Plan Review Details - Permit 19090882
Plan Review Stops For Permit 19090882
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-01-06 Cont ID  
Sent By shill Date 2020-01-06 Time 15:52 Rev Time 0.00
Received By shill Date 2020-01-06 Time 15:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-12-19 Cont ID  
Sent By dbattles Date 2019-12-19 Time 08:53 Rev Time 0.00
Received By dbattles Date 2019-12-19 Time 08:53 Sent To  
Notes
2019-12-19 08:55:54COMMENT FROM FIRST REVIEW NOT ADDRESSED.
 PLEASE PROVIDE LETTER STATING THAT YOU HAVE BEEN IN
 COMPLIANCE WITH PBC HEALTH DEPARTMENT REQUIREMENTS FOR
 ASBESTOS.
 THIS SHOULD HAVE OCCURED DURING DEMO PERMIT 19050002.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By dbattles Date 2019-11-15 Time 16:13 Rev Time 0.00
Received By dbattles Date 2019-11-15 Time 16:13 Sent To  
Notes
2019-11-15 16:13:37PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By dbattles Date 2019-12-19 Time 08:49 Rev Time 0.00
Received By dbattles Date 2019-12-19 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-11-18 Cont ID  
Sent By dbattles Date 2019-11-18 Time 15:29 Rev Time 0.00
Received By dbattles Date 2019-11-12 Time 11:02 Sent To  
Notes
2019-11-18 15:29:47BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19090882
 REVIEWED: NOVEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 404.6 FBC[B]ENCLOSURE OF ATRIUMS. ATRIUM SPACES
 SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR
 FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 707
 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
 HOW ARE BOTH LEVELS OF ATRIUM SEPARATED FROM ADJACENT
 SPACES? THE LIFE SAFETY PLAN SHOW A DASH DOT LINE ON
 THE FIRST FLOOR THAT MAY REPRESENT 1 HOUR RATING, BUT
 IT IS NOT DENOTED WHAT THE LINE REPRESENTS.
 ALSO, IT WAS DISCUSSED IN A MEETING ABOUT FIRE CURTAINS
 AT THE 2 ND FLOOR OPENINGS.
 HOW IS THE SECOND LEVEL SEPARATED AS REQUIRED IN 404.6?
  
 2) 716.5 FBC TABLE[B]OPENING FIRE PROTECTION
 ASSEMBLIES, RATINGS AND MARKINGS.
 PLEASE LIST FIRE RATING OF ALL EXISTING DOORS IN RATED
 WALLS AND SHAFTS.
 ALSO, PROVIDE SPECIFICATIONS FOR ANY FIRE CURTAINS
 BEING INSTALLED, OR INDICATE THAT THEY WILL BE A
 DEFERRED SUBMITTAL.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-10-21 Cont ID  
Sent By jleahy Date 2019-10-21 Time 11:43 Rev Time 0.00
Received By jleahy Date 2019-10-10 Time 17:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-12-05 Cont ID  
Sent By pleduc Date 2019-12-05 Time   Rev Time 0.00
Received By pleduc Date 2019-12-04 Time 16:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-10-28 Cont ID  
Sent By pleduc Date 2019-10-28 Time   Rev Time 0.00
Received By pleduc Date 2019-10-08 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2019-12-03 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-18 Cont ID  
Sent By dbattles Date 2019-11-18 Time 15:29 Rev Time 0.00
Received By dbattles Date 2019-10-04 Time 13:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-01-21 Cont ID  
Sent By cpuell Date 2020-01-21 Time 11:35 Rev Time 0.00
Received By cpuell Date 2020-01-07 Time 13:52 Sent To  
Notes
2020-01-21 11:36:581/21/20 IMPACT FEES OFFICE DETERMINED NO FEES DUE,
 IMPACT FEES OFFICE STAMPED PLANS.
2020-01-07 13:52:321/7/20 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By dbattles Date 2019-11-15 Time 14:50 Rev Time 0.00
Received By dbattles Date 2019-11-15 Time 14:50 Sent To  
Notes
2019-11-15 14:50:43109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-30 Cont ID  
Sent By ccole Date 2019-12-30 Time 15:17 Rev Time 0.00
Received By ccole Date 2019-12-30 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-06 Cont ID  
Sent By ccole Date 2019-11-06 Time 14:05 Rev Time 0.00
Received By ccole Date 2019-11-06 Time 07:57 Sent To  
Notes
2019-11-06 15:17:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090882
 11/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-301 & M-501: IT APPEARS AHU & CU 1-7 HAVE
 BEEN MISLABELED AS AHU & CU 1-2 ON THE FLOOR PLAN
 LAYOUT- PLEASE CORRECT.
  
 2) M-501: PROVIDE O/A CALCULATIONS FOR THE NEW RETAIL
 AC SYSTEM- TABLE 403.3.1.1 FBC M.
  
 3) M-310: VERIFY THE RETAIL O/A INTAKE LOCATION IS IN
 COMPLIANCE WITH SECTION 401.4 FBC M FOR REQUIRED
 CLEARANCES.
  
 4) M-303: A FIRE/SMOKE DAMPER IS REQUIRED AT THE
 PENETRATION OF THE 12X12 OA DUCT INTO THE SHAFT PER
 607.5.5 FBC M.
  
 5) PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE FIRE DAMPERS AND
 FIRE/SMOKE DAMPERS (IF REQUIRED). THE SPECS MAY BE
 DEFERRED SUBMITTALS PER SECTION 107.3.4.1 WPB.
  
 6) M-301: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 NEW RETAIL AHU- SECTION 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 11:31 Rev Time 0.00
Received By gjohnson Date 2020-01-03 Time 11:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By gjohnson Date 2019-11-14 Time 08:33 Rev Time 0.00
Received By gjohnson Date 2019-11-08 Time 14:22 Sent To  
Notes
2019-11-14 08:34:001ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE FOLLOWING REQUIRED ACCESSIBILITY
 DETAILS PER WPB AMEND TO FBC 107.2.1
  
 A)ON ALL ENLARGED BATHROOM DETAILS LABEL CLEAR FLOOR
 SPACES FOR FBC ACC 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES \
 MINIMUM MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 B)ON ALL ENLARGED BATHROOM DETAILS AND BREAK ROOM SINK
 LABEL CLEAR FLOOR SPACES AND SHALL BE CENTERED FOR
 LAVATORY'S AND SINKS, FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED. EXCEPTIONS: 1.A
 PARALLEL APPROACH COMPLYING WITH 305 SHALL BE PERMITTED
 TO A KITCHEN SINK, IN A SPACE WHERE A COOK TOP OR
 CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET BARS.
  
 C)FBC ACC 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET
 ABOVE THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND
 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT.
 SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION.
  
 D)FBC ACC 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR
 SHALL BE 42 INCHES LONG MINIMUM, LOCATED 12 INCHES
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL.
  
 E)FBC ACC 604.5.2 REAR WALL.THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE.
  
 F)609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
  
 G)FBC ACC 604.7 DISPENSERS.TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-12-19 Cont ID  
Sent By dbattles Date 2019-12-19 Time 08:17 Rev Time 0.00
Received By dbattles Date 2019-12-19 Time 08:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-11-15 Cont ID  
Sent By dbattles Date 2019-11-15 Time 16:09 Rev Time 0.00
Received By dbattles Date 2019-11-15 Time 16:09 Sent To  
Notes
2019-11-15 16:10:18ALL SHEETS OK FOR FIRST REVIEW.
 ALL ADDITIONAL SHEETS SUPPLIED FOR 2ND REVIEW WILL NEED
 TO BE DIGITALLY SIGNED.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-12-31 Cont ID  
Sent By aaponte Date 2019-12-31 Time 13:13 Rev Time 0.00
Received By aaponte Date 2019-12-31 Time 13:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-11-14 Cont ID  
Sent By aaponte Date 2019-11-14 Time 15:05 Rev Time 0.00
Received By aaponte Date 2019-11-14 Time 15:05 Sent To  
Notes
2019-11-14 15:07:511. VERSA WALL NEXT TO THE PATIO ENTRANCE CANNOT BE MORE
 THAN 4 FEET IN HEIGHT.
 2. NEW DOORS ON RETAIL AREA AND EMERGENCY EXIT ALONG
 DATURA STREET CANNOT ENCROACH INTO ROW WHEN OPEN.
 3. LANDSCAPE PLANS SHALL BE SEPARATED AND SUBMITTED
 UNDER A SEPARATE LANDSCAPE PLAN.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.