Plan Review Details - Permit 19091092
Plan Review Stops For Permit 19091092
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-11-15 Cont ID  
Sent By pvalenti Date 2019-11-15 Time 12:51 Rev Time 0.00
Received By pvalenti Date 2019-11-15 Time 12:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-11-01 Cont ID  
Sent By pvalenti Date 2019-11-01 Time 15:06 Rev Time 0.00
Received By pvalenti Date 2019-11-01 Time 15:06 Sent To  
Notes
2019-11-01 15:09:55***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-10-29 Cont ID  
Sent By pvalenti Date 2019-10-29 Time 11:28 Rev Time 0.00
Received By pvalenti Date 2019-10-29 Time 11:28 Sent To  
Notes
2019-10-29 11:35:13***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-22 Cont ID  
Sent By jbrooks Date 2019-10-22 Time 08:41 Rev Time 0.00
Received By jbrooks Date 2019-10-22 Time 08:41 Sent To  
Notes
2019-10-24 07:24:3410/23 - SPOKE W/APPLICANT, GAVE OPTIONS. NUCORE
 (LAMINATE) WAS SUBMITTED, SPEC SHEET SHOWS COMPLIANCE
 BUT WAS TESTED WITH A DROPPED CEILING, APPEARS THAT
 THIS PRODUCT ALONE WILL NOT MEET STC/IIC REQUIREMENTS.
 WHISPERMAT HW WAS ALSO SUBMITTED AS PROPOSED
 UNDERLAYMENT; WE HAVE STC/IIC ON FILE BUT NO FLAME
 SPREAD. ADVISED APPLICANT TO CONTACT WHISPERMAT
 TECHNICAL REP AND OBTAIN FLAME SPREAD TEST IF
 AVAILABLE. [email protected]
  
  
2019-10-22 08:42:11JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 1207.2, 1207.3 PLEASE NOTE THAT TEST REPORTS
 ARE REQUIRED - MANUFACTURER SPEC SHEETS ARE NOT
 ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT). SECOND REQUEST.
 2. FBC B 1207.2, 1207.3 THE TEST REPORT CANNOT INCLUDE
 A DROPPED GYPSUM CEILING. PROVIDE A COPY OF THE TEST
 REPORT. SECOND REQUEST.
 3. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. SECOND REQUEST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-01 Cont ID  
Sent By jbrooks Date 2019-10-01 Time 09:20 Rev Time 0.00
Received By jbrooks Date 2019-10-01 Time 09:20 Sent To  
Notes
2019-10-01 09:20:24JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1.FBC B 107.2.1. PROVIDE TWO SETS OF FLOOR
 PLANS/BUILDING FOOT PRINT SHOWING LOCATION OF PROPOSED
 FLOORING TO BE REPLACED.
 2. FBC B 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 3. FBC B 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
 4. FBC B 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 5. PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-11-15 Cont ID  
Sent By pvalenti Date 2019-11-15 Time 12:51 Rev Time 0.00
Received By pvalenti Date 2019-11-13 Time 15:56 Sent To  
Notes
2019-11-14 15:56:41RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-01 Cont ID  
Sent By pvalenti Date 2019-11-01 Time 15:11 Rev Time 0.00
Received By pvalenti Date 2019-10-30 Time 13:53 Sent To  
Notes
2019-10-31 13:54:00RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-22 Cont ID  
Sent By jbrooks Date 2019-10-22 Time 08:42 Rev Time 0.00
Received By jbrooks Date 2019-10-15 Time 14:07 Sent To  
Notes
2019-10-16 14:08:01RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-01 Cont ID  
Sent By jbrooks Date 2019-10-01 Time 09:20 Rev Time 0.00
Received By jbrooks Date 2019-09-26 Time 13:41 Sent To  
Notes
2019-09-27 13:41:37BLDG <5K