Plan Review Details - Permit 19090385
Plan Review Stops For Permit 19090385
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2019-10-22 Cont ID  
Sent By shill Date 2019-10-22 Time 17:56 Rev Time 0.00
Received By shill Date 2019-10-22 Time 17:56 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2019-10-22 Time 11:43 Sent To  
Notes
2019-10-22 15:00:03ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By jwitmer Date 2019-09-24 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2019-09-24 Time 09:11 Sent To  
Notes
2019-09-24 14:37:00BUILT IN 1919. ASBESTOS COMMERCIAL: PLEASE PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON
 LETTERHEAD, STATING THAT THE INSTRUCTIONS ON THE
 WEBSITE OF ASBESTOS PROGRAM COORDINATOR, FLORIDA
 DEPARTMENT OF HEALTH PALM BEACH COUNTY WILL BE FOLLOWED
 AND THAT NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-12-17 Cont ID  
Sent By jwitmer Date 2019-12-17 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2019-12-17 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-11-26 Cont ID  
Sent By jgomez Date 2019-11-26 Time 09:54 Rev Time 0.00
Received By jgomez Date 2019-11-25 Time 18:00 Sent To  
Notes
2019-11-26 09:54:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090385
 ADD: 1913 S DIXIE HWY SUITE: 400
 CONT: PM DEVELOPMENT
 TEL: 561-889-5874
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUESDAY NOV. 26/2019
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) OK.
  
 3- OK
  
 ORIGINAL COMMENT:
 4) PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY
 ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER
 OF RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 RESPONSE:
 PRODUCT APPROVALS WERE NOT REVIEWED BY THE ARCHITECT OF
 RECORD AND INFORMATION ON PRODUCT APPROVAL IS NOT
 MARKED SHOWING THE SPECIFIC SIZE, TYPE OF GLAZING
 MULLION SIZE, ETC AS REQUESTED.
 NOTE: THIS INFORMATION MAY BE SUBMITTED LATER AS
 DEFERRED SUBMITTAL BUT BEFORE INSPECTIONS.
  
 5) OK
  
 6) OK
  
 7) COMPLIED.
  
 ORIGINAL COMMENT:
 8) NEW COMMENT. SHEET LS1.01 & A1.01 BOTH SHOW A NEW
 FRONT ENTRY DESIGN WITH A DOUBLE DOOR LOBBY/ VESTIBULE
 SYSTEM. WITH THIS TYPE OF SYSTEM YOU STILL WILL NEED TO
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 404.2.6 DOORS IN SERIES AND FIGURE 404.2.6. THE
 DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES
 AND GATES IN SERIES SHALL BE 48 INCHES MINIMUM PLUS THE
 WIDTH OF DOORS OR GATES SWINGING INTO THE SPACE.
  
 RESPONSE:
 NOT ADDRESSED. AND, THERE IS A NEW COMMENT THAT
 UNFORTUNATELY WAS OVERLOOKED REGARDING THE MANEUVERING
 CLEARANCE REQUIRED AT MANUAL DOORS. IT LOOKS LIKE THE
 CORRIDOR LEADING TO OFFICE #105 IS TOO NARROW.
 ACCORDING TO SEC. 404.2.4.1 AND FIGURE 404.2.4.1(J) FBC
 ACCESSIBILITY, THE MINIMUM CORRIDOR WIDTH NEEDS TO BE
 AT LEAST 42 INCHES. REVISE PLANS AS REQUIRED.
  
 ORIGINAL COMMENT:
 9) NEW COMMENT. SHEET LS1.01 & A1.01 BOTH SHOW A NEW
 FRONT ENTRY DESIGN WITH STRUCTURAL WING WALLS AND
 CEILING THAT WILL BE SUBJECT TO EXTERIOR WEATHER
 CONDITIONS RAIN AND WIND. PLEASE PROVIDE THE MATERIALS
 THIS EXTERIOR WALL & CEILING WILL BE CONSTRUCTED FROM.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 THE ADMINISTRATIVE CODE 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 10) THE NEWLY FORM SET OF PLANS ARE NOT COMPLETE,
 MISSING THE COVERSHEET WITH INDEX OF DRAWINGS AND THE
 D.01 DEMOLITION SHEET AND NOTES. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 THE
 ADMINISTRATIVE CODE 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 RESPONSE:
 NOT ADDRESSED. NEED TO COORDINATE SET OF PLANS. PROVIDE
 COMPLETE SET OF PLANS.
  
