Plan Review Stops For Permit 19090882 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2020-01-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-01-06 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-01-06 |
Time |
15:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2019-12-19 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-12-19 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-12-19 |
Time |
08:53 |
Sent To |
|
|
Notes |
2019-12-19 08:55:54 | COMMENT FROM FIRST REVIEW NOT ADDRESSED. | | PLEASE PROVIDE LETTER STATING THAT YOU HAVE BEEN IN | | COMPLIANCE WITH PBC HEALTH DEPARTMENT REQUIREMENTS FOR | | ASBESTOS. | | THIS SHOULD HAVE OCCURED DURING DEMO PERMIT 19050002. | | | | DYLAN BATTLES | | 561-805-6718 | | [email protected] | | |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2019-11-15 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-15 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-15 |
Time |
16:13 |
Sent To |
|
|
Notes |
2019-11-15 16:13:37 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM | | BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME | | NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION. | | HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA | | EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT | | LINE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-12-19 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-12-19 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-12-19 |
Time |
08:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-18 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-12 |
Time |
11:02 |
Sent To |
|
|
Notes |
2019-11-18 15:29:47 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 19090882 | | REVIEWED: NOVEMBER 18, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC[B] = FBC BUILDING | | FBC[EXISTING] = FBC EXISTING BUILDING | | FBC[A] = FBC ACCESSIBILITY | | FBC[E] = FBC ENERGY CONSERVATION | | | | 1) 404.6 FBC[B]ENCLOSURE OF ATRIUMS. ATRIUM SPACES | | SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR | | FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 707 | | OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH | | SECTION 711, OR BOTH. | | HOW ARE BOTH LEVELS OF ATRIUM SEPARATED FROM ADJACENT | | SPACES? THE LIFE SAFETY PLAN SHOW A DASH DOT LINE ON | | THE FIRST FLOOR THAT MAY REPRESENT 1 HOUR RATING, BUT | | IT IS NOT DENOTED WHAT THE LINE REPRESENTS. | | ALSO, IT WAS DISCUSSED IN A MEETING ABOUT FIRE CURTAINS | | AT THE 2 ND FLOOR OPENINGS. | | HOW IS THE SECOND LEVEL SEPARATED AS REQUIRED IN 404.6? | | | | 2) 716.5 FBC TABLE[B]OPENING FIRE PROTECTION | | ASSEMBLIES, RATINGS AND MARKINGS. | | PLEASE LIST FIRE RATING OF ALL EXISTING DOORS IN RATED | | WALLS AND SHAFTS. | | ALSO, PROVIDE SPECIFICATIONS FOR ANY FIRE CURTAINS | | BEING INSTALLED, OR INDICATE THAT THEY WILL BE A | | DEFERRED SUBMITTAL. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2019-10-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-10-21 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-10-10 |
Time |
17:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2019-12-05 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-12-05 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-12-04 |
Time |
16:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-10-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-10-08 |
Time |
14:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-01-03 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-01-03 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-12-03 |
Time |
08:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-11-18 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-18 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-10-04 |
Time |
13:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2020-01-21 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-01-21 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-01-07 |
Time |
13:52 |
Sent To |
|
|
Notes |
2020-01-21 11:36:58 | 1/21/20 IMPACT FEES OFFICE DETERMINED NO FEES DUE, | | IMPACT FEES OFFICE STAMPED PLANS. | 2020-01-07 13:52:32 | 1/7/20 EMAILED IMPACT FEE OFFICE. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2019-11-15 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-15 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-15 |
Time |
14:50 |
Sent To |
|
|
Notes |
2019-11-15 14:50:43 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2019-12-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-12-30 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-12-30 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2019-11-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-11-06 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-11-06 |
Time |
07:57 |
Sent To |
|
|
Notes |
