Plan Review Details - Permit 19090168
Plan Review Stops For Permit 19090168
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-09-17 Cont ID  
Sent By rmcdouga Date 2019-09-17 Time 17:27 Rev Time 0.00
Received By rmcdouga Date 2019-09-17 Time 17:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-09-18 Cont ID  
Sent By jleahy Date 2019-09-18 Time 09:33 Rev Time 0.00
Received By jleahy Date 2019-09-18 Time 09:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-09-25 Cont ID  
Sent By lcrespo Date 2019-09-25 Time 15:00 Rev Time 0.00
Received By lcrespo Date 2019-09-25 Time 15:00 Sent To  
Notes
2019-09-25 15:02:0009/25/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-09-23 Cont ID  
Sent By lcrespo Date 2019-09-23 Time 06:48 Rev Time 0.00
Received By lcrespo Date 2019-09-23 Time 06:48 Sent To  
Notes
2019-09-23 06:55:4409/23/2019 2ND GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE TIE-DOWN SPECS ONLY ONE OF SIGNATURE OR SEAL
 WAS SUBMITTED IT REQUIRED ONE PER SET OF DOCUMENTS IN
 ACCORDANCE WITH WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND FLORIDA
 ADMINISTRATIVE CODE PER 61G15-23.001, FLORIDA STATUTE
 471. PLEASE PROVIDE THE DOCUMENT FOR YOUR TIE DOWN
 WITHOUT A SEAL AND SIGNATURE, NO COPIES
 2. WHEN RESUBMITTING PLANS PLEASE REMOVE ANY VOIDED
 SHEETS & REPLACE ANY PAGES AS NECESSARY. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By lcrespo Date 2019-09-17 Time 16:08 Rev Time 0.00
Received By lcrespo Date 2019-09-17 Time 16:08 Sent To  
Notes
2019-09-17 16:09:1509/17/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW ALL UNIONS IN FRONT OF SECOND STAGE
 REGULATOR 1? OF EITHER SIDE PER THE 2017 FBC FG SEC
 410.2.
 2. SHOW THE DEPTH OF THE LP GAS CONTAINER IF BELOW
 GRADE. COMPLY WITH NFPA 58 SEC. 6.6.6.1.
 3. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN INCLUDING CITY. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. IN THE UNDERGROUND UNIT CLEARLY INDICATE ON TIE-DOWN
 SHEET WHICH IS THE LP TANK TIE-DOWN METHOD AND IF YOU
 ARE USING STRAPS OR CABLE, IF CABLE HOW IS IT PROTECTED
 FOR THE LP TANK AND APPURTENANCES PER NFPA 58. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 5. ON THE TIE-DOWN SPECS A COPY OF SIGNATURE OR SEAL IS
 NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE PER
 61G15-23.001, FLORIDA STATUTE 471. PLEASE PROVIDE THE
 DOCUMENT FOR YOUR TIE DOWN WITHOUT A SEAL AND
 SIGNATURE, NO COPIES.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-25 Cont ID  
Sent By lcrespo Date 2019-09-25 Time 15:00 Rev Time 0.00
Received By lcrespo Date 2019-09-24 Time 13:26 Sent To  
Notes
2019-09-25 13:26:18RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-23 Cont ID  
Sent By lcrespo Date 2019-09-23 Time 06:48 Rev Time 0.00
Received By lcrespo Date 2019-09-23 Time 06:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-18 Cont ID  
Sent By jleahy Date 2019-09-18 Time 09:33 Rev Time 0.00
Received By jleahy Date 2019-09-06 Time 09:29 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-09-09 Cont ID  
Sent By jleahy Date 2019-09-18 Time 09:33 Rev Time 0.00
Received By rfalcone Date 2019-09-09 Time 16:35 Sent To P
Notes
***NONE***