2020-05-31 08:24:31 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19100523 |
| ADD: 311 N. SAPODILLA AVE. (DUMPSTER ENCLOSURE) |
| CONT: TBD/ TO BE DETERMINED |
| TEL:??? CONTACT: PIERRE KETLENE |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUN. MAY 31/2020 |
| ACTION: DENIED |
| |
| 1) THIS PROJECT BEING PERMITTED IS FOR THE BUILDING OF |
| A DUMPSTER ENCLOSURE. THERE ARE SHEETS THAT WERE |
| SUBMITTED THAT HAVE NO BEARING ON THE DUMPSTER |
| ENCLOSURE. |
| SHEET 319A THE PROPOSED FLOOR PLAN. |
| SHEET 401S THIS DESIGN CRITERIA AS LISTED IS FOR THE |
| MAIN BUILDING THAT WOULD BE REMODELED, DESIGN IS FOR AN |
| ENCLOSED BUILDING, IMPORTANCE FACTOR, AND ROOF |
| PRESSURES THAT ARE GIVEN ARE ALL FOR AN ENCLOSED |
| BUILDING. NOTHING IS FOR THE DUMPSTER ENCLOSURE. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) SHEET 333A DETAIL # 6 SHOWS DETAIL B, C, & D |
| ELEVATION WITH A 6 INCH BLOCK WALL AND A 8 INCH |
| CONCRETE CAP WITH AN 2 INCH OFFSET TO THE EXTERIOR |
| SIDE. SHEET 406S4.0 DETAIL # 1 SECTION AT TRASH |
| ENCLOSURE SHOWS THE WALL WITH AN 8 INCH CONCRETE CAP |
| AND 8 INCH BLOCK WALL. SHEET 403S3.0 ALSO STATES THE |
| BLOCK WALL IS TO BE 8 INCH CONCRETE BLOCK? |
| DISCREPANCY IN PLANS, PLEASE CORRECT THE DISCREPANCY. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) SHEET 406S4.0 DETAIL 1 ALSO SHOWS THE FOUNDATION BUT |
| NO SIZE NOR STEEL REINFORMENT INFORMATION IS GIVEN NOR |
| A IDENTIFICATION MARKER TO NAME THE FOOTER. SHEET |
| 403S3.0 DOES HAVE FOOTER SIZE AND STEEL SIZING AND |
| PLACEMENT BUT WITHOUT THE FOOTER IDENTIFICATION TAG |
| WHICH IS TO BE INSTALLED? 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 4) THE SAME HOLD TRUE ABOUT THE VERTICAL REINFORCEMENT |
| THERE ARE VARIOUS DETAILS BUT THEY DO NOT PROVIDE THEY |
| ARE TO BE USED AS PART OF THE DUMPSTER ENCLOSURE |
| DETAILS. SIZE OF STEEL, PLACEMENT OF STEEL LAP FROM THE |
| FOUNDATION ARE NOT GIVEN IN THE DETAILS (IDENTIFICATION |
| MARKERS). 107.2.1.2 ADDITIONAL INFORMATION REQUIRED. |
| 2017 FBC-B 2103.4 REINFORCEMENT FOR CMU. |
| |
| 5) THE SHEET 333A DETAIL 6 NOTES THE DOUBLE GATES ARE |
| TO BE 13 FEET WIDE BY 5 FEET HIGH LOUVERED ALUMINUM |
| GATES ON 2X2 ALUMINUM TUBE. WITHIN THE FILE FOLDER IS A |
| MIAMI-DADE NOA 19-0731.04 LOUVERED DOOR PRODUCT |
| APPROVAL, IS THERE TO BE A DOOR TO BE CUT INTO ONE OF |
| THE SIDE WALLS? 107.2.1.2 AGAIN ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |