Plan Review Details - Permit 19091173
Plan Review Stops For Permit 19091173
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-18 Cont ID  
Sent By tklarge Date 2019-11-18 Time 13:12 Rev Time 0.00
Received By tklarge Date 2019-11-05 Time 10:45 Sent To  
Notes
2019-11-06 10:45:50RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-21 Cont ID  
Sent By tklarge Date 2019-10-21 Time 12:40 Rev Time 0.00
Received By tklarge Date 2019-10-16 Time 13:03 Sent To  
Notes
2019-10-17 13:03:31RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-07 Cont ID  
Sent By tklarge Date 2019-10-07 Time 06:53 Rev Time 0.00
Received By tklarge Date 2019-09-27 Time 13:03 Sent To  
Notes
2019-10-01 13:03:28ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-18 Cont ID  
Sent By tklarge Date 2019-11-18 Time 13:11 Rev Time 0.00
Received By tklarge Date 2019-11-18 Time 06:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-10-21 Cont ID  
Sent By tklarge Date 2019-10-21 Time 12:40 Rev Time 0.00
Received By tklarge Date 2019-10-21 Time 04:51 Sent To  
Notes
2019-10-21 11:42:461) REMOVE ALL OLD DOCUMENTS FROM THE APPLICATION
 PACKAGE THAT ARE NOT TO BE USED FOR THIS INSTALLATION.
 DOCUMENTS SHALL BE IN TWO COMPLETE SETS FOR SUBMITTAL
 AND REVIEW. WPB AMEND. TO FBC SEC. 107.1.
 2) ALL PLUMBING PRODUCTS AND MATERIALS SHALL BE LISTED
 BY A THIRD- PARTY CERTIFICATION AGENCY AS COMPLYING
 WITH THE REFERENCED STANDARDS. THE SUBMITTED
 SPECIFICATION SHEETS FOR THE SHOWER DO NOT SHOW ANY
 TYPE OF LISTING OR CERTIFICATION.SUBMIT SPECIFICATION
 SHEETS THAT COMPLY. 2017 FBC-PLUMBING SEC. 303.4. 2ND
 REQUEST.
 3) SHT. L3.11 - DETAIL "E" - THERE IS A NOTE ON THE
 DRYWELL DETAIL THAT STATES" 4 INCH DRAIN PIPE FROM
 DRINKING FOUNTAIN.NOT REQUIRED FOR SHOWER DRAIN" YET
 THE SUBMITTED NARRATIVE FOR THE ALTERNATE APPROVAL
 STATES THAT THE DRINKING FOUNTAIN AND SHOWER WILL
 DISCHARGE TO THE DRYWELL. HOW IS THE SHOWER DRAINING TO
 THE DRYWELL? THE INFORMATION ON THE DRAWING AND IN THE
 NARRATIVE MUST CORRELATE.CLARIFY AND ENSURE THE
 NARRATIVE AND DRAWING CLEARLY EXPLAIN AND REFLECCT THE
 SCOPE OF WORK.WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT TWO COPIES OF THE NARRATIVE FOR THE ALTERNATE
 APPROVAL REQUEST ALONG WITH THE DRYWELL DETAIL. BOTH
 COPIES SHALL BEAR THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL OF RECORD. FL. ADMIN. CODE RULE
 61G15-23.001.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-07 Cont ID  
Sent By tklarge Date 2019-10-07 Time 06:53 Rev Time 0.00
Received By tklarge Date 2019-10-07 Time 04:37 Sent To  
Notes
2019-10-07 05:17:581) THE LETTER FOR THE ALTERNATE APPROVAL FOR THE DRAIN
 TO A DRYWELL IS FOR SHOWER EFFLUENT BUT THE SUBMITTED
 "DETAIL E" NOTES THE DRAIN FROM A DRINKING FOUNTAIN.
 WHICH IS IT? CLARIFY. A REVISED LETTER WILL BE REQUIRED
 OR A REVISED DETAIL IF IT FOR A SHOWER.
 2) THE LETTER FOR THE ALTERNATE APPROVAL OF THE DRAIN
 TO THE DRYWELL AND THE CORRESPONDING DETAIL SHALL BEAR
 THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL PER
 FL. ADMIN. CODE RULE 61G15-23.001.
 3) TWO DIFFERENT SPECIFICATIONS HAVE BEEN SUBMITTED FOR
 THE DRINKING FOUNTAINS ( 1035 SMSS & 10155 SM). WHICH
 UNIT IS BEING INSTALLED. CLARIFY. WPB AMEND. TO FBC
 SEC. 107.2.1.
 4) SHT.L3.11 - DETAIL "C" - THE MAXIMUM HEIGHT TO THE
 BOTTLE FILLER CONTROLS AND BOTTLE SHELF SHALL BE 48
 INCHES PER THE 2017 FBC-ACCESSIBILITY SECS.308.2,
 308.3, 309.
 5) SHT.L3.11 - DETAIL "C"- THE MAXIMUM HEIGHT OF THE
 WATER SPOUT SHALL BE 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER 2017 FBC-ACCES. SEC. 602.4 FOR
 ACCESSIBLE FOUNTAINS FOR USE BY PEOPLE IN WHEELCHAIRS.
 MODEL 10155 SM DOES NOT COMPLY AS SHOWN ON THIS DETAIL.
 6) THE DETAIL FOR DRINKING FOUNTAIN 10155 SM SHOWN ON
 SHT. L3.11 DOES NOT CORRELATE WITH THE MANUFACTURER'S
 SPECIFICATION SHEET THAT HAS BEEN SUBMITTED FOR THIS
 SAME MODEL IN REGARDS TO THE HEIGHT OF THE DRINKING
 FOUNTAIN ABOVE THE FINISH FLOOR OR GROUND. CLARIFY.
 7) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES MINIMUM AND 43 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER 2017 FBC-
 ACCESS. SEC. 602.7.
 8 ) THE HEIGHT OF THE SPOUT FOR PEOPLE IN WHEELCHAIRS
 SHALL BE LOCATED A MAXIMUM OF 36 INCHES ABOVE THE
 FINISH FLOOR OR GROUND. REFER TO THE MANUFACTURER'S
 SPECIFICATION SHEET FOR MODEL 10135 SMSS.
 9) WHO IS THE MANUFACTURER FOR DRINKING FOUNTAIN MODEL
 10135 SMSS? THE IS NO MANUFACTURER LISTED ON THE
 SPECIFICATION SHEET. CLARIFY.SUBMIT SPEC SHEET THAT
 SHOWS THE MANUFACTURER.WPB AMEND. TO FBC SEC. 107.2.1.
 10) ALL PLUMBING PRODUCTS AND MATERIALS SHALL BE LISTED
 BY A THIRD- PARTY CERTIFICATION AGENCY AS COMPLYING
 WITH THE REFERENCED STANDARDS. THE SUBMITTED
 SPECIFICATION SHEETS FOR THE DRINKING FOUNTAINS OR THE
 SHOWER DO NOT SHOW ANY TYPE OF LISTING OR
 CERTIFICATION.SUBMIT SPECIFICATION SHEETS THAT COMPLY.
 11) THE SUBMITTED SPECIFICATION SHEETS FOR THE SHOWER
 SHOW THE HEIGHT OF THE SHOWER CONTROLS IN SI UNITS OF
 MEASUREMENT ( MILLIMETERS? ). SHOW THE HEIGHT OF THE
 SHOWER CONTROL IN U.S. CUSTOMARY SYSTEM UNITS OF
 MEASUREMENT. WPB AMEND. TO FBC SEC. 107.2.1.THE HEIGHT
 OF THE CONTROL SHALL COMPLY WITH THE 2017 FBC- ACCESS.
 SECS. 308 & 309.
 12) RESPONSE #2 OF THE RESPONSE NARRATIVE REFERS TO
 CORRESPONDENCE FROM THE MANUFACTURER OF THE DRINKING
 FOUNTAINS INDICATING COMPLIANCE WITH THE FLORIDA
 ACCESSIBILITY CODE. THERE IS NO SUCH CORRESPONDENCE IN
 THE SUBMITTAL PACKAGE. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW