Plan Review Details - Permit 19091105
Plan Review Stops For Permit 19091105
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2020-05-28 Cont ID  
Sent By jgomez Date 2020-05-28 Time 14:38 Rev Time 0.00
Received By jgomez Date 2020-05-28 Time 11:35 Sent To  
Notes
2020-05-28 11:35:53NOTE:
 ENERGY CALCULATIONS SUBMITTED ON 05/18/2020 ARE NOT
 REVISED. THEY ARE THE SAME CALCULATIONS THAT WERE
 PREVIOUSLY SUBMITTED . THEY WERE PRINTED ON 03/03/2020.
 CALCULATIONS NEED TO BE REVISED. SEE PROVISO BELOW.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE ENERGY CALCULATIONS:
 A) REVISE WINDOWS AREAS AND ORIENTATION TO MATCH PLANS.
 B) REVISE DOORS ORIENTATION TO MATCH PLANS.
 C) REVISE DOOR TYPE TO MATCH PLANS AND PRODUCT
 APPROVALS. (NO WOOD)

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-03-24 Cont ID  
Sent By jgomez Date 2020-03-24 Time 14:55 Rev Time 0.00
Received By jgomez Date 2020-03-24 Time 11:59 Sent To  
Notes
2020-03-24 15:09:08BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE ENERGY CALCULATIONS:
 A) REVISE WINDOWS AREAS AND ORIENTATION TO MATCH PLANS.
 B) REVISE DOORS ORIENTATION TO MATCH PLANS.
 C) REVISE DOOR TYPE TO MATCH PLANS AND PRODUCT
 APPROVALS. (NO WOOD)
  
 2- REVISE THE DESIGN CRITERIA ON SHEET A-2. CURRENT
 CODE IS THE 2017 NOT 2007. BUILDING EXPOSURE IS "C" NOT
 "B". REVISE DESIGN PRESSURES ACCORDINGLY.
 NOTE: COORDINATE WITH DESIGN CRITERIA ON SHEET A-1

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 11:24 Rev Time 0.00
Received By jgomez Date 2020-02-11 Time 15:00 Sent To  
Notes
2020-02-12 11:10:03DENIED:
 THIS BUILDING CAN NOT BE APPROVED WITH PROVISO. PLANS
 SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING TO
 CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN THIS
 LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE ZONING
 SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED SURVEY
 SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT COMPLETE
 FLOOR PLANS AND ENERGY CALCULATIONS FOR THE PROPOSED
 MODEL FOR COMPLETE REVIEW.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-12-19 Cont ID  
Sent By jgomez Date 2019-12-19 Time 09:43 Rev Time 0.00
Received By jgomez Date 2019-12-19 Time 09:32 Sent To  
Notes
2019-12-19 09:33:4312/18/19 MET WITH CHRISTOPHER BACHE (CONTRACTOR). HE
 AGREED TO PASS BUILDING REVIEWS WITH PROVISO. JG.
  
 12/19/19 DENIED:
 THIS BUILDING CAN NOT BE APPROVED WITH PROVISO. PLANS
 SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING TO
 CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN THIS
 LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE ZONING
 SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED SURVEY
 SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT COMPLETE
 FLOOR PLANS AND ENERGY CALCULATIONS FOR THE PROPOSED
 MODEL.
  
  
  
 ********PREVIOUS COMMENTS:
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- ENERGY CALCULATIONS:
 A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY
 CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4 ON
 PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4
 DOESN'T MATCH PLANS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, PERMIT OFFICE AND
 JURISDICTION SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NO DOORS N THE WEST SIDE AND THERE ARE NO WOOD
 DOORS SHOWN ON PLANS OR PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E) WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
  
 2- SURVEY SUBMITTED:
 HOUSE FOOTPRINT SHOWN ON THE NEW SURVEY SUBMITTED
 DOESN'T MATCH HOUSE FOOTPRINT OF PLANS SUBMITTED. PLANS
 ARE FOR A 5 BEDROOM HOUSE. NEED TO COORDINATE PLANS AND
 SURVEY. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 3- OK
  
 4- OK
  
 5- OK
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 ONLY ONE PRODUCT APPROVAL WAS SUBMITTED. NEED TWO. SEC.
 107.1 CITY AMENDMENTS.
  
 7-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 8- OK
  
 9- OK
  
 10-IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-11 Cont ID  
Sent By jgomez Date 2019-12-11 Time 09:16 Rev Time 0.00
Received By jgomez Date 2019-12-11 Time 08:11 Sent To  
Notes
2019-12-11 08:28:28 
 12/19/19 DENIED:
 PLANS SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING
 TO CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN
 THIS LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE
 ZONING SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED
 SURVEY SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT
 COMPLETE FLOOR PLANS AND ENERGY CALCULATIONS FOR THE
 PROPOSED MODEL.
  
  
  
 ***COMMENTS BELOW APPLY ONLY TO THE 5 BEDROOM MODEL
 THAT WAS ORIGINALLY SUBMITTED:
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- ENERGY CALCULATIONS:
 A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY
 CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) NUMBER OF BEDROOMS IS INCORRECT. REVISE ITEM #4 ON
 PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B) CONDITIONED FLOOR AREA ON ITEM #6 ON PAGE 1 OF 4
 DOESN'T MATCH PLANS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, PERMIT OFFICE AND
 JURISDICTION SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE
 ARE NO DOORS N THE WEST SIDE AND THERE ARE NO WOOD
 DOORS SHOWN ON PLANS OR PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E) WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOWS ORIENTATION AND AREA TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
  
 2- SURVEY SUBMITTED:
 HOUSE FOOTPRINT SHOWN ON THE NEW SURVEY SUBMITTED
 DOESN'T MATCH HOUSE FOOTPRINT OF PLANS SUBMITTED. PLANS
 ARE FOR A 5 BEDROOM HOUSE. NEED TO COORDINATE PLANS AND
 SURVEY. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 3- OK
  
 4- OK
  
 5- OK
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 ONLY ONE PRODUCT APPROVAL WAS SUBMITTED. NEED TWO. SEC.
 107.1 CITY AMENDMENTS.
  
 7-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 8- OK
  
 9- OK
  
 10-IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By jgomez Date 2019-10-17 Time 15:20 Rev Time 0.00
Received By jgomez Date 2019-10-17 Time 15:15 Sent To  
Notes
2019-10-17 15:20:42NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ENERGY CALCULATIONS:
 A)MISSING THE ENERGY CALCULATIONS. PROVIDE ENERGY
 CALCULATIONS (2 COPIES) AS REQUIRED BY SEC. R101.5.1
 FBC-ENERGY CONSERVATION.
  
 B) AN ENVELOPE LEAKAGE TEST REPORT PERFORMANCE METHOD
 WAS SUBMITTED WITH THE CONTRACTOR CERTIFYING THAT THE
 ENVELOPE LEAKAGE PERFORMANCE RESULTS DEMONSTRATE
 COMPLIANCE. CONTRACTOR TO CLAREIFY HOW CAN THE
 CONTRACTOR CERTIFY THAT THE ENVELOPE LEAKAGE
 PERFORMANCE RESULTS IS IN COMPLIANCE IF THE HOSE IS NOT
 BUILT YET?
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- SURVEY SUBMITTED:
 A) SURVEY SUBMITTED IS NOT DRAWN TO SCALE. SURVEY
 SPECIFIES 1"-10' SCALE. NEED A LARGER SHEET SIZE AS
 NOTED ON SURVEY REPORT NOTE #13 OR PROVIDE SURVEY WITH
 TRUE SCALE. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 B) SURVEY SUBMITTED HAS A PRINTED COPY OF A DIGITAL
 SIGNATURE. DIGITAL SIGNATURES ARE FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS. THIS IS NOT AN ELECTRONIC
 SUBMITTAL. SURVEY NEEDS ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY SEC. 472.025 FLORIDA STATUES.
  
 3- ATTIC ACCESS SIZE SPECIFIED ON PLANS (22"X54")DON'T
 SEEM TO FIT ON THE HALLWAY THE WAY IS SHOWN ON PLANS.
 IF THIS IS THE SIZE THAT IS GOING TO BE INSTALLED, THEN
 THE OPENING NEEDS TO BE ORIENTED PERPENDICULAR TO THE
 ROOF TRUSSES AND STRUCTURAL FRAMING DETAILS WILL NEED
 TO BE PROVIDED. REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- REVISE DOOR/WINDOW BUCK NOTES ON SHEET A-1. BEVELED
 BUCKS AR NOT ALLOWED. THE BUCK NEEDS TO EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME AS
 REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. REVISE
 NOTES AS REQUIRED.
  
 5- ROOF SHEATHING NAILING TYPE AND SIZE SPECIFIED ON
 THE TYPICAL WALL SECTION ON SHEET S-3 DOESN'T MATCH THE
 SPECIFICATIONS SHOWN ON THE ROOF SHEATHING DIAPHRAGM
 SCHEDULE ON SHEET S-2. REVISE AS REQUIRED TO MATCH.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR AS SHOWN ON PLANS.
  
 B) ROOF SHINGLES. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. NEED
 COVER PAGE TO VERIFY CURRENT CODE AND IF THE PRODUCT IS
 APPROVED.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 7-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 8- TRUSS PACKAGE
 NOTE:
 TRUSS PACKAGE IS NOT REQUIRED TO BE SUBMITTED FOR PLAN
 REVIEW FOR ONE AND TWO FAMILY BUILDINGS. CONTRACTOR MAY
 DELIVER THE TRUSS PACKAGE TO THE BUILDING INSPECTOR AT
 THE TIME OF FRAMING INSPECTIONS AFTER CORRECTIONS
 ADDRESSING THE COMMENTS ARE ADDRESSED.
  
 A) ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 TRUSS DRAWING AND TRUSS LAYOUT AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 B)TRUSS PACKAGE SUBMITTED NEEDS A TITLE BLOCK WITH THE
 INFORMATION OF THE TRUSS ENGINEER ON EACH SHEET AND
 EACH SHEET NEEDS TO BE SIGNED AND SEALED BY THE TRUSS
 ENGINEER AS REQUIRED BY SEC. 61G15-23.001 FAC.
  
 C) TRUSS LAYOUT TO SHOW THE TRUSS TO TRUSS CONNECTORS
 AND LOCATION. TRUSS ENGINEER TO SIGN AND SEAL THESE
 PLANS AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE SCOPE OF WORK. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND
 PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO
 $201,054. THE PERMIT FEE BALANCE IS $4503.23.
  
 10-IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2020-05-29 Cont ID  
Sent By ppetty Date 2020-05-29 Time 09:07 Rev Time 0.00
Received By ppetty Date 2020-05-29 Time 09:07 Sent To  
Notes
2020-05-28 11:35:41NEW SET OF PLANS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-03-25 Cont ID  
Sent By rmcdouga Date 2020-03-25 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2020-03-25 Time 12:18 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-12-19 Cont ID  
Sent By jpearson Date 2019-12-19 Time 10:32 Rev Time 0.00
Received By jpearson Date 2019-12-19 Time 10:32 Sent To  
Notes
2019-12-19 10:32:18MODEL NEEDS TO BE CHANGED PER ZONING SETBACKS, SO NEW
 PLAN WILL NEED TO BE SUBMITTED AND REVIEWED FOR THAT
 MODEL. WPB FBC 105.1, 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-19 Cont ID  
Sent By cthroop Date 2019-12-13 Time 14:38 Rev Time 0.00
Received By jpearson Date 2019-12-13 Time 11:48 Sent To  
Notes
2019-12-19 10:32:41SEE 3RD REVIEW NOTE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-16 Cont ID  
Sent By jpearson Date 2019-10-16 Time 11:19 Rev Time 0.00
Received By jpearson Date 2019-10-16 Time 10:16 Sent To  
Notes
2019-10-16 11:19:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE
 CONDUCTORS MUST HAVE OVERCURRENT PROTECTION WHERE THEY
 ENTER THE DWELLING UNIT. SERVICE CONDUCTORS ARE NOT
 PERMITTED TO EXTEND FURTHER THAN 8 FEET INTO A
 STRUCTURE WITHOUT OVERCURRENT PROTECTION. IF THIS
 OVERCURRENT PROTECTION IS LOCATED ON THE EXTERIOR OF
 THE DWELLING, THAN THE CONDUIT TO THE INTERIOR PANEL
 MUST INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. IF THE
 CONDUCTORS ARE RUN UNDERGROUND FROM THE METER TO THE
 INTERIOR PANEL, AND THAT PANEL HAS A MAIN BREAKER, THE
 CONDUCTORS MUST NOT EXCEED 8 FEET IN LENGTH BEFORE
 TERMINATION TO THE MAIN BREAKER. PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 230.70, 250.122; FBC RE E3601.6,
 E3704.6, 3607.3.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 3. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 4. NOTE 12 STATES THAT LIGHTING IN CLOTHES CLOSETS
 SHALL COMPLY WITH NEC 410.8, WHICH IS NOT THE CORRECT
 CODE. PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 5. NOTE 18 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2020-05-29 Cont ID  
Sent By ppetty Date 2020-05-29 Time 09:07 Rev Time 0.00
Received By ppetty Date 2020-05-18 Time 13:47 Sent To  
Notes
2020-05-21 17:02:21ROUTED TO JULIO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-04-06 Cont ID  
Sent By jgomez Date 2020-04-06 Time 08:45 Rev Time 0.00
Received By jgomez Date 2020-04-02 Time 08:45 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-03-25 Cont ID  
Sent By rmcdouga Date 2020-03-25 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2020-03-05 Time 13:27 Sent To  
Notes
2020-03-06 13:27:40R26