2019-11-06 15:17:15 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19090882 | | 11/5/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS M-301 & M-501: IT APPEARS AHU & CU 1-7 HAVE | | BEEN MISLABELED AS AHU & CU 1-2 ON THE FLOOR PLAN | | LAYOUT- PLEASE CORRECT. | | | | 2) M-501: PROVIDE O/A CALCULATIONS FOR THE NEW RETAIL | | AC SYSTEM- TABLE 403.3.1.1 FBC M. | | | | 3) M-310: VERIFY THE RETAIL O/A INTAKE LOCATION IS IN | | COMPLIANCE WITH SECTION 401.4 FBC M FOR REQUIRED | | CLEARANCES. | | | | 4) M-303: A FIRE/SMOKE DAMPER IS REQUIRED AT THE | | PENETRATION OF THE 12X12 OA DUCT INTO THE SHAFT PER | | 607.5.5 FBC M. | | | | 5) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND | | INSTALLATION INSTRUCTIONS FOR THE FIRE DAMPERS AND | | FIRE/SMOKE DAMPERS (IF REQUIRED). THE SPECS MAY BE | | DEFERRED SUBMITTALS PER SECTION 107.3.4.1 WPB. | | | | 6) M-301: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE | | NEW RETAIL AHU- SECTION 307.2.1 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-01-03 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2020-01-03 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2020-01-03 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-11-14 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-11-14 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-11-08 |
Time |
14:22 |
Sent To |
|
|
Notes |
2019-11-14 08:34:00 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE SHOW THE FOLLOWING REQUIRED ACCESSIBILITY | | DETAILS PER WPB AMEND TO FBC 107.2.1 | | | | A)ON ALL ENLARGED BATHROOM DETAILS LABEL CLEAR FLOOR | | SPACES FOR FBC ACC 604.3.1 SIZE. CLEARANCE AROUND A | | WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED | | PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES \ | | MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL. | | | | B)ON ALL ENLARGED BATHROOM DETAILS AND BREAK ROOM SINK | | LABEL CLEAR FLOOR SPACES AND SHALL BE CENTERED FOR | | LAVATORY'S AND SINKS, FBC ACC 606.2 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED. EXCEPTIONS: 1.A | | PARALLEL APPROACH COMPLYING WITH 305 SHALL BE PERMITTED | | TO A KITCHEN SINK, IN A SPACE WHERE A COOK TOP OR | | CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET BARS. | | | | C)FBC ACC 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET | | ABOVE THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND | | 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. | | SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED | | POSITION. | | | | D)FBC ACC 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR | | SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES | | MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES | | MINIMUM FROM THE REAR WALL. | | | | E)FBC ACC 604.5.2 REAR WALL.THE REAR WALL GRAB BAR | | SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE | | CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE | | SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. | | | | F)609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE | | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM | | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED | | TO THE TOP OF THE GRIPPING SURFACE, | | | | G)FBC ACC 604.7 DISPENSERS.TOILET PAPER DISPENSERS | | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM | | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET | | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET | | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 | | INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE | | LOCATED BEHIND GRAB BARS | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-12-19 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-12-19 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-12-19 |
Time |
08:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-11-15 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-11-15 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-11-15 |
Time |
16:09 |
Sent To |
|
|
Notes |
2019-11-15 16:10:18 | ALL SHEETS OK FOR FIRST REVIEW. | | ALL ADDITIONAL SHEETS SUPPLIED FOR 2ND REVIEW WILL NEED | | TO BE DIGITALLY SIGNED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-12-31 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2019-12-31 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2019-12-31 |
Time |
13:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-11-14 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2019-11-14 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2019-11-14 |
Time |
15:05 |
Sent To |
|
|
Notes |
2019-11-14 15:07:51 | 1. VERSA WALL NEXT TO THE PATIO ENTRANCE CANNOT BE MORE | | THAN 4 FEET IN HEIGHT. | | 2. NEW DOORS ON RETAIL AREA AND EMERGENCY EXIT ALONG | | DATURA STREET CANNOT ENCROACH INTO ROW WHEN OPEN. | | 3. LANDSCAPE PLANS SHALL BE SEPARATED AND SUBMITTED | | UNDER A SEPARATE LANDSCAPE PLAN. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|