Plan Review Details - Permit 19090007
Plan Review Stops For Permit 19090007
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-09-17 Cont ID  
Sent By rmcdouga Date 2019-09-17 Time 07:25 Rev Time 0.00
Received By rmcdouga Date 2019-09-17 Time 06:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-09-12 Cont ID  
Sent By jleahy Date 2019-09-12 Time 14:33 Rev Time 0.00
Received By jleahy Date 2019-09-12 Time 14:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-25 Cont ID  
Sent By lcrespo Date 2019-09-25 Time 16:49 Rev Time 0.00
Received By lcrespo Date 2019-09-24 Time 13:24 Sent To  
Notes
2019-09-25 13:24:44RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-19 Cont ID  
Sent By lcrespo Date 2019-09-19 Time 18:22 Rev Time 0.00
Received By lcrespo Date 2019-09-05 Time 10:58 Sent To  
Notes
2019-09-06 10:58:23ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-25 Cont ID  
Sent By lcrespo Date 2019-09-25 Time 16:49 Rev Time 0.00
Received By lcrespo Date 2019-09-25 Time 16:48 Sent To  
Notes
2019-09-25 16:49:4309/25/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-19 Cont ID  
Sent By lcrespo Date 2019-09-19 Time 17:01 Rev Time 0.00
Received By lcrespo Date 2019-09-19 Time 17:01 Sent To  
Notes
2019-09-19 17:20:0309/19/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE
 USED IF NO POOL FILL IS INSTALLED AT THE METER AND
 INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO
 PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240
 FOR FURTHER DIRECTIONS.
  
 2. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW (SHOW YOUR WORK PLEASE). IDENTIFY
 ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE
 PUMP BEING INSTALLED ON THIS POOL. IT REQUIRES THAT THE
 MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED
 MAXIMUM FLOW RATE OF THE SUCTION OUTLET FITTING
 ASSEMBLY (DRAIN COVER). THE TDH CALCULATIONS MUST
 INCLUDE ALL THE SYSTEM COMPONENTS INCLUDING SUCTION AND
 RETURN PIPING, FITTINGS, VALVES, HEATER, FILTER, AND
 CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT THE PUMP PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 3. INDICATE ON THE PUMP CURVE WHICH PUMP BEING
 INSTALLED ON THIS SYSTEM. SUBMIT A POOL PUMP CURVE THAT
 IS ENLARGED, CLEAR IN DETAIL AND LEGIBLE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-09-10 Cont ID  
Sent By rfalcone Date 2019-09-10 Time 09:32 Rev Time 0.00
Received By rfalcone Date 2019-09-10 Time 09:32 Sent To  
Notes
***NONE***