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 11:28 Rev Time 0.00
Received By jgomez Date 2020-01-17 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-23 Cont ID  
Sent By cthroop Date 2019-12-23 Time 11:55 Rev Time 0.00
Received By cthroop Date 2019-12-19 Time 09:31 Sent To  
Notes
2019-12-19 09:31:4812/18/19 MET WITH CHRISTOPHER BACHE (CONTRACTOR). HE
 AGREED TO PASS REVIEWS WITH PROVISO. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-13 Cont ID  
Sent By cthroop Date 2019-12-13 Time 14:38 Rev Time 0.00
Received By cthroop Date 2019-12-03 Time 15:04 Sent To  
Notes
2019-12-13 09:55:20TO CT DESK
  
2019-12-04 15:04:22R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-10-21 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-26 Time 14:38 Sent To I
Notes
2019-09-27 14:38:30R37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status P Date 2020-04-06 Cont ID  
Sent By jgomez Date 2020-04-06 Time 08:40 Rev Time 0.00
Received By jgomez Date 2020-04-06 Time 08:26 Sent To  
Notes
2020-04-06 08:43:04$2,695.44 PAID. MU-2020-000972.
  
 COUNTY STAMPED PLANS ON 03/27/2020 CONFIRMING THAT FEES
 PAID ARE FOR THIS LOT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2020-03-24 Cont ID  
Sent By jgomez Date 2020-03-24 Time 15:19 Rev Time 0.00
Received By jgomez Date 2020-03-24 Time 15:19 Sent To  
Notes
2020-03-24 15:23:35IMPACT FEES MU-2020-000972 ARE FOR THE 5 BEDROOM MODEL.
 THIS MODEL IS NOT GOING TO BE BUILT IN THIS LOT BECAUSE
 IT DOESN'T MEET THE ZONING REQUIREMENTS. THE NEW
 PROPOSED MODEL NEEDS TO BE REVIEWED BY THE COUNTY FOR
 IMPACT FEES.
 THE IMPACT FEES NEED TO BE COORDINATED WITH NEW MODEL.
 PROVIDE COUNTY STAMPED PLANS WITH THE NEW MODEL.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 11:25 Rev Time 0.00
Received By jgomez Date 2020-02-12 Time 11:25 Sent To  
Notes
2020-02-12 11:28:52IMPACT FEES MU-2020-000972 ARE FOR THE 5 BEDROOM MODEL.
 THIS MODEL IS NOT GOING TO BE BUILT IN THIS LOT BECAUSE
 IT DOESN'T MEET THE ZONING REQUIREMENTS. A NEW SET OF
 PLANS FOR PROPOSED MODEL NEEDS TO BE SUBMITTED FOR
 COMPLETE REVIEW. THE IMPACT FEES NEED TO BE COORDINATED
 WITH NEW MODEL.
  
  
  
 DENIED:
 THIS BUILDING CAN NOT BE APPROVED WITH PROVISO. PLANS
 SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING TO
 CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN THIS
 LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE ZONING
 SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED SURVEY
 SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT COMPLETE
 FLOOR PLANS AND ENERGY CALCULATIONS FOR THE PROPOSED
 MODEL FOR COMPLETE REVIEW.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-12-19 Cont ID  
Sent By jgomez Date 2019-12-19 Time 10:00 Rev Time 0.00
Received By jgomez Date 2019-12-19 Time 10:00 Sent To  
Notes
2019-12-19 10:01:04IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-12-11 Cont ID  
Sent By jgomez Date 2019-12-11 Time 09:16 Rev Time 0.00
Received By jgomez Date 2019-12-11 Time 09:16 Sent To  
Notes
2019-12-11 09:16:32IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By jgomez Date 2019-10-17 Time 15:23 Rev Time 0.00
Received By jgomez Date 2019-10-17 Time 15:23 Sent To  
Notes
2019-10-17 15:23:52IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2020-05-28 Cont ID  
Sent By jgomez Date 2020-05-28 Time 15:55 Rev Time 0.00
Received By jgomez Date 2020-05-28 Time 15:49 Sent To E
Notes
2020-05-28 15:57:33MECHANICAL REVIEW APPROVED WITH PROVISO:
 1- BALANCED RETURN AIR DUCT TO BE 12" MIN. AS REQUIRED
 BY SEC. M1602.3 FBC-RESIDENTIAL EXCEPTION #3.
 2- REVISE LOAD CALCULATIONS. ENTRY DOOR DOESN'T FACE
 WEST. SEE PLANS AND REVISE AS REQUIRED.
2020-05-28 11:35:28NEW SET OF PLANS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-04-06 Cont ID  
Sent By jgomez Date 2020-04-06 Time 09:07 Rev Time 0.00
Received By jgomez Date 2020-04-06 Time 08:53 Sent To  
Notes
2020-04-06 09:09:50MECHANICAL REVIEW APPROVED WITH PROVISO PER SAMANTHA
 HILL (04/06/2020) :
 1- PROVIDE COPY OF PLAN SHOWING THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 SEC. 17.2.1 CITY AMENDMENTS

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-03-24 Cont ID  
Sent By ccole Date 2020-03-24 Time 09:49 Rev Time 0.00
Received By ccole Date 2020-03-24 Time 09:30 Sent To  
Notes
2020-03-24 09:51:353RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19091105
 3/24/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL
 EXISTS- PLEASE COMPLY.
  
 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-12-23 Cont ID  
Sent By cthroop Date 2019-12-23 Time 11:48 Rev Time 0.00
Received By cthroop Date 2019-12-23 Time 11:02 Sent To  
Notes
2019-12-23 11:55:39PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
 (NOT ADDRESSED)
  
 2) THE ENERGYGAUGE FORM R405 LISTS NUMBER OF BEDROOMS
 AS 4. THIS MODEL HAS 5 BEDROOMS.
 ENERGY PERFORMANCE LEVEL EPL DISPLAY CARD LISTS NUMBER
 OF BEDROOMS AS 4. THIS MODEL HAS 5 BEDROOMS.
 RE-SUBMIT CORRECTED FORM R405 AND EPL CARD.
  
 3) CORRECTED
  
 4) CORRECTED.
  
 5) AC-1: THE RETURN TRANSFER DUCTS FROM BEDROOMS 3, 4,
 & 5 ARE UNDERSIZED PER SECTION M1602.3 FBC RES- THE
 RETURN DUCT DIAMETERS SHALL BE 1.5 TIMES THE DIAMETERS
 OF THE SUPPLY DUCTS. (NOT ADDRESSED)
  
 6) AC-1 EXHAUST VENTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED
 FOR THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE
 SECTION M1503.1 FOR RANGE HOOD REQUIREMENTS, AND
 M1503.4 FOR MAKEUP AIR. (NOT ADDRESSED)
  
 7) CORRECTED - AIR HANDLER RE-LOCATED TO CLOSET.
  
 8) CORRECTED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-12-13 Cont ID  
Sent By cthroop Date 2019-12-13 Time 13:53 Rev Time 0.00
Received By cthroop Date 2019-12-13 Time 11:48 Sent To  
Notes
2019-12-13 14:08:55PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
 (NOT ADDRESSED)
  
 2) CORRECTED
  
 3) CORRECTED
  
 4) AC-1: INDICATE THE SIZE OF THE DUCT FROM THE RAG TO
 THE AIR HANDLER- SECTION M1602.2 FBC RES. (PARTIAL
 CORRECTION)
  
 5) AC-1: THE RETURN TRANSFER DUCTS FROM BEDROOMS 3, 4,
 & 5 ARE UNDERSIZED PER SECTION M1602.3 FBC RES- THE
 RETURN DUCT DIAMETERS SHALL BE 1.5 TIMES THE DIAMETERS
 OF THE SUPPLY DUCTS. (NOT ADDRESSED)
  
