2019-11-05 15:31:18 | SEE PERMIT 19071543 FOR GATE WORK JLEAHY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-11-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-09-25 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-09-25 |
Time |
09:35 |
Sent To |
|
|
Notes |
2019-09-25 09:36:02 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107, SCOPE NOT CLEAR. IS THE GATE UNDER ANOTHER | | PERMIT? IF YES, THAT PERMIT NEEDS TO BE ISSUED FIRST | | AND THE TWO SHOULD BE TRAVELLING TOGETHER TO AVOID | | DUPLICATIVE WORK. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2020-01-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-01-09 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-01-09 |
Time |
14:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2019-12-19 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-12-19 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-12-19 |
Time |
11:35 |
Sent To |
|
|
Notes |
2019-12-19 11:41:42 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER SHOWS 4 MOTORS AND PANEL SCHEDULE ONLY SHOWS 2 | | ??? PLEASE EXPLAIN. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-11-05 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-11-05 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-11-05 |
Time |
15:20 |
Sent To |
|
|
Notes |
2019-11-05 15:29:38 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PANEL SCHEDULE SHOWS 3 MOTORS I DO NOT SEE THREE | | MOTORS PLEASE INDICATE WHERE THESE MOTORS ARE LOCATED. | | HOW FAR FROM THE PANEL ARE THESE MOTORS (GATE OPENERS) | | LOCATED | | | | 2) VALUE IS TO INCLUDE THE VALUE OF THREE GATE OPENERS | | IF THERE IS THREE OR HOW EVER MANY ARE BEING INSTALLED. | | SHOW BREQAK DOWN OF VALUE FOR LABOR AND EQUIPMENT | | GATE OPENERS WERE DESIGNATED AS FUTURE ON ORIGINAL | | PERMIT . |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-09-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-09-25 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-09-25 |
Time |
08:18 |
Sent To |
Z |
|
Notes |
2019-09-25 09:30:43 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NEED TO SHOW MORE DETAIL OF YOUR WORK!!! | | | | ARE YOU INSTALLING THE GATES ALSO ????? | | | | WHAT SIZE PIPES IN THE GROUND TO GATES AND CARD READERS | | SIZE OF WIRE TO GATES. | | | | VALUE FOR THE WORK IS LOW PLEASE SUBMIT A SIGNED | | CONTRACT.. | | | | ONLY ONE COPY OF SITE PLAN.. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2019-10-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-10-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-10-28 |
Time |
12:48 |
Sent To |
E |
|
Notes |
2019-10-28 12:51:23 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) A KNOX KEY SWITCH IS REQUIRED. | | | | PLEASE ENSURE COMPLIANCE. | | | | | | 2) BOTH GATES SHALL OPEN WHEN KNOX KEY SWITCH IS | | ACTIVATED FOR FD ACCESS AND EGRESS. | | | | PLEASE ENSURE COMPLIANCE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2019-10-02 |
|
|
Cont ID |
|
Sent By |
J.Walker |
Date |
2019-10-02 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-10-02 |
Time |
|
Sent To |
I |
|
Notes |
2019-10-02 07:39:45 | SUBMITTED PLANS FAIL TO INDECATE FIRE DEPARTMENT KNOX | | KEY SWITCH AND SEQUENCE OF GATE OPPERATION | | NFPA 1 CH 18 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-12-19 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-12-19 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-12-17 |
Time |
14:06 |
Sent To |
|
|
Notes |
2019-12-18 14:06:50 | RESUB ROUTED TO JLEAHY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-11-06 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-11-06 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-10-18 |
Time |
13:46 |
Sent To |
|
|
Notes |
2019-10-21 13:46:58 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-10-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-10-02 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-09-20 |
Time |
15:22 |
Sent To |
|
|
Notes |
2019-09-25 07:03:03 | TO JL DESK | | | 2019-09-23 15:22:16 | ELEC <5K |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-10-25 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2019-10-25 |
Time |
09:37 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2019-10-25 |
Time |
09:37 |
Sent To |
FIRE |
|
Notes |
2019-10-25 09:37:39 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 10.25.2019 | | PERMIT NO.: 19090816 | | ________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. ELECTRICAL WORK ONLY! SEE PERMIT #19071543 FOR GATE | | INSTALLATION. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-09-27 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2019-09-27 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2019-09-27 |
Time |
10:43 |
Sent To |
FIRE |
|
Notes |
2019-09-27 10:43:44 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 09.27.2019 | | PERMIT NO.: 19090816 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PLEASE CLARIFY THE SCOPE OF THE PERMIT. IS THIS ONLY | | ELECTRICAL WORK FOR THE GATES? ARE THE GATES UNDER A | | SEPARATE PERMIT? IF SO, THE PRIMARY PERMIT # SHOULD BE | | IDENTIFIED, AND THE SUB-PERMIT WILL NOT BE ISSUED UNTIL | | THE PRIMARY PERMIT IS ISSUED. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|