Plan Review Details - Permit 19090623
Plan Review Stops For Permit 19090623
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-19 Cont ID  
Sent By jgomez Date 2019-09-19 Time 16:40 Rev Time 0.00
Received By jgomez Date 2019-09-19 Time 16:26 Sent To  
Notes
2019-09-19 16:40:35RECEIVED E-MAIL FROM
 STACEY LOFTUS
 RANGER ROOFING CORPORATION
 1508 53RD STREET
 WEST PALM BEACH, FLORIDA 33407
 OFFICE: 561-842-6943
 FAX: 561-842-6969
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-19 Cont ID  
Sent By jgomez Date 2019-09-19 Time 09:51 Rev Time 0.00
Received By jgomez Date 2019-09-19 Time 08:37 Sent To  
Notes
2019-09-19 10:09:54RESIDENTIAL (R3) ROOFING BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ROOF TILE NOA 14-0102.04 SUBMITTED EXPIRED ON
 02/13/19. NEED TO PROVIDE CURRENT NOA.
 FAC 61G20-3.001.
  
 2- - ROOF TILE NOA SUBMITTED: CLEARLY MARK ROOF TILE
 FASTENING METHOD AS REQUIRED BY CITY POLICY FOR ALL
 ROOFING PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R3012.1 FBC-RESIDENTIAL. .
  
 3- ROOF TILE ADHESIVE FLORIDA PRODUCT APPROVAL
 FL6332-R8 SUBMITTED: CLEARLY MARK PADDY SIZE AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO
 VERIFY COMPLIANCE WITH SEC. R301.2.1 FBC-RESIDENTIAL.
  
 4- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL14317-R9 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
  
 A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
  
 B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION
 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM
 FRSA/TRI APRIL 2012 (04-12), APPENDIX A, TABLE 1.
 CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-19 Cont ID  
Sent By jgomez Date 2019-09-19 Time 16:40 Rev Time 0.00
Received By jgomez Date 2019-09-19 Time 16:39 Sent To I
Notes
2019-09-19 16:40:15RECEIVED E-MAIL FROM
 STACEY LOFTUS
 RANGER ROOFING CORPORATION
 1508 53RD STREET
 WEST PALM BEACH, FLORIDA 33407
 OFFICE: 561-842-6943
 FAX: 561-842-6969
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-19 Cont ID  
Sent By jgomez Date 2019-09-19 Time 10:10 Rev Time 0.00
Received By jgomez Date 2019-09-17 Time 10:59 Sent To I
Notes
2019-09-18 10:59:52REROOF BIN


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved