Plan Review Details - Permit 19090997
Plan Review Stops For Permit 19090997
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-04-07 Cont ID  
Sent By pvalenti Date 2020-04-07 Time 06:53 Rev Time 0.00
Received By pvalenti Date 2020-04-07 Time 06:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-03-24 Cont ID  
Sent By jbrooks Date 2020-03-24 Time 08:39 Rev Time 0.00
Received By jbrooks Date 2020-03-24 Time 08:39 Sent To  
Notes
2020-03-24 08:40:02JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. REVISE FLOOR PLANS/BUILDING FOOT
 PRINT AND DESIGN PRESSURE CALCULATIONS PAGE SHOWING
 LOCATION OF PROPOSED SHUTTERS TO BE INSTALLED AND
 PROVIDE CORRECTED DIMENSIONS OF EACH OPENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-13 Cont ID  
Sent By jgomez Date 2020-03-13 Time 17:56 Rev Time 0.00
Received By jgomez Date 2020-03-13 Time 15:38 Sent To  
Notes
2020-03-13 15:38:56RESIDENTIAL (R3) SHUTTERS THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MET WITH MR. ROTHMAN. I PRINTED THE FLORIDA PRODUCT
 APPROVAL HE SAID WAS THE CORRECT ONE (CLEAR PANEL) TO
 SEE IF THE PERMIT COULD BE APPROVED. AFTER REVIEWING
 THE SHUTTERS INSTALLATION SCHEDULE I NOTICED THAT THE
 OPENINGS DIMENSIONS WERE INCORRECT. ALSO, THE CLEAR
 PANEL SHUTTERS COULD NOT BE USED BASED ON THE SPECIFIED
 DESIGN PRESSURES AND SHUTTERS SPAN. WENT OVER THESE
 COMMENTS WITH MR ROTHMAN. I TOLD HIM THAT HE NEEDS TO
 COMPLETELY REVISE THE INSTALLATION SCHEDULE AND
 RE-SUBMIT FOR REVIEW.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jbrooks Date 2020-03-12 Time 08:07 Rev Time 0.00
Received By jbrooks Date 2020-03-12 Time 08:07 Sent To  
Notes
2020-03-12 08:08:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC R 301 FAC9N-3. SUBMITTED FLORIDA PRODUCT
 APPROVAL COVER PAGE FL28390 DO NOT MATCH SUBMITTED
 INSTALLATION INSTRUCTIONS FL6416.1. PLEASE PROVIDE TWO
 COMPLETE SETS OF PRODUCT APPROVALS FOR THE STORM PANELS
 USED.
 2. FBC R 301. PLEASE COMPLETE THE ?SCHEDULE FOR
 INSTALLATION OF OPENINGS PROTECTIVE DEVICES? ACCORDING
 TO THE PRODUCT APPROVAL USED. (IF APPLICABLE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-26 Cont ID  
Sent By jbrooks Date 2019-09-26 Time 14:14 Rev Time 0.00
Received By jbrooks Date 2020-03-12 Time 08:06 Sent To  
Notes
2019-09-26 14:14:58JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET): INFORMATION MUST CORRESPOND WITH
 SUBMITTED PRODUCT APPROVALS.
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
 2. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT
 APPROVAL, PROVIDE THE FOLLOWING FOR EACH PRODUCT: COVER
 SHEET (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE
 CODE VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT) EVALUATION REPORT;
 INSTALLATION INSTRUCTIONS. PROVIDE TWO COMPLETE SETS
 FOR THE PROPOSED STORM PANELS USED
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By fmittner Date 2020-03-19 Time 10:01 Rev Time 0.00
Received By fmittner Date 2020-03-19 Time 10:01 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-03-13 Cont ID  
Sent By fmittner Date 2020-03-13 Time 11:56 Rev Time 0.00
Received By fmittner Date 2020-03-13 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-04-07 Cont ID  
Sent By pvalenti Date 2020-04-07 Time 06:53 Rev Time 0.00
Received By pvalenti Date 2020-04-06 Time 17:15 Sent To  
Notes
2020-04-06 17:16:06TO PV DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-24 Cont ID  
Sent By jbrooks Date 2020-03-24 Time 08:40 Rev Time 0.00
Received By jbrooks Date 2020-03-17 Time 09:36 Sent To  
Notes
2020-03-19 15:53:553/19 RESUB ROUTED TO JBROOKS
2020-03-18 09:36:19RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-13 Cont ID  
Sent By jgomez Date 2020-03-13 Time 18:15 Rev Time 0.00
Received By jgomez Date 2020-03-13 Time 15:37 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-13 Cont ID  
Sent By jbrooks Date 2020-03-13 Time 13:30 Rev Time 0.00
Received By lmarchan Date 2020-03-10 Time 13:20 Sent To  
Notes
2020-03-12 10:11:243/12 ROUTED TO HISTORIC INBOX
2020-03-11 13:21:11RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-26 Cont ID  
Sent By jbrooks Date 2019-09-26 Time 14:15 Rev Time 0.00
Received By jbrooks Date 2019-09-24 Time 14:54 Sent To  
Notes
***NONE***