Plan Review Details - Permit 19081423
Plan Review Stops For Permit 19081423
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-27 Cont ID  
Sent By cthroop Date 2019-11-27 Time 09:17 Rev Time 0.00
Received By cthroop Date 2019-11-26 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-19 Cont ID  
Sent By cthroop Date 2019-09-19 Time 10:34 Rev Time 0.00
Received By cthroop Date 2019-09-19 Time 09:10 Sent To  
Notes
2019-09-19 10:40:26BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. KEYNOTE (1) ON PLAN PAGE A.OB AND FLOOR PLAN NOTE 15
 ON PLAN PAGE A.1B STATES LANDINGS SHALL BE 18 INCHES.
 LANDINGS SHALL BE A MINIMUM OF 36 INCHES IN THE
 DIRECTION OF TRAVEL PER R311.7.6.
 R311.7.6 LANDINGS FOR STAIRWAYS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY. THE MINIMUM WIDTH PERPENDICULAR TO
 THE DIRECTION OF TRAVEL SHALL BE NO LESS THAN THE WIDTH
 OF THE FLIGHT SERVED. LANDINGS OF SHAPES OTHER THAN
 SQUARE OR RECTANGULAR SHALL BE PERMITTED PROVIDED THE
 DEPTH AT THE WALK LINE AND THE TOTAL AREA IS NOT LESS
 THAN THAT OF A QUARTER CIRCLE WITH A RADIUS EQUAL TO
 THE REQUIRED LANDING WIDTH. WHERE THE STAIRWAY HAS A
 STRAIGHT RUN, THE MINIMUM DEPTH IN THE DIRECTION OF
 TRAVEL SHALL BE NOT LESS THAN 36 INCHES (914 MM).
  
 2. PROVIDE WINDOW SCHEDULE. INCLUDE ROUGH OPENINGS AND
 SPECIFIC PRODUCT APPROVALS FOR EACH OPENING.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE PRODUCT APPROVALS FOR ALL NEW WINDOWS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-27 Cont ID  
Sent By cthroop Date 2019-11-27 Time 09:17 Rev Time 0.00
Received By cthroop Date 2019-11-26 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jpearson Date 2019-09-16 Time 11:23 Rev Time 0.00
Received By jpearson Date 2019-09-16 Time 08:04 Sent To  
Notes
2019-09-16 11:23:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30; WPB FBC 107.2.1
 2. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE CORRECTION. NEC 225.31,
 225.32
 4. STUDIO ELECTRICAL PLAN SHOWS THE GFI RECEPTACLE FOR
 THE BATHROOM ON THE WALL ACROSS FROM THE BASIN, AND ON
 THE SAME CIRCUIT AS LIVING AREA. A GFCI PROTECTED
 RECEPTACLE OUTLET ON A 20 AMP CIRCUIT IS REQUIRED
 WITHIN 3 FEET OF EACH BASIN. THERE CAN BE NO OTHER
 OUTLETS. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A
 WALL OR PARTITION THAT IS ADJACENT TO THE BASIN OR
 BASIN COUNTERTOP, LOCATED ON THE COUNTERTOP, OR
 INSTALLED ON THE SIDE OR FACE OF THE BASIN CABINET.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3901.6
 5. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 6. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 8. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.6
 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 10. FOR THE ISLAND, THE SINK INSTALLED CREATES TWO
 SEPARATE SPACE, AND A GFCI RECEPTACLE OUTLET IS
 REQUIRED FOR EACH. PROVIDE CORRECTION. FBC RE
 E3901.4.4; NEC 210.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By gjohnson Date 2019-11-21 Time 14:05 Rev Time 0.00
Received By gjohnson Date 2019-11-21 Time 14:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-09-11 Cont ID  
Sent By lcrespo Date 2019-09-11 Time 16:44 Rev Time 0.00
Received By lcrespo Date 2019-09-11 Time 16:44 Sent To  
Notes
2019-09-11 17:45:3709/11/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
 6. PLEASE SHOW SHUTOFF VALVES, UNIONS, DRIP LEGS, BTU'S
 AND REGULATORS ON ISOMETRIC PER THE 2017 FBC RES. SEC.
 G2420.4.
 7. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
 9. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3.
 10. SUBMIT TWO COPIES OF THE FOR INSTALLATION
 CLEARANCES FROM THE TANKLESS INSTALLATION MANUAL. THE
 MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12
 INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE
 LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN
 AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM
 EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 11. IF THIS TANKLESS UNIT CALL FOR 10.5? WATER COLUMN
 AND THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
 12. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC RES. SEC. G2413.2 AND G2404.3.
 13. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS DRYER, STOVE AND TANKLESS. THE GAS DRYER SHALL
 BE LISTED AND LABELED PER THE 2017 FBC FG RES. SEC.
 G2404.3. THE MANUFACTURER'S SPECIFICATIONS SHALL NOTE
 THE CFM'S THAT ARE BEING EXHAUSTED BY THE DRYER.
 14. TOTAL BTU?S OF ALL APPLIANCES NOT ON PLAN IN P.1B
 FOR THE GAS TOTAL LOAD PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 15. SHOW THE SIZE OF THE LOUVER(S) ON THE DRYER ON
 PLANS AND LOCATION PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By fmittner Date 2019-11-25 Time 16:31 Rev Time 0.00
Received By fmittner Date 2019-11-25 Time 16:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-09-09 Cont ID  
Sent By fmittner Date 2019-09-09 Time 12:19 Rev Time 0.00
Received By fmittner Date 2019-09-09 Time 12:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-27 Cont ID  
Sent By cthroop Date 2019-11-27 Time 09:17 Rev Time 0.00
Received By cthroop Date 2019-11-13 Time 16:18 Sent To  
Notes
2019-11-14 16:18:51R03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-19 Cont ID  
Sent By cthroop Date 2019-09-19 Time 10:40 Rev Time 0.00
Received By cthroop Date 2019-08-28 Time 13:43 Sent To  
Notes
2019-08-29 13:43:59R02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-11-27 Cont ID  
Sent By cthroop Date 2019-11-27 Time 09:17 Rev Time 0.00
Received By cthroop Date 2019-11-26 Time 08:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-19 Cont ID  
Sent By cthroop Date 2019-09-19 Time 10:30 Rev Time 0.00
Received By cthroop Date 2019-09-19 Time 09:10 Sent To  
Notes
2019-09-19 10:34:16MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECH. PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE ENERGY SUBMITTAL. INCLUDE MANUAL J AND
 EQUIPMENT SIZING CALCULATIONS.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By gjohnson Date 2019-11-21 Time 14:06 Rev Time 0.00
Received By gjohnson Date 2019-11-21 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-09-11 Cont ID  
Sent By lcrespo Date 2019-09-11 Time 16:44 Rev Time 0.00
Received By lcrespo Date 2019-09-11 Time 07:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By fmittner Date 2019-11-25 Time 16:31 Rev Time 0.00
Received By fmittner Date 2019-11-25 Time 16:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-09-09 Cont ID  
Sent By fmittner Date 2019-09-09 Time 12:19 Rev Time 0.00
Received By fmittner Date 2019-09-09 Time 12:19 Sent To  
Notes
***NONE***