Plan Review Details - Permit 19090403
Plan Review Stops For Permit 19090403
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2020-01-27 Cont ID  
Sent By rmcdouga Date 2020-01-27 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2020-01-27 Time 15:02 Sent To  
Notes
2020-01-27 15:04:48THIS IS NOT SUBJECT TO AIPP PER EMAIL FROM SYBILLE
 WELTER ON 1/27/2020.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-01-22 Cont ID  
Sent By rmcdouga Date 2020-01-22 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2020-01-22 Time 12:46 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-12-16 Cont ID  
Sent By rmcdouga Date 2019-12-16 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2019-12-16 Time 17:21 Sent To  
Notes
2019-12-16 17:21:48PREVIOUS COMMENT NOT ADDRESSED.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-10-09 Cont ID  
Sent By rmcdouga Date 2019-10-09 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2019-10-09 Time 13:09 Sent To  
Notes
2019-10-09 15:23:18FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-01-28 Cont ID  
Sent By rmcdouga Date 2020-01-28 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2020-01-28 Time 16:19 Sent To  
Notes
2020-01-28 16:32:13BUILDING PROVISOS
  
 1) AN ABANDONMENT OF EASEMENT DOCUMENT FROM FPL IS
 REQUIRED TO BE SUBMITTED.
  
 2) DEFERRED SUBMITTALS ARE LISTED ON SHEET GI002 AND
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED
 PRIOR TO INSTALLING.
  
 3) THE WALK-IN COOLER IS REQUIRED TO BE PERMITTED
 SEPARATELY AND WILL BE REQUIRED TO COMPLY WITH FBC
 2603.4.1.3.
  
  
  
  
  
  
2020-01-28 16:31:07 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-24 Cont ID  
Sent By rmcdouga Date 2020-01-24 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2020-01-22 Time 18:55 Sent To  
Notes
2020-01-23 19:12:57PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) INCOMPLETE. THE REQUIRED THRESHOLD FORMS WITH THE
 CONTRACTOR'S AND OWNER'S NOTARIZED SIGNATURES WERE NOT
 UPLOADED WITH THE REST OF THE THRESHOLD DOCUMENTS.
 PLEASE OBTAIN AND COMPLETE THE CITY OF WEST PALM
 BEACH'S THRESHOLD INSPECTION DOCUMENT AND SUBMIT THE
 NOTARIZED FORMS THAT ARE REQUIRED. THE ORIGINAL
 NOTARIZED DOCUMENTS WILL NEED TO BE SUBMITTED AT THE
 FRONT COUNTER OF THE BUILDING DEPARTMENT. THIS BUILDING
 QUALIFIES AS A THRESHOLD BUILDING. PLEASE SUBMIT THE
 REQUIRED THRESHOLD DOCUMENTS. FBC 110.8 THRESHOLD
 BUILDING / FL S. S. 553.71(7) "THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2) PROVISO. ART IN PUBLIC PLACES TO BE RESOLVED PRIOR
 TO C.O.
  
 3) NOT COMPLIED. THESE PLANS WILL BE REQUIRED TO BE
 REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF ANY
 IMPACT FEES ARE REQUIRED TO BE PAID. SEE COMMENTS IN
 THE IMPACT FEE REVIEW STOP.
  
 4) PROVISO. ABANDONMENT OF EASEMENT DOCUMENT FROM FPL
 TO BE SUBMITTED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) PROVISO. THE WALK-IN COOLER IS REQUIRED TO BE
 PERMITTED SEPARATELY AND WILL BE REQUIRED TO COMPLY
 WITH FBC 2603.4.1.3.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) PROVISO. DEFERRED SUBMITTALS ARE LISTED ON SHEET
 GI002.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-16 Cont ID  
Sent By rmcdouga Date 2019-12-16 Time 18:37 Rev Time 0.00
Received By rmcdouga Date 2019-12-13 Time 17:35 Sent To  
Notes
2019-12-16 17:22:51PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) INCOMPLETE. PLEASE OBTAIN AND COMPLETE THE CITY OF
 WEST PALM BEACH'S THRESHOLD INSPECTION DOCUMENT AND
 SUBMIT THE NOTARIZED FORMS THAT ARE REQUIRED. THE
 ORIGINAL NOTARIZED DOCUMENTS WILL NEED TO BE SUBMITTED
 AT THE FRONT COUNTER OF THE BUILDING DEPARTMENT. W.P.B.
 AMENDMENT 110.8.4.4 REQUIRES THE THRESHOLD STATEMENT IN
 1 C) TO BE ON ALL PLANS FOR THE BUILDING THAT ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD.
 THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. PLEASE
 SUBMIT THE REQUIRED THRESHOLD DOCUMENTS. FBC 110.8
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORD-KEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) NOT COMPLIED. THIS IS PHASE 2 OF THE RENOVATION OF
 AND ADDITION THE EXISTING CLUB HOUSE. THE ENTIRE SCOPE
 OF BOTH PHASES NEEDS TO BE CONSIDERED. IT APPEARS THAT
 THIS PROJECT WILL BE SUBJECT TO THE "ART IN PUBLIC
 PLACES" REQUIREMENTS. A HOLD HAS BEEN PLACED ON THE CC
 BY ZONING. PLEASE CONTACT SYBILLE WELTER AT
 561-822-1515 FOR MORE INFORMATION.
 THIS PROJECT IS REQUIRED TO COMPLY WITH "ART IN PUBLIC
 PLACES".
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 3) WILL COMPLY. THESE PLANS WILL BE REQUIRED TO BE
 REVIEWED BY PALM BEACH COUNTY TO DETERMINE IF ANY
 IMPACT FEES ARE REQUIRED TO BE PAID. SEE COMMENTS IN
 THE IMPACT FEE REVIEW STOP.
  
 4) NOT COMPLIED. THE APPROVED SITE PLAN ON PAGE 006 AND
 THE OVERALL ARCHITECTURAL SITE PLAN ON PAGE 030 BOTH
 SHOW A CORNER OF THE CLUBHOUSE EXPANSION ENCROACHING
 INTO THE 10' WIDE FLORIDA POWER AND LIGHT UTILITY
 EASEMENT. SUBMIT TWO SETS OF AN EASEMENT RELEASE FROM
 FPL THAT ADDRESSES THIS ISSUE.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) WILL COMPLY. THE WALK-IN COOLER IS REQUIRED TO BE
 PERMITTED SEPARATELY AND WILL BE REQUIRED TO COMPLY
 WITH FBC 2603.4.1.3.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) THE DOCUMENTS THAT WERE SUBMITTED RAISES SOME
 QUESTIONS. PROVIDE DOCUMENTATION OF THE FIRE RESISTIVE
 RATING OF THE SMOKE CURTAIN. THE PLANS INDICATE THAT
 THE 10 OCCUPANTS OF THE BLOW BAR ROOM #110 WILL EXIT
 THROUGH STAIR 5 AND THROUGH THE LOBBY TO THE EXTERIOR.
 IT APPEARS THAT THE SMOKE CURTAIN WILL BLOCK EGRESS TO
 THE LOBBY WHEN DEPLOYED. PLEASE PROVIDE CLARIFICATION.
 PROVIDE DETAILS AND CUT SHEETS FOR THE SMOKE CURTAIN AT
 STAIR #5 ON SHEET AE 103. FBC 713.4
  
 14) WILL COMPLY. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT PROPOSED ROOFING MATERIALS,
 WINDOWS, STRUCTURAL MULLIONS, EXTERIOR DOORS, BILCO
 ROOF HATCH AND MECHANICAL ROOF STANDS.
  
 15) COMPLIED.
  
 16) PLEASE LIST THE SUBMITTALS THAT WILL BE DEFERRED ON
 THE PLANS. FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-15 Cont ID  
Sent By rmcdouga Date 2019-10-15 Time 19:39 Rev Time 0.00
Received By rmcdouga Date 2019-10-09 Time 13:08 Sent To  
Notes
2019-10-15 17:51:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 PLEASE SUBMIT THE REQUIRED THRESHOLD DOCUMENTS. FBC
 110.8 THRESHOLD BUILDING / FL S. S. 553.71(7)
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) THIS PROJECT IS REQUIRED TO COMPLY WITH "ART IN
 PUBLIC PLACES".
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 3) THESE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM
 BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES ARE
 REQUIRED TO BE PAID. SEE COMMENTS IN THE IMPACT FEE
 REVIEW STOP.
  
 4) THE APPROVED SITE PLAN ON PAGE 006 AND THE OVERALL
 ARCHITECTURAL SITE PLAN ON PAGE 030 BOTH SHOW A CORNER
 OF THE CLUBHOUSE EXPANSION ENCROACHING INTO THE 10'
 WIDE FLORIDA POWER AND LIGHT UTILITY EASEMENT. SUBMIT
 TWO SETS OF AN EASEMENT RELEASE FROM FPL THAT ADDRESSES
 THIS ISSUE.
  
 5) SHOW THE LOCATION OF THE ASSUMED PROPERTY LINE
 BETWEEN THE CART BARN AND THE PROPOSED CLUBHOUSE
 ADDITION. FBC705.3
  
 6) PROVIDE CALCULATIONS TO SHOW THAT EACH OF THE
 BUILDINGS WILL COMPLY WITH FBC 708.5.1 FOR THE
 ALLOWABLE AREA OF OPENINGS IN THE EXTERIOR WALLS.
  
 7) PLEASE STATE IN THE CODE ANALYSIS THAT THIS BUILDING
 IS A FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13.
  
 8) THE WALK-IN COOLER IS REQUIRED TO BE PERMITTED
 SEPARATELY AND WILL BE REQUIRED TO COMPLY WITH FBC
 2603.4.1.3.
  
 9) THE FLOOR PLANS, SHEETS AE 403, 404, 406 AND 407 ARE
 MISSING MOST OF THE DIMENSIONS. FBC 107.2.1
  
 10) IN ADDITION TO THE ENLARGED FLOOR PLANS, CLEARLY
 SHOW THE FIRE RATED WALLS ON THE LIFE SAFETY PLANS. FBC
 107.2.1
  
 11) SHOW COMPLIANCE WITH FBC 713.13.3 FOR THE TRASH
 CHUTE ACCESS ROOM. SHEET AE 106.
  
 12) SHOW COMPLIANCE WITH FBC 713.13.4 FOR THE TRASH
 CHUTE DISCHARGE ROOM. SHEET AE 103.
  
 13) PROVIDE DETAILS AND CUT SHEETS FOR THE SMOKE
 CURTAIN AT STAIR #5 ON SHEET AE 103. FBC 713.4
  
 14) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 PROPOSED ROOFING MATERIALS, WINDOWS, STRUCTURAL
 MULLIONS, EXTERIOR DOORS, BILCO ROOF HATCH AND
 MECHANICAL ROOF STANDS.
  
 15) PROVIDE DETAILS AND CUT SHEETS FOR THE
 WATER-PROOFING SYSTEM THAT WILL BE INSTALLED ON THE
 WALLS THAT WILL EXTEND BELOW THE FINISHED GRADE. FBC
 1805.1
  
 16) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By jpearson Date 2019-11-21 Time 08:33 Rev Time 0.00
Received By jpearson Date 2019-11-21 Time 08:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-10-09 Cont ID  
Sent By jpearson Date 2019-10-09 Time 14:19 Rev Time 0.00
Received By jpearson Date 2019-10-09 Time 07:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-19 Cont ID  
Sent By pleduc Date 2019-11-19 Time   Rev Time 0.00
Received By pleduc Date 2019-11-19 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-09-26 Cont ID  
Sent By fstal Date 2019-09-26 Time   Rev Time  
Received By fstal Date 2019-09-26 Time   Sent To  
Notes
2019-09-26 10:22:04FFPC 1-14.2ED: FIRE PROTECTION CONTRACTOR SHALL SUBMIT
 SHOP DRAWINGS FOR APPROVAL. FFPC 1- 14.4 6ED: REVIEW &
 APPROVAL SHALL NOT RELIEVE THE CONTRACTOR OF THE
 REPONSIBILITY OF COMPLAINCE WITH THE CODE.
  
 NOTE: DIGITALPLAN REVIEW SIGN PG: G1101 & FP3.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By gjohnson Date 2020-01-13 Time 18:09 Rev Time 0.00
Received By gjohnson Date 2020-01-13 Time 18:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By shill Date 2019-12-10 Time 06:08 Rev Time 0.00
Received By shill Date 2019-12-10 Time 06:08 Sent To  
Notes
2019-12-10 06:08:44GAS 2ND REVIEW**DENIED**19090403
 1) TERMINATION OF WATER HEATER VENT DOES NOT SHOW
 ANCHORING OR INTAKE VENT. PLEASE CLARIFY. FBC 107.2.1
 2) DEFERRED SUBMITTAL ON GAS EQUIPMENT IS NOT PERMITTED
 AND MUST BE SUBMITTED FOR THIS PLAN REVIEW. AS I
 EXPLAINED OVER THE PHONE AFTER THE 1ST REVIEW THIS
 WOULD NEED TO BE APPROVE BY THE CHIEF PLUMBING
 INSPECTOR (TIM LARGE) WHICH TO DATE HAS NOT HAPPENED.
 SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3.GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1
 3) PROVIDE SIZING CHARTS FOR SYSTEM AFTER THE PRESSURE
 REDUCING REGULATORS. SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37)
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE INSIDE
 OF THE BUILDING SHALL BE APPROVED FOR INDOOR
 INSTALLATION. PROVIDE VENTING OF EACH REGULATOR. DOES
 NOT MATTER WHO IS SUPPLYING THEM BUT THE INSTALLATION
 MANUAL IS REQUIRED FOR THIS REVIEW. 2017 FGC SEC.410.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-10-16 Cont ID  
Sent By shill Date 2019-10-16 Time 05:55 Rev Time 0.00
Received By shill Date 2019-10-16 Time 05:55 Sent To  
Notes
2019-10-16 05:55:46GAS 1ST REVIEW**DENIED**
  
 1) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS.
 502 THRU 505
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR.
  
 4) PROVIDE SIZING TABLE FOR AFTER THE GAS REGULATOR
 .5LB SYSTEM. ) SUBMIT TWO COPIES OF THE APPLICABLE
 SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37)
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 6) ) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-30 Cont ID  
Sent By lmarchan Date 2020-01-30 Time 07:54 Rev Time 0.00
Received By lmarchan Date 2020-01-27 Time 16:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-24 Cont ID  
Sent By rmcdouga Date 2020-01-24 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2020-01-08 Time 07:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-18 Cont ID  
Sent By shill Date 2019-12-18 Time 10:47 Rev Time 0.00
Received By shill Date 2019-11-18 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-16 Cont ID  
Sent By shill Date 2019-10-16 Time 06:03 Rev Time 0.00
Received By shill Date 2019-09-18 Time 16:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-01-30 Cont ID  
Sent By lmarchan Date 2020-01-30 Time 07:52 Rev Time 0.00
Received By lmarchan Date 2020-01-27 Time 16:19 Sent To  
Notes
2020-01-30 07:53:50NO FEES DUE - ALL FEES PAID UNDER RECEIPT
 2019-0722-269. LEM
2020-01-27 16:19:391/27/20 SENT EMAIL TO IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-09 Cont ID  
Sent By rmcdouga Date 2019-10-09 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2019-10-09 Time 13:09 Sent To  
Notes
2019-10-09 14:51:46PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-11-19 Cont ID  
Sent By ccole Date 2019-11-19 Time 12:33 Rev Time 0.00
Received By ccole Date 2019-11-19 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-09 Cont ID  
Sent By ccole Date 2019-10-09 Time 16:32 Rev Time 0.00
Received By ccole Date 2019-10-09 Time 07:22 Sent To  
Notes
2019-10-09 17:25:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090403
 10/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6 & M7: PLEASE PROVIDE SYMBOLS TO SHOW THE
 LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE
 SUPPLY SYSTEMS OF AHU 1.10 & 1.11- SECTION 606.2.1 FBC
 M.
  
 2) M7: LABEL THE SUPPLY DROP FROM AHU-1.11 AND PROVIDE
 THE DUCT DIMENSIONS- SECTION 107.2.1 WPB.
  
 3) G1102, M6, & M7: A FIRE DAMPER IS REQUIRED AT THE
 PENETRATION OF THE DUCT RISER FROM AHU-1.11 THROUGH THE
 FIRE-RATED FLOOR CEILING ASSEMBLY- SECTION 607.2.1 FBC
 M.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS)
 FOR THE NEW COOKING APPLIANCES- SECTION 623.1 FBC-FG,
 AND PROVIDE COMBUSTION AIR CALCULATIONS ON THE PLAN-
 SECTION 304 FG.
  
 5) PROVIDE WINDLIOAD ENGINEERING FOR INSTALLATION OF
 THE ROOFTOP AC SYSTEM- SECTION 301.15 FBC M.
  
 6) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS, FIRE SUPPRESSION SYSTEMS, AND WALKIN COOLERS AND
 FREEZERS- SECTION 107.2.1 WPB. PLEASE NOTE THE
 FOLLOWING ITEMS PERTAINING TO THE HOOD PERMIT. A) SHEET
 M9: IT APPEARS THAT THE DISCHARGE FROM THE GREASE
 EXHAUST FANS WILL BE WITHIN THE REQUIRED 10' CLEARANCE
 TO THE PARAPET WALL- SECTION 506.3.1.3.3 UNLESS MEETING
 THE EXCEPTION TO THAT SECTION. B) THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE EXHAUST HOOD MAKEUP AIR AND
 THE AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F- SECTION 508.1.1
  
 7) COMMISSIONING OF THE MECHANICAL, SERVICE WATER
 HEATING SYSTEMS, AND AUTOMATIC LIGHTING SYSTEM CONTROLS
 IS REQUIRED PER SECTION C408.2 FBC-17 ENERGY
 CONSERVATION. SUBMIT A COMMISSIONING PLAN AS OUTLINED
 IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2-
 C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT
 FINAL INSPECTION, ALONG WITH A LETTER FROM THE BUILDING
 OWNWERSHIP ACKNOWLEDGING RECEIPT OF THE REPORT.
  
 8) DEFERRED SUBMITTALS: THE KITCHEN APPLIANCES, AND
 WINDLOAD ENGINEERING NOTED ABOVE MAY BE DEFERRED
 SUBMITTALS IF NECESSARY. PLEASE REVIEW THE REQUIRED
 SUBMITTALS LISTED BELOW THAT MAY ALSO BE DEFERRED.
  
 1) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 2) MOTORIZED O/A DAMPERS
 3) DUCT SMOKE DETECTORS
 4) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 5) AC STAND NOA?S OR FL. PRODUCT APPROVALS
 6) CO2 SENSORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By gjohnson Date 2020-01-13 Time 18:09 Rev Time 0.00
Received By gjohnson Date 2020-01-13 Time 13:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By shill Date 2019-12-10 Time 06:08 Rev Time 0.00
Received By shill Date 2019-11-22 Time 17:01 Sent To  
Notes
2019-12-10 06:08:12PLUMBING 2ND REVIEW**DENIED**19090403
 1) SHT. AE501 TOILET DETAIL SHOWS SIDE GRAB BAR OVERALL
 AS 52? AND NOT THE REQUIRED MIN OF 54?. FBC-ACC 604.5.1
 2) PROVIDE THE GREASE INTERCEPTOR SIZING CALCULATIONS
 BASE ON YOUR PDI G 101 . FBC 107.3.5
 3) PROVIDE GREASE INTERCEPTOR INSTALLATION MANUAL. FBC
 107.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
2019-12-03 09:08:40TIM HUNT IS REVIEWING REMOTELY

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-16 Cont ID  
Sent By shill Date 2019-10-16 Time 05:54 Rev Time 0.00
Received By shill Date 2019-10-08 Time 16:46 Sent To  
Notes
2019-10-16 05:55:04PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE CLEAR FLOOR SPACE FOR ALL TOILET ROOMS
 SHOWING THE INTENT TO MEET FLORIDA ACCESSIBILITY. FBC
 107.3.5
 2) SHT. AE-504 SHOWS THE MIRROR MOUNTING 40? TO THE
 BOTTOM EDGE. THE MAX 40? IS TO THE REFLECTIVE SURFACE
 OF THE MIRROR. FBC-ACC 603.3
 3) PROVIDE CABINET DETAIL SHOWING THE COPY ROOM SINKS
 E129 AND E202 WILL MEET FLORIDA ACCESSIBILITY FOR CLEAR
 FLOOR SPACE AND HEIGHT MAX 34?. FBC-ACC 606.3, 606.3
 4) SHT. P-16 IS MISSING THE REQUIRED SHUT OFF VALVE ON
 THE SUMP PUMP. FBC-PLB 712.2
 5) PROVIDE HOW YOU DETERMINE THE SIZE OF THE GREASE
 INTERCEPTOR EITHER BY PDI G 101 OR 64E-6
 6) SHT. P-16 UNDER NOTE #1 PLEASE ADD THAT THE MIXING
 VALVE SHALL BE AN ASSE 1070 APPROVED DEVICE. FBC-PLB
 607.1.2
 7) SHT.P-10 AND P-11 ARE MISSING WATER ISOMETRIC ARE
 MISSING THE REQUIRED SHUT OFF VALVES ON ALL DOWN FEEDS.
 FBC-PLB 606.1 (5)
 8) PROVIDE LOCATION OF THE HI-LOW DRINKING FOUNTAIN AS
 REQUIRED IN FBC-PLB 410.3
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By gjohnson Date 2020-01-13 Time 18:09 Rev Time 0.00
Received By gjohnson Date 2020-01-13 Time 18:09 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By shill Date 2019-12-10 Time 06:09 Rev Time 0.00
Received By shill Date 2019-12-10 Time 06:09 Sent To  
Notes
2019-12-10 06:09:26SEE PLUMBING
 REVIEWED REMOTELY BY TIM HUNT
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By shill Date 2019-10-17 Time 06:19 Rev Time 0.00
Received By shill Date 2019-10-17 Time 06:19 Sent To  
Notes
2019-10-17 06:20:00SEE PLUMBING
 REVIEWED REMOTELY BY TIM HUNT
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-01-24 Cont ID  
Sent By dbattles Date 2020-01-24 Time 14:17 Rev Time 0.00
Received By dbattles Date 2020-01-24 Time 14:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-01-22 Cont ID  
Sent By rmcdouga Date 2020-01-22 Time 18:50 Rev Time 0.00
Received By rmcdouga Date 2020-01-22 Time 18:50 Sent To  
Notes
2020-01-22 18:55:07THE PLANS AND DOCUMENTS THAT ARE SIGNED BY PHILIP J.
 RIZZO ARE SHOWING UP AS INVALID.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By shill Date 2019-12-10 Time 06:28 Rev Time 0.00
Received By shill Date 2019-12-10 Time 06:25 Sent To  
Notes
2019-11-21 08:33:49ELECTRICAL SHEETS OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-10-16 Cont ID  
Sent By shill Date 2019-10-16 Time 06:03 Rev Time 0.00
Received By shill Date 2019-10-16 Time 05:56 Sent To  
Notes
2019-10-16 06:03:22LANDSCAPE PAGES WERE REMOVED - SUBMIT LANDSCAPE PLANS
 WITH A PERMIT APPLICATION, TO BE REVIEWED UNDER
 SEPARATE PERMIT
  
 A SHEETS - OK
 SURVEY - OK
 CIVIL - OK
 STRUCTURAL - INVALID IN ADOBE; OK IN PDF EXPRESS
 M - OK
 P - OK
 FP - OK
  
2019-10-09 07:35:05ELECTRICAL SHEETS OK.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2020-01-28 Cont ID  
Sent By rmcdouga Date 2020-01-28 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2020-01-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By rfalcone Date 2019-11-25 Time 14:23 Rev Time 0.00
Received By rfalcone Date 2019-11-25 Time 14:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-04 Cont ID  
Sent By rfalcone Date 2019-10-04 Time 14:09 Rev Time 0.00
Received By rfalcone Date 2019-10-04 Time 13:32 Sent To I
Notes
2019-10-04 13:33:35**** ZONING PROVISO ******
 PRIOR TO ZONING APPROVAL AND ISSUANCE OF A CERTIFICATE
 OF OCCUPANCY, A CONDITIONAL APPROVAL FORM FOR THE
 LANDSCAPE PERMIT AND IRRIGATION PERMIT.
 A. THE SIGNATURE OF THE OWNER AND CONTRACTOR ARE
 REQUIRED ON THIS FORM. ONCE IT IS NOTARIZED, IT CAN BE
 DROPPED OFF TO ME IN THE PLANNING AND ZONING DEPARTMENT
 FOR SIGNATURES FROM THE ZONING AND BUILDING OFFICIALS.
 B. EACH PERMIT MUST HAVE ITS OWN CONDITIONAL APPROVAL.
  