Notes
2020-09-16 08:28:4609/16/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By jesmith Date 2019-12-19 Time 14:57 Rev Time 0.00
Received By jesmith Date 2019-12-19 Time 14:57 Sent To  
Notes
2019-12-19 14:57:11PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By gjohnson Date 2019-10-22 Time 13:46 Rev Time 0.00
Received By gjohnson Date 2019-10-22 Time 08:15 Sent To  
Notes
2019-10-22 13:47:151ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DETAILED SCOPE OF PLUMBING WORK BEING DONE
 PLAN IS UNCLEAR. PER WPB AMEND TO FBC 107.2.1
  
 2. BY INCLUDING THE SANITARY ISOMETRIC DRAWING IT
 APPEARS THAT THE SANITARY PIPING SYSTEM IS BEING
 REPLACED IF YOU ONLY MOVING THE TOILET A ISOMETRIC
 DRAWING IS NOT REQUIRED PLEASE CORRECT THE FOLLOWING
 CODE VIOLATIONS ON THE ISOMETRIC.
 A)THE KITCHEN BRANCH DRAIN CAN NOT CONNECT TO BATHROOM
 GROUP SHALL CONNECT DOWN STREAM. PER FBC RES P3108.1
 B)SHOWER SHALL CONNECT TO BATHROOM GROUP AND BE VENTED
 BY LAVATORY OR BE INDIVIDUALLY VENTED.PER FBC RES
 P3108.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 2022-08-15 Cont ID  
Sent By jgomez Date 2022-08-15 Time 13:52 Rev Time 0.00
Received By jgomez Date 2022-08-15 Time 13:51 Sent To  
Notes
2022-08-15 13:52:49ROOFING REVIEW:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
 ************************
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 15:49 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 15:49 Sent To  
Notes
2021-06-24 15:50:431- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
 ************************
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2021-03-12 Cont ID  
Sent By jgomez Date 2021-03-12 Time 11:48 Rev Time 0.00
Received By jgomez Date 2021-03-12 Time 11:47 Sent To  
Notes
2021-03-12 11:50:591- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL)
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. CONTRACTOR DIDN'T
 EVEN SPECIFIED IF SUBMITTING LATER AS A DEFERRED
 SUBMITTAL.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
 ************************
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2020-09-29 Cont ID  
Sent By cthroop Date 2020-09-29 Time 13:43 Rev Time 0.00
Received By cthroop Date 2020-09-29 Time 13:43 Sent To  
Notes
2020-09-29 13:44:51PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PRODUCT APPROVALS ARE MISSING FROM
 SUBMITTAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-12-20 Cont ID  
Sent By jgomez Date 2019-12-20 Time 14:24 Rev Time 0.00
Received By jgomez Date 2019-12-20 Time 14:24 Sent To  
Notes
2019-12-20 14:24:37OWENS CORNING SHINGLES NOA 17-1211.02.
  
 TAMKO UNDERLAYMENT NOA 17-0531.01

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-10-24 Cont ID  
Sent By jgomez Date 2019-10-24 Time 17:22 Rev Time 0.00
Received By jgomez Date 2019-10-24 Time 17:22 Sent To  
Notes
2019-10-24 17:24:59OWENS CORNING SHINGLES NOA 17-1211.02.
  
 TAMKO UNDERLAYMENT NOA 17-0531.01

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-09 Cont ID  
Sent By jgomez Date 2022-08-09 Time 12:59 Rev Time 0.00
Received By jgomez Date 2022-08-09 Time 10:51 Sent To  
Notes
2022-08-09 13:01:22HARD COPY DRAWINGS 1.1, 2.1, 3.1 AND 4.1 HAVE
 ARCHITECT'S EMBOSSED SEAL AND WET SIGNATURE. DRAWING
 C.1 HAS DIGITAL SIGNATURE. JG.
2022-08-09 10:13:36 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-16 Cont ID  
Sent By medwards Date 2021-06-16 Time 10:28 Rev Time 0.00
Received By medwards Date 2021-06-16 Time 10:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-12 Cont ID  
Sent By jgomez Date 2021-03-12 Time 11:46 Rev Time 0.00
Received By jgomez Date 2021-03-12 Time 11:46 Sent To  
Notes
2021-03-12 11:07:361-SURVEY NEEDS SEAL/SIGNATURE.
  
