Plan Review Details - Permit 19090050
Plan Review Stops For Permit 19090050
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-09-06 Cont ID  
Sent By rmcdouga Date 2019-09-06 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2019-09-06 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By jpearson Date 2019-09-06 Time 12:02 Rev Time 0.00
Received By jpearson Date 2019-09-06 Time 12:02 Sent To  
Notes
2019-09-06 12:02:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PERMIT APPLICATION FOR
 INSTALLATION OF ELECTRICAL ITEMS. WPB FBC 105.1
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW. PER THE WPB
 AMENDMENTS TO THE FBC, PLAN (EACH SHEET OF BOTH COPIES)
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. THIS PERSON
 MUST BE A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. WPB FBC 107.1, 107.2;
 FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-09-12 Cont ID  
Sent By pleduc Date 2019-09-12 Time   Rev Time 0.00
Received By pleduc Date 2019-09-12 Time 16:28 Sent To  
Notes
2019-09-12 16:32:34THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE GENERATOR SHALL BE PROTECTED FOR ACCIDENTAL
 CONTACT.
  
  
 2) THE GENERATOR EXHAUST SHALL BE POSITIONED AS TO NOT
 CAUSE EXPOSURE TO ATTENDEE'S (WATCH WIND DIRECTION,
 PLACE AWAY FROM BUILDING/TENTS)
  
  
 3) PROTECT ALL ELECTRICAL/EXTENSION CORDS FROM BEING A
 TRIP HAZARD, PROVIDE EXTENSION CORD BRIDGES WHERE
 ATTENDEE'S NEED TO WALK OVER THEM.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-13 Cont ID  
Sent By shill Date 2019-09-13 Time 05:30 Rev Time 0.00
Received By shill Date 2019-09-13 Time 05:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2019-09-06 Cont ID  
Sent By rmcdouga Date 2019-09-06 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2019-09-06 Time 10:59 Sent To  
Notes
***NONE***