 6) AC-1 EXHAUST VENTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED
 FOR THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE
 SECTION M1503.1 FOR RANGE HOOD REQUIREMENTS, AND
 M1503.4 FOR MAKEUP AIR. (NOT ADDRESSED)
  
 7) AC-1 VERIFY COMPLIANCE WITH SECTION R403.3.6
 AIR-HANDLING UNITS IN ATTICS: (NOT ADDRESSED)
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
  
 8) AC-1: PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES. (DETAIL PROVIDED -
 PLAN PAGE MISSING SIGNATURE AND SEAL OF DESIGN
 PROFESSIONAL)
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-21 Cont ID  
Sent By ccole Date 2019-10-21 Time 11:41 Rev Time 0.00
Received By ccole Date 2019-10-21 Time 11:37 Sent To I
Notes
2019-10-21 11:43:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19091105
 10/21/19
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 AC-1- SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
 2) THE ENERGYGAUGE FORM R405 IS MISSING FROM THE ENERGY
 COMPLIANCE SUBMITTAL- SECTION R405.2 FBC EC.
  
 3) PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM
 SIZING CALCULATIONS- SECTION R403.7.1 FBC EC.
  
 4) AC-1: INDICATE THE SIZE OF THE RETURN DUCT FROM THE
 MASTER BEDROOM TO THE 20X18 RAG, AND THE SIZE OF THE
 DUCT FROM THE RAG TO THE AIR HANDLER- SECTION M1602.2
 FBC RES.
  
 5) AC-1: THE RETURN TRANSFER DUCTS FROM BEDROOMS 3, 4,
 & 5 ARE UNDERSIZED PER SECTION M1602.3 FBC RES- THE
 RETURN DUCT DIAMETERS SHALL BE 1.5 TIMES THE DIAMETERS
 OF THE SUPPLY DUCTS.
  
 6) AC-1 EXHAUST VENTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED
 FOR THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE
 SECTION M1503.1 FOR RANGE HOOD REQUIREMENTS, AND
 M1503.4 FOR MAKEUP AIR.
  
 7) AC-1 VERIFY COMPLIANCE WITH SECTION R403.3.6
 AIR-HANDLING UNITS IN ATTICS:
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 8) AC-1: PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2020-05-28 Cont ID  
Sent By jgomez Date 2020-05-28 Time 15:28 Rev Time 0.00
Received By jgomez Date 2020-05-28 Time 15:28 Sent To  
Notes
2020-05-28 15:29:46PLUMBING APPROVED WITH PROVISO:
 1- NO MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION.
 REVISE.
 SEC. P3108.2.1 FBC-RESIDENTIAL.
2020-05-28 11:35:15NEW SET OF PLANS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 5 Status F Date 2020-03-19 Cont ID  
Sent By jbaker Date 2020-03-19 Time 13:22 Rev Time 0.00
Received By jbaker Date 2020-03-19 Time 13:21 Sent To  
Notes
2020-03-25 13:48:59RISER DIAGRAM HAS 3 BATHROOM GROUPS AND PLANS SHOW ONLY
 2 BATHROOMS.
2020-03-19 13:23:44PERMIT 19091105
 1. SHOW LAVATORY ON SANITARY RISER DIAGRAM THAT IS
 LOCATED IN BATHROOM THAT HAS A TUB. THERE ARE TWO
 LAVATORIES AND ONLY ONE IS SHOWN. 2017 FBC 107.2.1 AND
 P3005.4 IN 2017 FRC.
 2. SHOW RELIEF VALVE PIPING FOR HOT WATER HEATER ON
 PLANS TO ITS TERMINATION POINT. 2017 FPC 504.6
 3. PROVIDE A HOT WATER HEATER DRAIN PAN AND SHOW
 DISCHARGE PIPING TO ITS TERMINATION POINT ON THE PLANS
 PER 2017 FPC 504.7
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-02-12 Cont ID  
Sent By jgomez Date 2020-02-12 Time 11:22 Rev Time 0.00
Received By jgomez Date 2020-02-12 Time 11:22 Sent To  
Notes
2020-02-12 11:23:17 
  
 DENIED:
 THIS BUILDING CAN NOT BE APPROVED WITH PROVISO. PLANS
 SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING TO
 CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN THIS
 LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE ZONING
 SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED SURVEY
 SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT COMPLETE
 FLOOR PLANS AND ENERGY CALCULATIONS FOR THE PROPOSED
 MODEL FOR COMPLETE REVIEW.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-12-19 Cont ID  
Sent By jgomez Date 2019-12-19 Time 09:32 Rev Time 0.00
Received By jgomez Date 2019-12-19 Time 09:32 Sent To  
Notes
2019-12-19 09:59:3912/18/19 MET WITH CHRISTOPHER BACHE (CONTRACTOR). HE
 AGREED TO PASS REVIEWS WITH PROVISO. JG.
  