 2- ALL DRAWINGS SUBMITTED ARE NOT SIGNED AND SEALED BY
 THE ARCHITECT OF RECORD. ARCHITECT TO SIGN AND SEAL
 DRAWING AS REQUIRED BY 61G1-16.001FAC AND CHAPTER 481
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-29 Cont ID  
Sent By cthroop Date 2020-09-29 Time 13:39 Rev Time 0.00
Received By cthroop Date 2020-09-29 Time 11:39 Sent To  
Notes
2020-09-29 13:42:35PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A DIGITAL SIGNATURE OF THE DESIGN
 PROFESSIONAL IS REQUIRED.
  
 EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF
 (OR MAIL) ONE PAPER ORIGINAL WITH A WET SEAL AND
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop Z ZONING
Rev No 7 Status F Date 2022-08-12 Cont ID  
Sent By llouie Date 2022-08-12 Time   Rev Time 0.00
Received By llouie Date 2022-08-12 Time   Sent To  
Notes
2022-08-12 14:57:49** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 [10/11/2019, 12/16/2019, 1/8/2020, 9/8/2020, 3/12/2021
 AND 6/22/2021 REPEAT COMMENT - PLEASE NOTE THAT A
 LANDSCAPE PERMIT MUST BE SUBMITTED PRIOR TO ZONING'S
 APPROVAL OF THIS PERMIT. THIS COMMENT HAS NOT BEEN
 ADDRESSED ON MULTIPLE REVIEWS.]
  
  
 NOTES:
  
 * VOICE MESSAGE LEFT FOR KRISTEN CASTANO OF ACTION
 CONSTRUCTION GROUP AND FOLLOW UP EMAIL MADE TO
 [email protected] TO NOTIFY CONTRACTOR OF REQUIREMENT
 FOR A LANDSCAPE PERMIT PRIOR ZONING APPROVAL BACK ON
 3/2021.
  
 * LANDSCAPE PERMIT REQUIRED PRIOR TO ZONING APPROVAL -
 HOLD PLACED ON THE C.O.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS = 1 RESIDENCE (SOUTH
 BUILDING) + DUPLEX (NORTH BUILDING)).
  
 *SCOPE OF WORK: INTERIOR RENOVATIONS AND INFILL/REPLACE
 WINDOWS AND/OR DOORS TO NORTH BUILDING (DUPLEX) ON
 FIRST FLOOR ONLY.
 .
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 6 Status F Date 2021-06-22 Cont ID  
Sent By llouie Date 2021-06-22 Time   Rev Time 0.00
Received By llouie Date 2021-06-22 Time   Sent To  
Notes
2021-06-22 16:31:29** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 [10/11/2019, 12/16/2019, 1/8/2020, 9/8/2020 AND
 3/12/2021 REPEAT COMMENT - PLEASE NOTE THAT A LANDSCAPE
 PERMIT MUST BE SUBMITTED PRIOR TO ZONING'S APPROVAL OF
 THIS PERMIT. THIS COMMENT HAS NOT BEEN ADDRESSED ON
 MULTIPLE REVIEWS.]
  
  
 NOTES:
  
 * VOICE MESSAGE LEFT FOR KRISTEN CASTANO OF ACTION
 CONSTRUCTION GROUP AND FOLLOW UP EMAIL MADE TO
 [email protected] TO NOTIFY CONTRACTOR OF REQUIREMENT
 FOR A LANDSCAPE PERMIT PRIOR ZONING APPROVAL BACK ON
 3/2021.
  
 * LANDSCAPE PERMIT REQUIRED PRIOR TO ZONING APPROVAL -
 HOLD PLACED ON THE C.O.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS = 1 RESIDENCE (SOUTH
 BUILDING) + DUPLEX (NORTH BUILDING)).
  
 *SCOPE OF WORK: INTERIOR RENOVATIONS AND INFILL/REPLACE
 WINDOWS AND/OR DOORS TO NORTH BUILDING (DUPLEX) ON
 FIRST FLOOR ONLY.
 .
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 5 Status F Date 2021-03-12 Cont ID  
Sent By llouie Date 2021-03-12 Time 09:11 Rev Time 0.00
Received By llouie Date 2021-03-12 Time 09:11 Sent To  
Notes
2021-03-12 09:12:35** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 [10/11/2019, 12/16/2019, 1/8/2020 AND 9/8/2020 REPEAT
 COMMENT - PLEASE NOTE THAT A LANDSCAPE PERMIT MUST BE
 SUBMITTED PRIOR TO ZONING'S APPROVAL OF THIS PERMIT.
 THIS COMMENT HAS NOT BEEN ADDRESSED ON MULTIPLE
 REVIEWS.]
  
  
 NOTES:
  
 * VOICE MESSAGE LEFT FOR KRISTEN CASTANO OF ACTION
 CONSTRUCTION GROUP AND FOLLOW UP EMAIL MADE TO
 [email protected] TO NOTIFY CONTRACTOR OF REQUIREMENT
 FOR A LANDSCAPE PERMIT PRIOR ZONING APPROVAL.
  
 * LANDSCAPE PERMIT REQUIRED PRIOR TO ZONING APPROVAL -
 HOLD PLACED ON THE C.O.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS = 1 RESIDENCE (SOUTH
 BUILDING) + DUPLEX (NORTH BUILDING)).
  
 *SCOPE OF WORK: INTERIOR RENOVATIONS AND INFILL/REPLACE
 WINDOWS AND/OR DOORS TO NORTH BUILDING (DUPLEX) ON
 FIRST FLOOR ONLY.
 .
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 4 Status F Date 2020-09-18 Cont ID  
Sent By llouie Date 2020-09-18 Time   Rev Time 0.00
Received By llouie Date 2020-09-18 Time   Sent To  
Notes
2020-09-18 12:55:39** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 [10/11/2019, 12/16/2019 AND 1/8/2020 REPEAT COMMENT -
 PLEASE NOTE THAT A LANDSCAPE PERMIT MUST BE SUBMITTED
 PRIOR TO ZONING'S APPROVAL OF THIS PERMIT]
  
  
 NOTES:
  
 * VOICE MESSAGE LEFT FOR KRISTEN CASTANO OF ACTION
 CONSTRUCTION GROUP AND FOLLOW UP EMAIL MADE TO
 [email protected] TO NOTIFY CONTRACTOR OF REQUIREMENT
 FOR A LANDSCAPE PERMIT PRIOR ZONING APPROVAL.
  
 * LANDSCAPE PERMIT REQUIRED PRIOR TO ZONING APPROVAL -
 HOLD PLACED ON THE C.O.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS = 1 RESIDENCE (SOUTH
 BUILDING) + DUPLEX (NORTH BUILDING)).
  
 *SCOPE OF WORK: INTERIOR RENOVATIONS AND INFILL/REPLACE
 WINDOWS AND/OR DOORS TO NORTH BUILDING (DUPLEX) ON
 FIRST FLOOR ONLY.
 .
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-01-08 Cont ID  
Sent By llouie Date 2020-01-08 Time   Rev Time 0.00
Received By llouie Date 2020-01-08 Time   Sent To B
Notes
2020-01-08 09:18:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. [10/11/2019 AND
 12/16/2019 REPEAT COMMENT - PLEASE NOTE THAT A
 LANDSCAPE PERMIT MUST BE SUBMITTED PRIOR TO ZONING'S
 APPROVAL OF THIS PERMIT]
  
  
 NOTES:
  
 * VOICE MESSAGE LEFT FOR KRISTEN CASTANO OF ACTION
 CONSTRUCTION GROUP AND FOLLOW UP EMAIL MADE TO
 [email protected] TO NOTIFY CONTRACTOR OF REQUIREMENT
 FOR A LANDSCAPE PERMIT PRIOR ZONING APPROVAL.
  
 * LANDSCAPE PERMIT REQUIRED PRIOR TO ZONING APPROVAL -
 HOLD PLACED ON THE C.O.
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS = 1 RESIDENCE (SOUTH
 BUILDING) + DUPLEX (NORTH BUILDING)).
  
 *SCOPE OF WORK: INTERIOR RENOVATIONS AND INFILL/REPLACE
 WINDOWS AND/OR DOORS TO NORTH BUILDING (DUPLEX) ON
 FIRST FLOOR ONLY.
 .
 * ZONE: SF7
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-12-16 Cont ID  
Sent By llouie Date 2019-12-16 Time   Rev Time 0.00
Received By llouie Date 2019-12-13 Time   Sent To  
Notes
2019-12-16 10:12:14** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS
 MISSING FROM THE APPLICATION. PLEASE PROVIDE.
 [10/11/2019 REPEAT COMMENT]
  
 2.) SCOPE OF WORK SPECIFIES "FULL RENOVATION," BUT IT
 DOES NOT SPECIFY WHICH BUILDING ON THE PROPERTY IS
 SUBJECT TO THE SCOPE OF WORK. PLEASE ADDRESS IN WRITING
 AND IN THE REQUIRED SITE PLAN. [10/11/2019 MODIFIED
 COMMENT]
  
 3.) PROJECT LOCATION MAP IS NOT CORRECT ON SHEET C.1.
 [10/11/2019 MODIFIED COMMENT]
  
 4.) PROVIDE A SITE PLAN SHOWING ALL EXISTING AND
 PROPOSED (I.E. A/C UNIT) STRUCTURES ON THE PROPERTY.
 PLEASE NOTE THAT THE SETBACK DIMENSIONS FROM ALL
 PROPOSED NEW STRUCTURES SHALL ALSO BE PROVIDED IN THE
 SITE PLAN. [10/11/2019 REPEAT COMMENT]
  
 5.) THE PROJECT DATA ON SHEET 1.1 INDICATES THAT THERE
 IS A COVERED PATIO, BUT IT IS NOT ILLUSTRATED IN THE
 FLOOR PLAN. ARE THERE ANY PROPOSED CHANGES? PLEASE
 CLARIFY. [10/11/2019 REPEAT COMMENT]
  
 6.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. [10/11/2019 REPEAT
 COMMENT - PLEASE NOTE THAT A LANDSCAPE PERMIT MUST BE
 SUBMITTED PRIOR TO ZONING'S APPROVAL OF THIS PERMIT]
  
  
 NOTES:
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS, 1 RESIDENCE + DUPLEX)
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-11 Cont ID  
Sent By llouie Date 2019-10-11 Time   Rev Time 0.00
Received By llouie Date 2019-10-11 Time   Sent To  
Notes
2019-10-11 12:40:47** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 MISSING FROM THE APPLICATION. PLEASE PROVIDE.
  
 2.) SCOPE OF WORK SPECIFIES "FULL RENOVATION," BUT IT
 DOES NOT SPECIFY WHICH BUILDING ON THE PROPERTY IS
 SUBJECT TO THE SCOPE OF WORK.
  
 3.) PROJECT LOCATION MAP IS MISSING ON SHEET C.1
  
 4.) PROVIDE A SITE PLAN SHOWING ALL EXISTING AND
 PROPOSED (I.E. NEW A/C UNIT) STRUCTURES ON THE
 PROPERTY. PLEASE NOTE THAT SETBACK DIMENSIONS FROM ALL
 PROPOSED NEW STRUCTURES SHALL ALSO BE PROVIDED IN THE
 SITE PLAN.
  
 5.) DISCREPANCIES DETECTED IN THE BUILDING
 CALCULATIONS. THE PROJECT DATA ON SHEET 1.1 INDICATES
 THAT THERE IS A COVERED PATIO, BUT IT IS NOT
 ILLUSTRATED IN THE FLOOR PLAN. ARE THERE ANY PROPOSED
 CHANGES? PLEASE CLARIFY.
  
 6.) THE VALUE OF THE CONSTRUCTION ($60,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($106,046) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * GREEN CARD #7-191 (3 UNITS, 1 RESIDENCE + DUPLEX)
  
 * ZONE: SF7
  