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2019-10-22 Time 11:43 Sent To  
Notes
2019-10-22 15:01:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090385
 ADD: 1913 S DIXIE HWY SUITE: 400
 CONT: PM DEVELOPMENT
 TEL: 561-889-5874
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 22/ 2019
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SEMI-COMPLIED, 2.1-2.5. SHEET A1.02 SHOW NEW
 STOREFRONT GLAZING UNITS WITH THE WIND DESIGN CRITERIA
 AND STOREFRONT SYSTEMS IN V-ULT PRESSURES, THE EXPOSURE
 IS C. IT WOULD APPEAR THE PRESSURES GIVEN ARE B
 EXPOSURE PRESSURES. EXPOSURE C PRESSURES FOR A MEAN
 ROOF HEIGHT OF 15 FEET HAVE A MULTIPLIER OF 1.21
 BUMPING THE PRESSURES UP ABOUT 6 PSF. PLEASE ALSO
 CONVERT THE PRESSURES TO VASD SINCE THE FIELD
 INSPECTORS WILL LOOKING AT THE PRODUCT APPROVALS WHICH
 ARE IN VASD. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3-6) PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 4) PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY
 ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER
 OF RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) PROVISO: W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING.
  
 7) COMPLIED.
  
 8) NEW COMMENT. SHEET LS1.01 & A1.01 BOTH SHOW A NEW
 FRONT ENTRY DESIGN WITH A DOUBLE DOOR LOBBY/ VESTIBULE
 SYSTEM. WITH THIS TYPE OF SYSTEM YOU STILL WILL NEED TO
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 404.2.6 DOORS IN SERIES AND FIGURE 404.2.6. THE
 DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES
 AND GATES IN SERIES SHALL BE 48 INCHES MINIMUM PLUS THE
 WIDTH OF DOORS OR GATES SWINGING INTO THE SPACE.
  
 9) NEW COMMENT. SHEET LS1.01 & A1.01 BOTH SHOW A NEW
 FRONT ENTRY DESIGN WITH STRUCTURAL WING WALLS AND
 CEILING THAT WILL BE SUBJECT TO EXTERIOR WEATHER
 CONDITIONS RAIN AND WIND. PLEASE PROVIDE THE MATERIALS
 THIS EXTERIOR WALL & CEILING WILL BE CONSTRUCTED FROM.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 THE ADMINISTRATIVE CODE 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) THE NEWLY FORM SET OF PLANS ARE NOT COMPLETE,
 MISSING THE COVERSHEET WITH INDEX OF DRAWINGS AND THE
 D.01 DEMOLITION SHEET AND NOTES. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 THE
 ADMINISTRATIVE CODE 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By jwitmer Date 2019-09-24 Time 15:10 Rev Time 0.00
Received By jwitmer Date 2019-09-24 Time 09:11 Sent To  
Notes
2019-09-24 15:10:082017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090385
 ADD: 1913 S DIXIE HWY SUITE: 400
 CONT: PM DEVELOPMENT
 TEL: 561-889-5874
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 24/ 2019
 ACTION: DENIED
  
 1) SHEET LS1.01. SHOWS A DISTANCE OF 4 FEET 5 INCHES
 (53 INCHES) BETWEEN THE WALL AT BATHROOM # 2 AND THE
 CUBICAL WALL ACROSS THE AISLE. SHEET A1.01 IDENTIFIES
 THE DOOR FOR RESTROOM # 2 AS DOOR # 2. SHEET A1.02 IN
 THE DOOR SCHEDULE IDENTIFIES DOOR # 2 AS A 36 INCH WIDE
 DOOR. IN THE 2017 FBC-B SECTION
 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178
 MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN ONE-HALF. THE REQUIRED
 EGRESS WIDTH FOR AN OCCUPANT LOAD OFLESS THAN 50 IS 36
 INCHES, (TABLE 1020.2 2017 FBC-B). ONE/ HALF OF THE
 REQUIRED EGRESS WIDTH WOULD BE 18 INCHES CLEAR AS THE
 DOOR SWINGS. 53 INCHES - 36 INCHES = 17 INCHES. PLEASE
 NOTE 53-34= 19 INCHES CLEAR. NOTE A 34 INCH DOOR WILL
 LEAVE 32 INCHES CLEAR FOR THE RESTROOM AND ALSO LEAVE A
 19 INCH CLEARENCE AS THE DOOR SWINS.
  
 2) SHEET A1.01 & A1.02 BOTH SHOW NEW STOREFRONT GLAZING
 UNITS. THE ARCHITECTURAL SHEETS DO NOT PROVIDE THE WIND
 DESIGN CRITEIA. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING IN PSF
  
 2.6 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING.
  
