2019-10-29 07:41:40 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| HEADING ?SHUTTER GLASS SEPARATION?; PROVIDE INFORMATION |
| FROM SHEET 11 FL1850. COLUMN HEADING ?SHUTTER SPAN?; |
| PROVIDE INFORMATION FROM SHEET 5 FL1850, THE TOP OF THE |
| SHUTTER BLADE TO THE BOTTOM OF THE SHUTTER BLADES |
| LENGTH. COLUMN HEADING ?MINIMUM EDGE DISTANCE?; PROVIDE |
| INFORMATION FROM SHEET 16 & 17 FL1850. COLUMN HEADING |
| ?ANCHOR SPACING? PROVIDE INFORMATION FROM SHEET 15 |
| FL1850. EXAMPLE SUBSTRATE SOUTHERN PINE, MAXIMUM SPAN |
| 7?-0? A.S.D DESIGN NEGATIVE PRESSURE RATING (PSF) 60 |
| WALL MOUNTINGS P & Q ANCHOR SPACING IS 4? MAXIMUM. |
| SECOND REQUEST |
| |