Plan Review Details - Permit 19091144
Plan Review Stops For Permit 19091144
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-12-31 Cont ID  
Sent By pleduc Date 2019-12-31 Time   Rev Time 0.00
Received By pleduc Date 2019-12-31 Time 12:43 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-12-09 Cont ID  
Sent By pleduc Date 2019-12-09 Time   Rev Time 0.00
Received By pleduc Date 2019-12-09 Time 13:41 Sent To I
Notes
2019-12-09 13:47:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INDICATIONS OF UNDERGROUND FIRE LINE, IS IT
 EXISTING OR IS IT NEW.
  
 ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWING.
  
  
 1A.) IS THIS A DEDICATED FIRE LINE OR IS IT TIED INTO
 THE DOMESTIC LINE?
  
 IF THE WATER TO THE BLDG IS CUT OFF, WILL THE FS SYSTEM
 REMAIN WET.
  
 PLEASE PROVIDE DETAILS.
  
  
 2) THERE IS NO INDICATION OF A DDCV.
  
 WHERE IS THE DDCV LOCATED AND PROVIDED THE
 SPECIFICATION SHEETS INDICATING LEAD-FREE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-01 Cont ID  
Sent By pleduc Date 2019-10-01 Time   Rev Time 0.00
Received By pleduc Date 2019-10-01 Time 15:07 Sent To I
Notes
2019-10-01 15:15:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO HYDRAULIC CALCULATIONS PROVIDED.
  
 PLEASE PROVIDE.
  
  
  
 2) NFPA 13 PROVIDES THE FOLLOWING:
  
 22.17 HEALTH CARE FACILITIES CODE, HYPERBARIC CHAMBERS.
 22.17.1 DESIGN REQUIREMENTS.
 22.17.1.1 A FIXED WATER DELUGE EXTINGUISHING SYSTEM
 SHALL BE
 INSTALLED IN ALL CHAMBER COMPARTMENTS THAT ARE DESIGNED
 FOR
 MANNED OPERATIONS.
 22.17.1.2 IN CHAMBERS THAT CONSIST OF MORE THAN ONE
 CHAMBER
 COMPARTMENT (LOCK), THE DESIGN OF THE DELUGE SYSTEM
 SHALL
 MEET THE REQUIREMENTS OF 22.17.1.1 WHEN THE CHAMBER
 COMPARTMENTS
 ARE AT DIFFERENT DEPTHS (PRESSURES).
 22.17.1.3 THE DELUGE SYSTEM IN DIFFERENT COMPARTMENTS
 (LOCKS)
 SHALL OPERATE INDEPENDENTLY OR SIMULTANEOUSLY.
 22.17.1.4 FIXED DELUGE SYSTEMS SHALL NOT BE REQUIRED IN
 CHAMBER
 COMPARTMENTS THAT ARE USED STRICTLY AS PERSONNEL
 TRANSFER
 COMPARTMENTS (LOCKS) AND FOR NO OTHER PURPOSES.
 22.17.1.5* MANUAL ACTIVATION AND DEACTIVATION DELUGE
 CONTROLS
 SHALL BE LOCATED AT THE OPERATOR?S CONSOLE AND IN EACH
 CHAMBER
 COMPARTMENT (LOCK) CONTAINING A DELUGE SYSTEM.
 22.17.1.6 CONTROLS SHALL BE DESIGNED TO PREVENT
 UNINTENDED
 ACTIVATION.
 22.17.1.7 WATER SHALL BE DELIVERED FROM THE FIXED
 DISCHARGE
 NOZZLES AS SPECIFIED IN 22.17.1.9 WITHIN 3 SECONDS OF
 ACTIVATION
 OF ANY AFFILIATED DELUGE CONTROL.
 22.17.1.8* AVERAGE SPRAY DENSITY AT FLOOR LEVEL SHALL
 BE NOT LESS
 THAN 2 GPM/FT2 (81.5 L/MIN/M2), WITH NO FLOOR AREA
 LARGER THAN
 10.76 FT2 (1M2) RECEIVING LESS THAN 1 GPM/FT2 (40.75
 L/MIN/M2).
 22.17.1.9 WATER SHALL BE AVAILABLE IN THE DELUGE SYSTEM
 TO
 MAINTAIN THE FLOW SPECIFIED IN 22.17.1.8 SIMULTANEOUSLY
 IN
 EACH CHAMBER COMPARTMENT (LOCK) CONTAINING THE DELUGE
 SYSTEM
 FOR 1 MINUTE.
 22.17.1.10 THE LIMIT ON MAXIMUM EXTINGUISHMENT DURATION
 SHALL BE GOVERNED BY THE CHAMBER CAPACITY (BILGE
 CAPACITY ALSO, IF
 SO EQUIPPED) OR ITS DRAINAGE SYSTEM, OR BOTH.
 22.17.1.11 THE DELUGE SYSTEM SHALL HAVE STORED PRESSURE
 TO
 OPERATE FOR AT LEAST 15 SECONDS WITHOUT ELECTRICAL
 BRANCH
 POWER.
  
  
 PLEASE CORRECT OR PROVIDE DETAILED JUSTIFICATION
 MEETING COMPLIANCE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-31 Cont ID  
Sent By cpuell Date 2019-12-31 Time 15:13 Rev Time 0.00
Received By cpuell Date 2019-12-18 Time 14:31 Sent To  
Notes
2019-12-19 14:31:28RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-09 Cont ID  
Sent By cpuell Date 2019-12-09 Time 14:05 Rev Time 0.00
Received By cpuell Date 2019-12-05 Time 15:19 Sent To  
Notes
2019-12-06 15:20:04RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-02 Cont ID  
Sent By cpuell Date 2019-10-02 Time 10:28 Rev Time 0.00
Received By cpuell Date 2019-09-27 Time 13:14 Sent To  
Notes
2019-10-01 13:14:58ROUTED TO FIRE INBOX