Plan Review Details - Permit 19100325
Plan Review Stops For Permit 19100325
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2019-10-23 Cont ID  
Sent By cthroop Date 2019-10-23 Time 14:56 Rev Time 0.00
Received By cthroop Date 2019-10-23 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-11 Cont ID  
Sent By cthroop Date 2020-06-11 Time 09:33 Rev Time 0.00
Received By cthroop Date 2020-06-11 Time 08:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-22 Cont ID  
Sent By cthroop Date 2019-11-22 Time 15:35 Rev Time 0.00
Received By cthroop Date 2019-11-21 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-23 Cont ID  
Sent By cthroop Date 2019-10-23 Time 14:56 Rev Time 0.00
Received By cthroop Date 2019-10-07 Time 12:36 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2020-06-11 Cont ID  
Sent By cthroop Date 2020-06-11 Time 09:33 Rev Time 0.00
Received By cthroop Date 2020-06-11 Time 08:08 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2019-11-22 Cont ID  
Sent By cthroop Date 2019-11-22 Time 15:35 Rev Time 0.00
Received By cthroop Date 2019-11-22 Time 14:30 Sent To  
Notes
2019-11-22 15:41:03SENT TO RICHARD GATHRIGHT FOR REVIEW. CT
2019-11-22 15:36:50BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE. OK
 CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-10-24 Cont ID  
Sent By cthroop Date 2019-10-24 Time 12:46 Rev Time 0.00
Received By cthroop Date 2019-10-23 Time 14:56 Sent To  
Notes
2019-10-24 12:53:28NFIP REVIEW ? BUILDING UNDER CONSTRUCTION EC
  
 SUBMITTAL# 19100325
 MASTER PERMIT# 18090744
  
 ADDRESS ? 2305 S FLAGLER DR
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW ? MAIN RESIDENCE EC
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLEASE MAKE THE FOLLOWING CHANGES TO THE BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE PER FEMA ELEVATION
 CERTIFICATE INSTRUCTIONS, 2015 EDITION
  
 1. A9 (A) ? CHANGE SQ. FOOTAGE OF ATTACHED GARAGE FROM
 880 TO 1750 SQ. FT.
 (67.3FT. X 26 FT.)
 2. A9 (B) ? STATE NUMBER OF FLOOD OPENINGS. TOP OF
 GARAGE SLAB IS AT 7.9 FEET NAVD88. THIS IS BELOW DFE.
 FLOOD VENTS REQUIRED.
 3. A9 ( C ) - STATE NET AREA OF FLOOD OPENINGS
 4. A9 (D) ? NON-ENGINEERED OPENINGS SELECTED. PROVIDE
 DETAIL.
 5. C2 (A) ? TOP OF BOTTOM FLOOR STATED AT 8.9 FEET.
 PROVIDE COMMENT IN SECTION D THAT THIS ELEVATION WILL
 BE AT OR ABOVE DFE OF 9.0 FEET NAVD88 AT FINISHED
 CONSTRUCTION.
 6. C2 (E) ? ENTRY OF N/A. PROVIDE COMMENT IN SECTION D
 THAT LOWEST ELEVATION OF MACHINERY OR EQUIPMENT SHALL
 BE AT OR ABOVE DFE OF 9.0 FEET NAVD88 AT FINISHED
 CONSTRUCTION.
 7. SECTION D ? SEE COMMENTS UNDER SIGNATURE AND SEAL
 REVIEW.
  
 1ST REVIEW ? ACCESSORY STRUCTURE EC ? GYM
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLEASE MAKE THE FOLLOWING CHANGES TO THE BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE PER FEMA ELEVATION
 CERTIFICATE INSTRUCTIONS, 2015 EDITION
  
 1. A9 (A) ? THIS STRUCTURE DOES NOT HAVE AN ATTACHED
 GARAGE. ENTER 0.
 2. C2 (A) ? TOP OF BOTTOM FLOOR STATED AT 8.9 FEET.
 PROVIDE COMMENT IN SECTION D THAT THIS ELEVATION WILL
 BE AT OR ABOVE DFE OF 9.0 FEET NAVD AT FINISHED
 CONSTRUCTION.
 3. C2 (E) ? LOWEST ELEVATION OF MACHINERY OR EQUIPMENT
 STATED AS N/A. PROVIDE COMMENT IN SECTION D THAT LOWEST
 ELEVATION OF MACHINERY OR EQUIPMENT SHALL BE AT OR
 ABOVE DFE 9.0 FEET NAVD88.
 4. SECTION D ? SEE COMMENTS UNDER SIGNATURE AND SEAL
 REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-22 Cont ID  
Sent By cthroop Date 2019-11-22 Time 15:35 Rev Time 0.00
Received By cthroop Date 2019-11-22 Time 14:29 Sent To  
Notes
2019-11-21 14:47:5411/21/19 HARD COPIES ROUTED TO CTHROOP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-10-24 Cont ID  
Sent By cthroop Date 2019-10-24 Time 12:44 Rev Time 0.00
Received By cthroop Date 2019-10-23 Time 14:56 Sent To  
Notes
2019-10-24 12:46:22REVIEW ? DIGITAL SIGNATURES AND SEALS
  
 SUBMITTAL# - 19100325 ? ELEVATION CERTIFICATES
 MASTER PERMIT# - 18090744
  
 ADDRESS: 2305 S. FLAGLER DR
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. LETTER FROM AIA ? DIGITAL SIGNATURE AND SEAL ? NOT
 COMPLIANT. RE-SUBMIT USING PROJECT DOX OR PROVIDE HARD
 COPY WITH RAISED SEAL AND SIGNATURE.
 2. ELEVATION CERTIFICATES (RESIDENCE & ACCESSORY
 STRUCTURES) ? DIGITAL SIGNATURES AND SEALS ? NOT
 COMPLIANT. RE-SUBMIT USING PROJECT DOX OR PROVIDE HARD
 COPY WITH RAISED SEAL AND SIGNATURE.
  
 DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH FS
 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE NEXT
 REVIEW CYCLE REQUIRE REVIEW.
  
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  