 7) SHEET A1.04 WATER CLOSET GRABBARS PLEASE UPDATE THE
 PLAN TO SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By jpearson Date 2019-10-23 Time 13:09 Rev Time 0.00
Received By jpearson Date 2019-10-23 Time 13:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-04 Cont ID  
Sent By jleahy Date 2019-10-04 Time 12:39 Rev Time 0.00
Received By jleahy Date 2019-10-04 Time 12:39 Sent To  
Notes
2019-10-04 12:44:42.FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SUBMIT A RISER DIAGRAM
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 FBC 107.2.1
  
 2) LOAD CALCULATION IS DONE AS RESIDENCE.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
 3) ENERGY CONSERVATION CODE NOT ADDRESSED
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
  
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-12-13 Cont ID  
Sent By pleduc Date 2019-12-13 Time   Rev Time 0.00
Received By pleduc Date 2019-12-13 Time 15:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-11-18 Cont ID  
Sent By pleduc Date 2019-11-18 Time   Rev Time 0.00
Received By pleduc Date 2019-11-18 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-16 Cont ID  
Sent By pleduc Date 2019-10-16 Time   Rev Time 0.00
Received By pleduc Date 2019-10-16 Time 12:17 Sent To  
Notes
2019-10-16 12:25:42THE REVISED PLANS WERE NOT INCORPORATED INTO COMPLETE
 SETS.
  
 FIRE DID NOT STAMP THE COVER SHEETS, A 1.00, DUE TO
 INCORRECT SHEETS WITHIN THOSE STAPLED SETS.
  
 FIRE STAMPED THE FIRST PAGE, A 1.01 & LS 1.01, OF THE
 10 SUBMITTED REVISED SHEETS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By pleduc Date 2019-09-16 Time   Rev Time 0.00
Received By pleduc Date 2019-09-16 Time 14:28 Sent To  
Notes
2019-09-16 14:33:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS1.01 - THE DOOR TO BATHROOM # 2 OPENS OUT
 INTO THE EXIT CORRIDOR. THOUGH THIS IS NOT A VIOLATION
 INTO THE OPEN OFFICE SPACE, ONCE THE CUBICLE PARTITIONS
 ARE ADDED, THE CORRIDOR IS CREATED THAT RESTICTS
 EGRESS.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2019-12-11 Cont ID  
Sent By fmittner Date 2019-12-11 Time 16:19 Rev Time 0.00
Received By fmittner Date 2019-12-11 Time 16:19 Sent To  
Notes
2019-12-11 16:19:46CLEAR GLASS

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-11-15 Cont ID  
Sent By fmittner Date 2019-11-15 Time 16:18 Rev Time 0.00
Received By fmittner Date 2019-11-15 Time 16:18 Sent To  
Notes
2019-11-15 16:18:41ALL DECORATIVE PILASTERS TO REMAIN AND STOREFRONTS TO
 HAVE CLEAR GLASS

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By fmittner Date 2019-10-23 Time 16:30 Rev Time 0.00
Received By fmittner Date 2019-10-23 Time 16:30 Sent To  
Notes
2019-10-23 16:30:33DECORATIVE PILASTERS TO REMAIN PER DISCUSSION WITH
 ARCHITECT.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By fmittner Date 2019-10-03 Time 11:43 Rev Time 0.00
Received By fmittner Date 2019-10-03 Time 11:43 Sent To  
Notes
2019-10-03 11:49:19PROPERTY IN HISTORIC DISTRICT. STOREFRONT AS INDICATED
 DOES NOT MEET DESIGN GUIDELIENS. SHALL RETAIN EXISITNG
 INSET AND DECORATIVE PILASTERS. REVISE FLOORPLAN AND
 SUBMIT ELEVATION TO ENSURE COMPLIANCE. GLASS SHALL BE
 CLEAR. QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER AT (561) 822-1457 OR
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-12-17 Time 15:15 Rev Time 0.00
Received By lmarchan Date 2019-12-03 Time 15:20 Sent To  
Notes
2019-12-04 15:20:07B23

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-26 Cont ID  
Sent By jesmith Date 2019-11-26 Time 13:36 Rev Time 0.00
Received By jesmith Date 2019-11-26 Time 13:36 Sent To  
Notes
2019-11-13 16:30:24B21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-05 Cont ID  
Sent By jesmith Date 2019-11-05 Time 13:15 Rev Time 0.00
Received By jesmith Date 2019-11-05 Time 13:15 Sent To  
Notes
2019-10-15 14:13:32B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-04 Cont ID  
Sent By jleahy Date 2019-10-04 Time 12:46 Rev Time 0.00
Received By jleahy Date 2019-09-12 Time 14:12 Sent To  
Notes
2019-09-13 14:12:42B31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-24 Cont ID  
Sent By jwitmer Date 2019-09-24 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2019-09-24 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By ccole Date 2019-10-21 Time 16:45 Rev Time 0.00
Received By ccole Date 2019-10-21 Time 16:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-27 Cont ID  
Sent By ccole Date 2019-09-27 Time 16:56 Rev Time 0.00
Received By ccole Date 2019-09-27 Time 14:49 Sent To  
Notes
2019-09-27 17:11:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090385
 9/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01: THE SUPPLY DUCTS ARE MISLABLED AS
 RETURN DUCTS (RD). PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 2) M1.01: INDICATE THE DIFFUSER AND RETURN GRILL
 DIMENSIONS.
  
 3) M1.01: PLEASE CLEARLY IDENTIFY THE MAIN DUCT. THE
 PLAN DOES NOT CLEARLY SHOW HOW ALL AIR IS BEING
 RETRUNED TO THE AIR HANDLER- SECTION- 601.6 FBC M.
  
 4) M1.01: PLEASE PROVIDE THE MAKE AND MODEL OF THE
 EXISTING AIR HANDLER, AND IT'S COOLING AND HEATING
 CAPACITIES IN BTUH AND KW- SECTION 107.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-26 Cont ID  
Sent By jesmith Date 2019-11-26 Time 13:32 Rev Time 0.00
Received By jesmith Date 2019-11-26 Time 11:50 Sent To  
Notes
2019-11-26 13:32:32PLUMBING COMMENTS: APPROVED W/PROVISO
 1. THE NOTED RHEEM ZORO #G9984116 IS NOT A RHEEM
 MANUFACTURER?S MODEL. PER WPB FBC 107.2.1 AND WPB FBC
 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL, AS AN
 ADDENDUM TO P1.01, A MANUFACTURER?S SPECIFICATION FOR
 THE APPROPRIATE WATER HEATER MATCHING THE DESCRIPTION
 OF THE NOTED WATER HEATER. THE DOCUMENTS SHALL BE
 SUBMITTED AS A SUPPORTING DOCUMENT WITH REQUIRED
 ARCHITECT?S STAMP AND SIGNATURE, APPROVED AND ON SITE
 PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
 2. PAN W/DRAIN TO SERVICE SINK IS REQUIRED TO COMPLY
 W/FBC PL 504.7,504.7.1 AND 504.7.2
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-11-05 Cont ID  
Sent By jesmith Date 2019-11-05 Time 12:48 Rev Time 0.00
Received By jesmith Date 2019-11-05 Time 07:46 Sent To  
Notes
2019-11-05 12:40:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. REGARDING THE REQUIRED WATER FOUNTAINS AS REQUIRED
 PER FBC PL TABLE 403.2 COMPLYING WITH FBC ACC, PER WPB
 FBC 107.2, PROVIDE DETAIL OF DF SHOWING COMPLIANCE WITH
 FBC ACC 306, TOE AND KNEE CLEARANCES AND 602, SPOUTS
 HEIGHT AND LOCATION (SEE BELOW)
 A. 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 B. 602.5 SPOUT LOCATION. THE SPOUT SHALL BE LOCATED 15
 INCHES MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES
 MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING
 BUMPERS.
 C. 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 2. REGARDING DETAILS A1.03/2 AND A1.03/3, THE MAXIMUM
 HEIGHT OF 2'-10" (34") SHALL BE SHOWN TO THE TOP OF THE
 SINK RIM, NOT TO THE TOP OF THE COUNTER TO COMPLY WITH
 FBC ACC 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT "OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE" 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 3.RE: SANITARY ISOMETRIC; PER FBC PL 905.3 AND 905.4,
 DRY VENTS CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAINPIPE AND RISE VERTICALLY TO A POINT NOT LESS THAN
 6" ABOVE THE FLOOD LEVEL RIM OF THE FIXTURES BEING
 VENTED
 4. RE: WATER DISTRIBUTION ISOMETRIC
 A. PER FBC PL TABLE 604.5, URINAL REQUIRES 3/4" COLD
 WATER SUPPLY
 B. PER FBC PL TABLE 604.5, SERVICE SINK AND SINK EACH
 REQUIRES 1/2" HOT AND COLD WATER SUPPLY.
 C. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS USED IN
 SIZING OF WATER DISTRIBUTION. INCLUDE A PLUMBING
 FIXTURE SCHEDULE INDICATING THE DEMAND.
 D. PROVIDE NOTE, "WATER DISTRIBUTION SHALL BE OF A
 MATERIAL THAT COMPLIES WITH FBC PL TABLE 605.4."
 E. IS THERE AN EXISTING WATER SUPPLY? SHOW WHERE WATER
 SUPPLY IS COMING FROM AND THE SIZE.SHOW EXISTING
 BACKFLOW PREVENTER OR PROVIDE A NEW ONE TO CONFORM TO
 THE REQUIREMENTS OF FBC PL 608. PER WPB FBC 107.2.1,
 SHOW LOCATION ON FLOOR PLAN AS WELL AS RISER DIAGRAM.
 5. RE: P1.01, PLUMBING NOTE 14; INSERT THE WORDS "FROM
 LAVATORIES" BETWEEN THE WORDS "DELIVERED" AND "THROUGH"
 TO SHOW COMPLIANCE WITH FBC PL 416.5.
 6. REGARDING THE REQUIRED WATER HEATER DETAIL, DETAIL
 FOR WATER HEATER PIPING TO COMPLY WITH FBC PL 607.3,
 PROVIDE THERMAL EXPANSION CONTROL AND FBC PL 504, SHOW
 ANTI SIPHON DEVICE, I.E, .COLD DIP TUBE OR VACUUM
 RELIEF VALVE. PROVIDE AIR GAP FOR RELIEF LINE AT
 TERMINATION TO SERVICE SINK OR YOU MAY DISCHARGE TO
 REQUIRED PAN WITH AN AIR GAP; DRAIN SHALL BE SIZED AND
 OF A MATERIAL THAT COMPLIES WITH FBC PL TABLE 605.4.
 SHOW REQUIRED PAN AND DRAIN AND DISCHARGE TO SINK WITH
 AIR GAP; DRAIN SHALL BE SIZED AND OF A MATERIAL THAT
 COMPLIES WITH FBC PL TABLE 605.4. .
 ADDITIONALLY, PER WPB FBC 107.2.1, PROVIDE ELECTRICAL
 CHARACTERISTICS OF WATER HEATER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19090385 1913 S DIXIE HWY
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-27 Cont ID  
Sent By gjohnson Date 2019-09-27 Time 14:06 Rev Time 0.00
Received By gjohnson Date 2019-09-25 Time 10:37 Sent To  
Notes
2019-09-27 14:09:371ST REVIEW: 19090385
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.2
 COMPLYING WITH FBC ACC
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 2. THE LAVATORY OUTSIDE THE ACCESSIBLE STALL SHALL
 COMPLY WITH FBC ACC 606.2/606.3
  