 12/19/19 DENIED:
 THIS BUILDING CAN NOT BE APPROVED WITH PROVISO. PLANS
 SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING TO
 CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN THIS
 LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE ZONING
 SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED SURVEY
 SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT COMPLETE
 FLOOR PLANS AND ENERGY CALCULATIONS FOR THE PROPOSED
 MODEL.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-12-19 Cont ID  
Sent By jgomez Date 2019-12-11 Time 09:22 Rev Time 0.00
Received By jgomez Date 2019-12-11 Time 09:22 Sent To  
Notes
2019-12-19 10:00:2312/19/19 DENIED:
 PLANS SUBMITTED ARE FOR THE 5 BEDROOM MODEL. ACCORDING
 TO CONTRACTOR A DIFFERENT MODEL NEEDS TO BE BUILT IN
 THIS LOT BECAUSE THE 5 BEDROOM MODEL DOESN'T MEET THE
 ZONING SETBACKS. CONTRACTOR ONLY SUBMITTED THE REVISED
 SURVEY SHOWING THE NEW PROPOSED MODEL. NEED TO SUBMIT
 COMPLETE FLOOR PLANS AND ENERGY CALCULATIONS FOR THE
 PROPOSED MODEL.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-10-04 Cont ID  
Sent By gjohnson Date 2019-10-04 Time 13:06 Rev Time 0.00
Received By gjohnson Date 2019-10-04 Time 10:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-12-11 Cont ID  
Sent By jgomez Date 2019-12-11 Time 09:16 Rev Time 0.00
Received By jgomez Date 2019-12-11 Time 09:16 Sent To  
Notes
2019-12-11 09:17:31SHINGLES FL10124-R22

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By jgomez Date 2019-10-17 Time 15:24 Rev Time 0.00
Received By jgomez Date 2019-10-17 Time 15:23 Sent To  
Notes
2019-10-17 15:25:111- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) ROOF SHINGLES. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. NEED
 COVER PAGE TO VERIFY CURRENT CODE AND IF THE PRODUCT IS
 APPROVED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS

Review Stop Z ZONING
Rev No 3 Status P Date 2020-03-16 Cont ID  
Sent By rfalcone Date 2020-03-16 Time 16:07 Rev Time 0.00
Received By rfalcone Date 2020-03-16 Time 16:07 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-12-09 Cont ID  
Sent By rfalcone Date 2019-12-09 Time 14:12 Rev Time 0.00
Received By rfalcone Date 2019-12-09 Time 14:12 Sent To I
Notes
2019-12-09 14:12:2412/09/19 FAILED.
  
 PURUSANT ZLDR SEC. 94-72(A)(2)(B), MINIUMUM CORNER
 SETBACK FOR PRINCIPAL BUILDING IS 12.5 FEET. THE
 SETBACK PROVIDED ON THE PLANS IS 7 FEET ALONG 10TH
 STREET. PLEASE REVISE THE PLANS TO MEET THE CORNER
 SETBACK REQUIREMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT WEBSITE AT HTTPS://WPB.
 ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-07 Cont ID  
Sent By rfalcone Date 2019-10-07 Time 14:10 Rev Time 0.00
Received By rfalcone Date 2019-10-07 Time 14:10 Sent To I
Notes
2019-10-07 14:15:3210/07/19 FAILED.
  
 PURUSANT ZLDR SEC. 94-72(A)(2)(B), MINIUMUM CORNER
 SETBACK FOR PRINCIPAL BUILDING IS 12.5 FEET. THE
 SETBACK PROVIDED ON THE PLANS IS 7 FEET ALONG 10TH
 STREET. PLEASE REVISE THE PLANS TO MEET THE CORNER
 SETBACK REQUIREMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT WEBSITE AT HTTPS://WPB.
 ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved