Plan Review Details - Permit 19100519
Plan Review Stops For Permit 19100519
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date 2022-03-14 Cont ID  
Sent By aoliver Date 2022-03-14 Time 13:30 Rev Time 0.00
Received By aoliver Date 2022-03-14 Time 13:30 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 14:54 Sent To  
Notes
2020-08-07 14:58:16NOT LOOKING FOR AN ASBESTOS SURVEY. JUST NEED A LETTER
 FROM THE CONTRACTOR PER THE FOLLOWING COMMENT = PLEASE
 PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR,
 ON LETTERHEAD, STATING THAT THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE
 FOLLOWED, AND THAT NOTIFICATION WILL BE GIVEN TIMELY.
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 07:57 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 07:57 Sent To  
Notes
2020-06-30 07:57:33PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-06-01 Cont ID  
Sent By rmcphers Date 2020-06-01 Time 13:34 Rev Time 0.00
Received By rmcphers Date 2020-06-01 Time 13:34 Sent To  
Notes
2020-06-01 13:35:11PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By dbattles Date 2019-12-09 Time 08:10 Rev Time 0.00
Received By dbattles Date 2019-12-09 Time 08:10 Sent To  
Notes
2019-12-09 08:17:08THE ASBESTOS SURVEY IS OK TO BE IN THE PERMIT, BUT THE
 CITY LOOKS FOR VERIFICATION THAT THIS INFORMATION IS
 SUPPLIED TO THE PBC HEALTH DEPARTMENT. PLEASE SUPPLY A
 LETTER AS STATED BELOW TO STATE CONPLIANCE WITH PBC
 HEALTH DEPARTMENT REQUIREMENTS.
  
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 14:53 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 07:48 Sent To  
Notes
2020-06-30 07:55:21REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 NO CHANGES SINCE LAST REVIEW -
 1) DRAWING 308LS SHOWS BUILDING CONSTRUCTION TYPE AS
 (IB) - DRAWING G0.01 SHOWS BUILDING CONSTRUCTION TYPE
 AS (IIIA) - PLEASE CLARIFY.
 2) STRUCTURAL CALCULATIONS AND DRAWING (S1.0) SHOWS
 DESIGN WIND SPEED AS 169MPH - SHOULD BE 170MPH PER FBC
 WPB AMENDMENTS 120.1
 3) STRUCTURAL CALCULATIONS FOR THE DUMPSTER - DESIGN
 WIND SPEED USED IS 115MPH - SHOULD BE MIN. 150MPH PER
 FBC WPB AMENDMENTS 120.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-01 Cont ID  
Sent By rmcphers Date 2020-06-01 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2020-06-01 Time 09:40 Sent To  
Notes
2020-06-01 13:33:17REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING 308LS SHOWS BUILDING CONSTRUCTION TYPE AS
 (IB) - DRAWING G0.01 SHOWS BUILDING CONSTRUCTION TYPE
 AS (IIIA) - PLEASE CLARIFY.
 2) STRUCTURAL CALCULATIONS AND DRAWING (S1.0) SHOWS
 DESIGN WIND SPEED AS 169MPH - SHOULD BE 170MPH PER FBC
 WPB AMENDMENTS 120.1
 3) STRUCTURAL CALCULATIONS FOR THE DUMPSTER - DESIGN
 WIND SPEED USED IS 115MPH - SHOULD BE MIN. 150MPH PER
 FBC WPB AMENDMENTS 120.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By dbattles Date 2019-12-09 Time 15:42 Rev Time 0.00
Received By dbattles Date 2019-12-09 Time 08:05 Sent To  
Notes
2019-12-09 15:43:39BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19100519
 REVIEWED: DECEMBER 9, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 109.3 FBC[AMENDED]PLEASE PROVIDE COPY OF ESTIMATE
 PREPARED BY THE DESIGNER TO STATE HOW VALUE OF WORK WAS
 DETERMINED. VALUE SHOULD INCLUDE DESIGN COSTS,
 DEMOLITION AND ALL REMODEL WORK THAT IS INCLUDED IN
 THIS PERMIT.
  
 2) 402.2 FBC[A]PLEASE SHOW ACCESSIBLE ROUTE FROM THE
 ACCESSIBLE PARKING SPACE TO THE ENTRY BEING SERVED.
  
 3) 302.1 FBC[B] GENERAL. STRUCTURES OR PORTIONS OF
 STRUCTURES SHALL BE CLASSIFIED WITH RESPECT TO
 OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED IN THIS
 SECTION.
 PLEASE PROVIDE FURTHER BREAKDOWN OF EXTISTING VS
 PROPOSED. THIS WILL NEED PALM BEACH COUNTY IMPACT
 REVIEW FOR CHANGE OF OCCUPANCY AND THEY WILL NOT HAVE
 ENOUGH DATA TO DETERMINE CHANGE OF OCCUPANCY. STATE
 EXISTING USE, SQ. FOOTAGE EACH FLOOR AND PROPOSED USE
 AND SQ. FOOTAGE EACH FLOOR.
  
 4) CONSTRUCTION TYPE 1B IS BEING STATED ON SHEET 308
 LS. PLEASE SHOW HOW WALL TYPES MEET THAT CONSTRUCTION
 TYPE. EXTERIOR WALLS AT 2 HOURS, SHOW INTERIOR BEARING
 WALLS AT 2 HOURS IST FLOOR AND 1 HOUR WITH SECOND FLOOR
 PER TABLE 601 NOTE(A).
 TABLE 508.4 SEPARATION OF R2 FROM A2 FLOOR CONSTRUCTION
 NEEDS 2 HOUR RATING AND INFILL DETAILS SHOULD INCLUDE
 HOW THIS IS ACHIEVED.
  
 5) 456.3.2.2 FBC[B]PUBLIC BATHROOMS SHALL BE COMPLETELY
 ENCLOSED AND SHALL HAVE TIGHT-FITTING, SELF-CLOSING
 DOORS.
 ARE DOOR CLOSERS PROVIDED ON RESTROOMS?
  
 6) SHEET 319 A SHOWS VARIOUS CALL OUTS THAT FOR SHEET
 A6.01 TO A6.06 AND SHEET A7.02. I DON?T SEE THESE
 SHEETS OR THESE DETAIL ON OTHER SHEETS. PLEASE UPDATE
 CALLOUTS AND ADD DETAILS/SECTIONS TO MATCH.
 ALSO, PROVIDE STAGE DETAILS AND MATERIALS IN THE
 DETAILS/SECTIONS.
  
 7) 201.1.1 FBC[A]STAGE ACCESSIBILITY. WILL THE STAGE
 HAVE AN ACCESSIBLE RAMP? I DO NOT SEE EXEMPTION FOR
 ACCESS TO THE STAGE.
  
 PROVISOS:
 A) SEPARATE PERMITS REQUIRED FOR - LIGHT POLES/SITE
 LIGHTING, FIRE ALARM, FIRE SPRINKLER, LOW VOLTAGE,
 ACCESS, LANDSCAPING, IRRIGATION, PARKING LOT AND ALL
 OTHER ITEMS OTHER THAN BMEP
 B) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE PLANS
 AT FINAL STAMPING.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By jpearson Date 2020-06-03 Time 14:07 Rev Time 0.00
Received By jpearson Date 2020-06-03 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-22 Cont ID  
Sent By jpearson Date 2019-12-22 Time 14:32 Rev Time 0.00
Received By jpearson Date 2019-12-22 Time 14:31 Sent To  
Notes
2019-12-22 14:31:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-07 Cont ID  
Sent By pleduc Date 2020-05-07 Time   Rev Time 0.00
Received By pleduc Date 2020-05-05 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-12-17 Cont ID  
Sent By pleduc Date 2019-12-17 Time   Rev Time 0.00
Received By pleduc Date 2019-12-06 Time 12:54 Sent To  
Notes
2019-12-17 11:39:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 319A - THERE IS AN INDICATION OF DRY STORAGE
 UNDER THE SOUTH STAIR. THGERE IS NO STAIR DETAIL
 INDICATING THE REQUIRED SEPARATION OF THE STARIWELL.
  
 PER NFPA 101.
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE
 SPECIAL REQUIREMENTS OF 7.2.2, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.2.1.2.
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT
 SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2.
  
 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN
 EXIT
 ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER STAIRS,
 UNLESS
 OTHERWISE PERMITTED BY 7.2.2.5.3.2.
  
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS,
 PROVIDED THAT BOTH ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE
 SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM
 WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.)
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF
 COMBUSTIBLE OR
 FLAMMABLE LIQUIDS, OR OTHERWISE HAZARDOUS MATERIALS.
  
 PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF
 CONSTRUCTION.
  
  
 2) SHEET 319 A - THE NORTH STAIR DOES NOT INDICATE THE
 REQUIRED SEPARATION DETAIL AS NOTED IN # 1 ABOVE.
  
 PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF
 CONSTRUCTION.
  
  
  
 3) SHEET 319 A - THE IS A STAGE INDICATED.
  
 THERE ARE NO INDICATION OF THE CONSTRUCTION FEATURES OF
 THE STAGE.
  
 PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF
 CONSTRUCTION.
  
  
  
 4) SHEET 320 A - THERE ARE NO INDICATIONS OF DOOR
 HARDWARE WITHIN THE DOOR SCHEDULE.
  
 PLEASE REVIEW AND PROVIDE PER THE APPLICABLE OCCUPANCY
 CODE.
  
  
 5) SHEET 308 A - THERE IS AN INDICATION OF AN ASSEMBLY
 OCCUPNACY; HOWEVER, THERE ARE TWO RESIDENTIAL
 OCCUPANCIES.
  
 IS THIS A MIXED OR SEPARATED OCCUPANCY?
  
 PLEASE PROVIDE PER NFPA 101 CH 6, OCCUPANCY
 CLASSIFICATION.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING
 SHALL COMPLY
 WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN.
  
 PLEASE REVIEW AND PROVIDE APPLICABLE DETAILS OF
 CONSTRUCTION.
  
  
 6) SHEET 336 A - THE THREE MAIN EXIT DOORS TO THE
 ASSEMBLY AREA SHOW HARDWARE SET # 6. RIM CYLINDER,
 MORTISE DEVICE AND FLOOR STOP.
  
 THESE MAY NOT BE COMPLIANT WITH THE REQUIRED EXIT
 HARDWARE, PER NFPA 101, CH 12 & CH 7.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
  
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 PLEASE REVIEW AND CORRECT OF PROVIDE CODE COMPLIANT
 JUSTIFICATION.
  
  
 7) SHEET 319 A - THERE IS AN INDICATION OF A STAGE AND
 BAR IN THIS ASSEMBLY OCCUPANCY AND COULD BE CONSIDERED
 A NIGHCLUB
  
 PER NFPA 101, CH 12
  
 12.3.5 EXTINGUISHMENT REQUIREMENTS.
 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE
 FOLLOWING
 ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 9.7.1.1(1):
 (1) DANCE HALLS
 (2) DISCOTHEQUES
 (3) NIGHTCLUBS
 (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
  
 PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION OF JUSTIFY
 WITH DETAILED NARRATIVE AND CODE REFERNCES.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-06-08 Cont ID  
Sent By ccole Date 2020-06-08 Time 14:44 Rev Time 0.00
Received By ccole Date 2020-06-08 Time 14:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-06-01 Cont ID  
Sent By ccole Date 2020-06-01 Time 16:04 Rev Time 0.00
Received By ccole Date 2020-06-01 Time 13:02 Sent To  
Notes
2020-06-01 16:04:58 
 2ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 19100519
 6/1/2020
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW WERE NOT ADDRESSED- SEE
 BELOW.
  
 1) COMBUSTION AIR CALCULATIONS REQUIRED- SECTION 304.1
 FBC FG. INDICATE HOW THE AIR IS TO BE PROVIDED-
 INDOORS, OUTDOORS, OR MECHANICALLY.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES
 INCLUDING THE WATER HEATERS- SECTIONS 305.1 & 624.1 FBC
 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-12-12 Cont ID  
Sent By shill Date 2019-12-12 Time 17:18 Rev Time 0.00
Received By gjohnson Date 2019-12-09 Time 10:27 Sent To  
Notes
2019-12-12 17:18:57GAS COMMENTS
 1. COMBUSTION AIR CALC REQUIRED PER WPB AMEND TO FBC
 107.2.1
 2. MANUFACTURE SPECIFICATIONS FOR ALL GAS APPLIANCE PER
 WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 [email protected]
 561-805-6724

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By fmittner Date 2020-05-06 Time 15:23 Rev Time 0.00
Received By fmittner Date 2020-05-06 Time 15:23 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-12-11 Cont ID  
Sent By fmittner Date 2019-12-11 Time 11:55 Rev Time 0.00
Received By fmittner Date 2019-12-11 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-03-15 Cont ID  
Sent By aoliver Date 2022-03-15 Time 08:23 Rev Time 0.00
Received By aoliver Date 2022-03-14 Time 13:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2020-07-01 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 07:59 Rev Time 0.00
Received By rmcphers Date 2020-06-05 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-03 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-04 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-13 Cont ID  
Sent By lmarchan Date 2020-01-13 Time 10:48 Rev Time 0.00
Received By lmarchan Date 2019-11-14 Time 09:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2022-05-10 Cont ID  
Sent By lmarchan Date 2022-05-10 Time 10:34 Rev Time 0.00
Received By lmarchan Date 2022-03-14 Time 13:32 Sent To  
Notes
2022-05-09 16:13:40RECEIPT MU-2020-029346 - $20176.53 PAID
2022-03-14 13:33:043/14/22 EMAILED IMPACT FOR REVIEW AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-03-14 Cont ID  
Sent By rmcphers Date 2022-03-14 Time 13:32 Rev Time 0.00
Received By aoliver Date 2020-07-01 Time   Sent To  
Notes
2020-08-07 15:00:48PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
2020-07-01 08:18:237/1/20 SENT EMAIL TO IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By dbattles Date 2019-12-09 Time 08:37 Rev Time 0.00
Received By dbattles Date 2019-12-09 Time 08:37 Sent To  
Notes
2019-12-09 08:37:55109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-06-01 Cont ID  
Sent By medwards Date 2020-06-01 Time 10:08 Rev Time 0.00
Received By medwards Date 2020-06-01 Time 10:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By ccole Date 2019-12-24 Time 09:21 Rev Time 0.00
Received By ccole Date 2019-12-23 Time 17:01 Sent To  
Notes
2019-12-24 09:33:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19100519
 12/24/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD,
 FIRE SUPPRESSION SYSTEM, AND THE WALK-IN COOLER AND
 FREEZER. PLEASE PLACE A BOLD NOTE ON THE PLAN- SECTION
 107.2.1 WPB.
  
 2) PLEASE INDICATE HOW COMBUSTION AIR WILL BE SUPPLIED
 TO THE GAS-FIRED COOKING APPLIANCES AND PROVIDE
 CALCULATIONS- SEE SECTION 304.1 FBC FG.
  
 3) ADVISORY: VERIFY THAT THE TEMPERATURE DIFFERENTIAL
 BETWEEN THE EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE DOES NOT EXCEED 10 DEGREES F- SECTION
 508.1.1 FBC M.
  
 4) THE $150,000 VALUE APPEARS TO BE LOW FOR THE SCOPE
 OF WORK ON THE PLANS. PERMIT FEE FOR THE RESTAURANT
 WILL BE BASED ON THE TOTAL COST OF LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, FIXTURES, SITE WORK, AND DESIGN
 FEES FOR ALL PHASES OF THE PROJECT- SECTION 109.3 WPB.
 PLEASE NOTE THAT THE COSTS ASOCIATED WITH THE KITCHEN
 HOOD, FIRE SUPPRESSION, AND WALK-INS SHOULD NOT BE
 INCLUDED IN THE MAIN RESTAURANT PERMIT VALUE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-08 Cont ID  
Sent By ccole Date 2020-06-08 Time 14:44 Rev Time 0.00
Received By ccole Date 2020-06-08 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-01 Cont ID  
Sent By ccole Date 2020-06-01 Time 15:47 Rev Time 0.00
Received By ccole Date 2020-06-01 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-12-12 Cont ID  
Sent By shill Date 2019-12-12 Time 17:16 Rev Time 0.00
Received By gjohnson Date 2019-12-09 Time 17:16 Sent To  
Notes
2019-12-12 17:16:57REVIEWED REMOTELY BY GEORGE JOHNSON
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2020-06-01 Cont ID  
Sent By ccole Date 2020-06-01 Time 15:47 Rev Time 0.00
Received By ccole Date 2020-06-01 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-12-12 Cont ID  
Sent By shill Date 2019-12-12 Time 17:17 Rev Time 0.00
Received By gjohnson Date 2019-12-12 Time 17:17 Sent To  
Notes
2019-12-12 17:17:59REVIEWED REMOTELY BY GEORGE JOHNSON
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-08-24 Cont ID  
Sent By shill Date 2020-08-24 Time 12:19 Rev Time 0.00
Received By shill Date 2020-08-24 Time 12:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 15:00 Sent To  
Notes
2020-08-07 15:05:33DRAWINGS LABELED
 407 SECTIONS & DETAILS.PDF V3
 403 S FOUNDATION & FLOOR PLAN.PDF V3
 405 S SCHEDULES.PDF V3
 402 S WIND LOAD ELEVATIONS.PDF V2
 401 S GENERAL NOTES.PDF V2
 SHOW IN "ADOBE READER" AS "SIGNATURE IS INVALID"
 THE ELECTRONIC OR DIGITAL SIGNATURE NEEDS TO SHOW IN
 "ADOBE READER" AS "SIGNATURES ARE VALID".
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 07:59 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-01 Cont ID  
Sent By medwards Date 2020-06-01 Time 10:31 Rev Time 0.00
Received By medwards Date 2020-06-01 Time 10:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-12-09 Cont ID  
Sent By dbattles Date 2019-12-09 Time 08:35 Rev Time 0.00
Received By dbattles Date 2019-12-09 Time 08:34 Sent To  
Notes
2019-12-09 08:36:56OK - ALL SHEETS REVIEWED (A,S,M,E,P)
 OK - ENGINEER SHEETS THIRD PARTY VERIFIED.
 ANY ADDITIONAL SHEETS WILL NEED TO BE DIGITALLY SIGNED.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-07 Cont ID  
Sent By elevesqu Date 2020-07-07 Time 16:04 Rev Time 0.00
Received By elevesqu Date 2020-07-07 Time 15:44 Sent To  
Notes
2020-07-07 16:03:04PROVISOS:
  
  
 BICYCLE RACK SHALL BE REVIEWED THROUGH SEPARATE PERMIT
  
 TO BE REVIEWED THROUGH SEPARATE PERMIT: FENCE, GATES,
 LANDSCAPING, AWNINGS AND CANOPIES, PAVEMENT AND
 PARKING, TRASH ENCLOSURE
  
 IF ROOF MOUNTED EQUIPMENT IS NOT EFFICIENTLY SCREENED
 BY PARAPET, ALTERNATIVE SCREENING SHALL BE PROVIDED -
 CONFIRMED AT TIME OF CO
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-14 Cont ID  
Sent By elevesqu Date 2020-05-14 Time 10:07 Rev Time 0.00
Received By elevesqu Date 2020-05-08 Time 12:15 Sent To  
Notes
2020-05-08 12:15:20PROVISOS:
  
 BACKFLOW PREVENTER SHALL BE SCREENED BY LANDSCAPE -
 PROPOSED PLATER BOX SHOWN IN LANDSCAPE PERMIT DOES NOT
 MATCH PROPOSED LOCATION ON SITE PLAN. PLANTER BOX MAY
 NOT PERMIT SUFFICIENT ACCESS TO BACKFLOW PREVENTER.
 CONSIDER FOUNDATION LANDSCAPING ALONG THIS FACADE
 INSTEAD OF PLANTER BOXES.
 COORDINATE WITH RAY CARANCI AND LIZ LEVESQUE
  
 PLEASE SUBMIT DETAILS OF BICYCLE RACK THROUGH SEPARATE
 PERMIT FOR INSTALLATION -
  
 IS 4' HIGH WALL EXISTING ALONG WEST PROPERTY LINE? - IF
 NOT, NEEDS TO BE REVIEWED THROUGH SEPARATE FENCE/WALL
 PERMIT
  
 TO BE REVIEWED THORUGH SEPARATE PERMIT: FENCE, GATES,
 LANDSCAPING, AWNINGS AND CANOPIES, PAVEMENT AND
 PARKING, TRASH ENCLOSURE
 IF ROOF MOUNTED EQUIPMENT IS NOT EFFICIENTY SCREENED BY
 PARAPET, ALTERNATIVE SCREENING SHALL BE PROVIDED -
 CONFIRMED AT TIME OF CO
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By elevesqu Date 2020-01-06 Time 16:43 Rev Time 0.00
Received By elevesqu Date 2020-01-06 Time 16:43 Sent To  
Notes
2019-12-31 13:55:03DRAFT
  
 1. PLEASE REMOVE LANDSCAPE PLAN FROM PERMIT SET- TO BE
 REVIEW THROUGH SEPARATE LANDSCAPE PERMIT
 2. PLEASE SUBMIT A SEPARATE FENCE PERMIT FOR
 FENCE/ROLLING GATE - NO PERMIT ON FILE .
 FENCES WITHIN THE FRONT YARD SETBACK (ALONG 3RD STREET)
 ARE PERMITTED A MAXIMUM HEIGHT OF 6 FEET WITH 10%
 ADDITIONAL ALLOWANCE FOR DECORATIVE ELEMENTS.
 - WILL VEHICLES STILL BE ENTERING THIS LOCATION? PLEASE
 INDICATE ON PLANS
 3. DUMPSTER ENCLOSURE DOES NOT MEET REQUIREMENTS FROM
 CITY OF WPB PUBLIC WORKS. DUMSTER ENCLOSURE
 REQUIREMENTS IS 14'2" WIDE BY 13'8" LONG. WILL THE
 DUMPSTER BE ROLLED OUT TO THE CURB? CONTACT MATT HEJAZI
 AT [email protected] TO DISCUSS DUMPSTER ENCLOSURE
 REQUIREMENTS AND SPECIFICS FOR THIS SITE - INCLUDE
 ZONING IN DISCUSSION AND RESPONSE
 4. PLEASE PAINT DOWN SPOUT TO MATCH BUILDING COLOR-
 PLEASE MAKE NOTE ON PLANS
 5. HOW WILL EXHAUST DUCTWORK BE SCREENED? PLEASE FIND
 SOLUTION TO SCREEN AND/OR PAINT TO MATCH
 6. ROOF MOUNTED EQUIPMENT REQUIRES SCREENING TO HEIGHT
 OF EQUIPMENT- PLEASE ILLUSTRATE ON PLANS
 7. PLEASE INCLUDE A PLAN OUTLINING THE FAR FOR THE SITE
 - FAR IS CALCULATED USING GROSS BUILDING AREA, AS
 DEFINED BY SECTION 94-86 HISTORIC RESDIENTIAL DISTRICT
 DEFINITIONS. PLEASE INCLUDE A TABLE OUTLINING TOTAL
 EXISTING FAR ON SITE AND PROPOSED FAR TOTAL. FAR CANNOT
 EXCEED MAX. FAR OF NWD-R-C1 AS REQUIRED BY SECTION
 94-84 (FOR LOTS 7,500 SQUARE FEET AND OVER - 0.45 FAR)
 8. PLEASE INCLUDE INFORMATION ON THE MAXIMUM LOT
 COVERAGE WHICH MAY INCLUDE ADDITIONS - CHECK DEFINITION
 OF LOT COVERAGE PER SECTION 94-86 - MAX. LOT COVERAGE
 CANNOT EXCEED 25% FOR LOTS OVER 7,500 SF
  
  
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  