 3. PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE
 BREAK ROOM SINK. PER FBC ACC 606.2
  
 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 5. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 6. SHOW COMPLIANCE FOR THE LAVATORY'S. PER FBC ACC
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 7. ON THE SANITARY ISOMETRIC THE TOILETS AND URINAL ARE
 NOT VENTED THEY SHALL BE VENTED BEFORE CONNECTING TO
 THE BUILDING DRAIN WITH A SEPARATE VENT OR WET VENT
 SYSTEM COMPLYING WITH FBC PL 912.1
  
 8. SHT. P1.01 NOTE 11 ALL FIXTURES SHALL COMPLY WITH
 FLORIDA BUILDING CODE ACCESSIBILITY 2017 6TH EDITION.
  
 9. PLEASE PROVIDE WATER ISOMETRIC DRAWING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 11. A BACK FLOW IS REQUIRED ON SUPPLY TO ANY ICE MAKER
 OR COFFEE MACHINE. PER FBC PL 608.3 608.16.10
  
 12. PROVIDE DETAIL FOR WATER HEATER PIPING TO COMPLY
 WITH FBC ACC 607.3, 504,
  
 13. PROVIDE DETAIL FOR WATER HEATER PLATFORM SHOW WHAT
 TYPE OF ANCHORS WILL BE USED IT SHALL HOLD 300LB +. PER
 WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2019-11-15 Cont ID  
Sent By fmittner Date 2019-11-15 Time 16:18 Rev Time 0.00
Received By fmittner Date 2019-11-15 Time 16:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By fmittner Date 2019-10-23 Time 16:30 Rev Time 0.00
Received By fmittner Date 2019-10-23 Time 16:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-02 Cont ID  
Sent By rfalcone Date 2019-10-02 Time 11:13 Rev Time 0.00
Received By rfalcone Date 2019-10-02 Time 11:12 Sent To HIST
Notes
***NONE***