2019-09-11 16:37:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A 219 - THERE ARE SYMBOLS; CIRCLES, SQUARES |
| AND OCTAGONS, WITH NUMBERS IN THEM BUT NO LEGEND |
| IDENTIFYING WHAT THEY REPRESENT. |
| |
| PLEASE REVIEW AND CLARIFY OF PROVIDE THE APPLICABLE |
| LEGEND. |
| |
| |
| |
| 2) SHEET A 219 - ELEVATOR EXIT LOBBY DOOR EXIT 1971, IS |
| NOT INDICATED WITH HARDWARE IN COMPLIANCE WITH NFPA |
| 101, CH 7 MEANS OF EGRESS. |
| |
| 7.4.1.6 ELEVATOR LANDING AND LOBBY EXIT ACCESS. |
| 7.4.1.6.1 EACH ELEVATOR LANDING AND LOBBY SHALL HAVE |
| ACCESS TO AT |
| LEAST ONE EXIT. |
| 7.4.1.6.2 THE ELEVATOR LANDING AND LOBBY EXIT ACCESS |
| REQUIRED BY |
| 7.4.1.6.1 SHALL NOT REQUIRE THE USE OF A KEY, A TOOL, |
| SPECIAL |
| KNOWLEDGE, OR SPECIAL EFFORT, UNLESS PERMITTED BY |
| 7.4.1.6.3. |
| 7.4.1.6.3 DOORS SEPARATING THE ELEVATOR LOBBY FROM THE |
| EXIT ACCESS |
| REQUIRED BY 7.4.1.6.1 SHALL BE PERMITTED TO BE |
| ELECTRONICALLY LOCKED |
| IN ACCORDANCE WITH 7.2.1.6.3. |
| |
| |
| 3) THERE DOES NOT APPEAR TO BE A DOOR SCHEDULE |
| INDICATING EACH DOOR LOCATION, TYPE, HARDWARE GROUP, |
| LOCKS & LATCHES , ETC. |
| |
| SHEET A 219 HAS A DOOR TYPE SCHEDULE AND HARDWARE |
| GROUPS BUT NO CORRESPONDING DOOR LOCATIONS. |
| |
| PLEASE REIVEW AND PROVIDE. |
| |
| |
| 4) SHEET A 219 - THERE IS AN INDICATION OF DOOR |
| SECURITY EQUIPMENT. |
| |
| ALL ACCESS CONTROL SHALL BE UNDER SEPARATE PERMIT, SHOP |
| DRAWINGS, EQUIPMENT SPECS AND COMPLY WITH NFPA 101, CH |
| 7 , MEANS OF EGRESS, WERE APPLICABLE. |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT AND |
| COMPLIANCE. |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |