Plan Review Details - Permit 19081399
Plan Review Stops For Permit 19081399
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-10-17 Cont ID  
Sent By shill Date 2019-10-17 Time 16:07 Rev Time 0.00
Received By shill Date 2019-10-17 Time 16:07 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-23 Cont ID  
Sent By jwitmer Date 2019-09-23 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2019-09-23 Time 06:02 Sent To  
Notes
2019-09-23 06:59:43ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By dbattles Date 2019-10-25 Time 13:58 Rev Time 0.00
Received By dbattles Date 2019-10-25 Time 13:58 Sent To  
Notes
2019-10-25 14:13:37SEE COVER SHEET FOR PROVISOS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-23 Cont ID  
Sent By jwitmer Date 2019-09-23 Time 09:45 Rev Time 0.00
Received By jwitmer Date 2019-09-23 Time 06:02 Sent To  
Notes
2019-09-23 09:45:182017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081399
 ADD: 1105 N. DIXIE HWY.
 CONT: FINE LINE CONSTRUCTION
 TEL: 6500 GEORGIA AVE.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 23/ 2019
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET LIST TWICE DEAD END CORRIDOR
 LENGTH IS 25 FEET. ONCE UNDER THE HEADING OF LIFE
 SAFETY REQUIREMENTS, THE 2ND TIME UNDER LIFE SAFETY
 DATA. IN NEITHER CASE DOES THE PLAN STATE WHERE THIS
 MEASUREMENT IS REFERENCED IN THE CODE?
  
 UNDER THE 2017 FBC-B FOR AN UNSPRINKLERED BUILDING,
 BUSINESS OCCUPANCY SECTION 1020.4 STATES DEAD END
 CORRIDORS SHALL BE NO LONGER THAN 20 FEET. UNDER THE
 2017 EXIST. BUILDING CODE LEVEL II ALTERATION SECTION
 805.6 THE CODE ALLOWS DEAD END CORRIDORS ARE ALLOWED TO
 BE 35 FEET WITH THE EXCEPTION TO SPRINKLERED BUILDINGS
 50 FEET THE SAME AS THE FBC-B FOR SPRINKLERED
 BUILDINGS. PLEASE UPDATE THE PLANS.
  
 2) PLEASE NOTE SHEET A-2 INDICATES CREATING NEW
 OPENINGS FOR WINDOWS AND DOORS AS WELL AS ON THE NORTH
 SIDE OF THE BUILDING STORAGE ROOM 125 THAT CROSSES THE
 PROPERTY LINE. THE EXISTING BUILDING SITS ON 1105 NORTH
 DIXIE BUT THE SAME OWNERS (JCK ENTERPRISES INC.) OWN
 THE 2 ADJACENT LOTS 1101 AND 1109. THE NEW PROPOSED
 OPENINGS ON THE SOUTH SIDE OF THE BUILDING WOULD
 VIOLATE THE AMOUNT OF ALLOWABLE OPENINGS IN TABLE 705.8
 OF THE FBC-B AND ON THE NORTH SIDE THE EXISTING
 BUILDING THE STORAGE ROOM 125 TRANSGRESSES THE PROPERTY
 LINE. PLEASE GET A UNITY OF TITLE TO MAKE THESE
 MODIFICATIONS CODE COMPLIANT.
  
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) THIS BUILDING WAS BUILT IN 1930. ASBESTOS
 COMMERCIAL: PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT
 FROM THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 4) SHEET A-2 INDICATES THE WIND SPEED OF 170 VULT,
 EXPOSURE C WITH WORST CASE WITH PRESSURES OF 41.9+/
 56.1- PSF. WHAT THE PLAN DOES NOT STATE IF THE
 PRESSURES ARE IN VULT SINCE THE WIND SPEED IS IN VULT
 OR IF THE PRESSURES ARE STATED IN VASD? WE WOULD ASSUME
 VASD, THEY WOULD BE CORRECT FOR A MEAN ROOF HEIGHT OF
 15 FEET, ALSO AN UNKNOWN.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 ADMINISTRATIVE CODE SECTION 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) THE SUBMITTED FLORIDA APPROVAL FL# 25676 IS MISSING
 THE FRONT COVER SHEET. PLEASE NOTE THIS APPROVAL IS FOR
 CURTAIN WALL SYSTEM HEADER AND FLOOR ANCHORS ONLY. NONE
 OF THE CHARTS HAVE BEEN IDENTIFIED. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET A-2 INDICATES NEW DOUBLE DOORS, LARGE MISSILE
 IMPACT DOOR AND A NEW REAR DOOR OPENING WITH METAL DOOR
 NORTH WALL. SOUTH WALL INDICATES NEW DOOR OPENING,
 LARGE MISSILE IMPACT AND METAL DOOR. THIS REVIEW NO
 PRODUCT APPROVALS FOR DOORS WERE SUBMITTED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
  
 7) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) THE LIFE SAFETY PLAN, SHEET A-2 FLOOR PLAN NOR THE
 SHEET A-4 THE REFLECTIVE CEILING PLAN SHOW EXIT LIGHTS.
 THE ELECTRICAL SHEET E1 THE LIGHTING FLOOR PLAN DOES
 INDICATE 3 EXIT LIGHTS. NONE OF THE ARCHITECTURAL
 SHEETS SHOW COMPLIANCE WITH REQUIRED SIGNAGE FOR
 NON-ACCESSIBLE ENTRANCES/ EXITS. STEP/ LANDING JUST
 WITHIN THE DOORWAY.
 2017 FBC-ACCESSIBILITY CODE SECTION 216.6 ENTRANCES.
 WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES
 COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT
 INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING
 WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT
 COMPLY WITH 404.
  
 10) SHEET ID-5 DETAIL: 18 SHOWS A BUILT IN SHELF WITH
 THE UPPER BREAK ROOM CABINETS. THE BOTTOM OF THE SHELF
 IS AT A HEIGHT OF 56 INCHES FROM FINISH FLOOR. THE
 ELECTRICAL SHEETS ( E2 & E3) INDICATE A RECESSED OUTLET
 ABOVE THE SHELF FOR A SMALL APPLIANCE OUTLET. THE
 PROPOSED LOCATION FOR THE SMALL APPLIANCE OUTLET DOES
 NOT COMPLY WITH THE ACCESSIBILITY CODE FOR:
 308 REACH RANGES
 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 AND POSSIBLY FOR :
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 11) SHEET ID-2 SHOWS THE RECEPTION DESK BUT THE PLAN
 DOES NOT SHOW WHERE THE CLEAR FLOOR SPACE (30 X 48
 INCHES) FOR AN ACCESSIBLE COUNTER. ACCESS. CODE 904.4
 EXCEPTION 904.4.1 OR 904.4.2.
  
 12) SHEET ID-3 & 4:
 12A) PLEASE NOTE ON THIS SHEET ALL OF THE WATER CLOSET
 GRAB BARS THE MEASUREMENTS ARE TAKEN CENTER LINE OF THE
 BAR TO THE FLOOR.
 GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 12B) DETAILS 6 & 8 THE TOILET PAPER DISPENSER DOES NOT
 SHOW COMPLIANCE WITH 2017 FBC-ACCESS. CODE 604.7
 DISPENSERS AS DIMENSIONED. TOILET PAPER DISPENSERS.
 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
 12C)(1) ALL OF THE RESTROOM ELEVATION DETAILS SHOW TILE
 WALLS TO A HEIGHT OF 40 INCHES/ 3 FEET 4 INCHES. PLEASE
 SHOW COMPLIANCE WITH THE 2017 FBC-B:
 1210.2.2 WALLS AND PARTITIONS. WALLS AND PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 12C)(2) THIS REVIEW, I DIDN?T SEE NOTATION FOR THE TILE
 SUB-BASE IN THE RESTROOMS AND OR BATHROOMS AND
 COMPLIANCE WITH THE 2017 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURER?S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
  
 12D) SHEET ID-4 PRIVATE WATER CLOSET & SHOWER DOES NOT
 REQUIRE GRAB BARS IT DOES REQUIRE THE PLACEMENT OF
 BACKING FOR THE INSTALLATION OF FUTURE GRAB BARS.
 PLEASE REVIEW THE 2017 FBC-ACCESS. CODE SECTION 604.5
 EXCEPTION # 1 & 608.3 EXCEPTION # 1.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-06 Cont ID  
Sent By jpearson Date 2019-11-06 Time 10:24 Rev Time 0.00
Received By jpearson Date 2019-11-06 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 10:50 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 07:55 Sent To  
Notes
2019-09-24 10:50:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. PROVIDE NOTE TO INDICATE THE REQUIRED MARKING OF
 HIGH LEG IN SERVICE AND PANELS. NEC 110.15
 4. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By pleduc Date 2019-10-21 Time   Rev Time 0.00
Received By pleduc Date 2019-10-21 Time 12:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-30 Cont ID  
Sent By pleduc Date 2019-08-30 Time   Rev Time 0.00
Received By pleduc Date 2019-08-30 Time 14:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-11-06 Cont ID  
Sent By gjohnson Date 2019-11-06 Time 09:12 Rev Time 0.00
Received By gjohnson Date 2019-11-06 Time 09:12 Sent To  
Notes
2019-11-06 09:14:18REFERENCE TO GAS REMOVED FROM PLAN BY JIM PAINE
 ARCHITECT
  
  
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-11-04 Cont ID  
Sent By gjohnson Date 2019-11-04 Time 15:23 Rev Time 0.00
Received By gjohnson Date 2019-11-04 Time 15:23 Sent To  
Notes
2019-11-04 15:26:272ND REVIEW: 19081399
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 11. A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND
 CAPPING OF THE GAS APPLIANCES AND PIPING.PLEASE PLACE
 NOTE ON PLAN. PER AMEND TO FBC 107.2.1 AND 105.1
  
 12. PROVIDE FLOOR PLAN SHOWING LOCATION OF GAS PIPING
 TO BE CAPPED . PER WPB AMEND TO FBC
 107.3.5.1.5(1)(2)(9)
  
 THE RESPONSE LETTER CLAIMS THERE IS NO GAS WORK THAT
 THE GAS PIPING AND APPLIANCES WAS ALREADY ABANDONED AND
 CAPPED OFF BUT THE SHEET P-2 SHOWS A EXISTING WATER
 HEATER TO BE REMOVED AND NOTE #4 STATES GAS TO BE
 CAPPED. THERE IS NO RECORD OF GAS PERMIT FOR DEMOLITION
 OF GAS PIPING. REMOVE NOTE FROM PLAN REFERENCING GAS
 PIPING AND APPLIANCES
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-09-23 Cont ID  
Sent By gjohnson Date 2019-09-23 Time 11:00 Rev Time 0.00
Received By gjohnson Date 2019-09-23 Time 11:00 Sent To  
Notes
2019-09-23 11:01:551ST REVIEW: 19081399
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
 1. A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND
 CAPPING OF THE GAS APPLIANCES AND PIPING.PLEASE PLACE
 NOTE ON PLAN. PER AMEND TO FBC 107.2.1 AND 105.1
  
 2. PROVIDE FLOOR PLAN SHOWING LOCATION OF GAS PIPING TO
 BE CAPPED . PER WPB AMEND TO FBC 107.3.5.1.5(1)(2)(9)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-06 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-17 Time 13:16 Sent To  
Notes
2019-10-18 13:17:00B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-02 Cont ID  
Sent By cpuell Date 2019-10-02 Time 16:59 Rev Time 0.00
Received By cpuell Date 2019-08-28 Time 13:29 Sent To  
Notes
2019-10-02 15:35:16ROUTED FROM ZONING TO PERMIT LIBRARIAN 10/2/19 EL
2019-08-29 13:29:24B26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-23 Cont ID  
Sent By jwitmer Date 2019-09-23 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2019-09-23 Time 06:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By ccole Date 2019-10-24 Time 14:21 Rev Time 0.00
Received By ccole Date 2019-10-24 Time 12:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-20 Cont ID  
Sent By ccole Date 2019-09-20 Time 15:46 Rev Time 0.00
Received By ccole Date 2019-09-20 Time 15:11 Sent To  
Notes
2019-09-20 16:04:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081399
 9/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $78,500 VALUE FOR THE PROPOSED PROJECT APPEARS
 UNDERVALUED FOR THE SCOPE OF WORK SHOWN ON THE PLANS.
 PLEASE PROVIDE BONAFIDE CONTRACTS AND/OR ESTIMATES THAT
 INCLUDE THE LABOR, MATERIALS, EQUIPMENT, INTERIOR
 FINISHES, DESIGN FEES, AND OVERHEAD AND PROFIT- SECTION
 109.3 WPB.
  
 2) REFER TO SECTION 809.2 FBC-EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 4) M-1: EXHAUST VENTILATION FOR THE KITCHEN IS REQUIRED
 PER TABLE 403.3.1.1 FBC M. PLEASE SHOW A SYSTEM ON THE
 PLANS AND INDICATE THE SEQUENCE OF OPERATION. SUBMIT
 MANUFACTURER'S SPECS.
  
 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING LOCATIONS OF
 THE RTU'S AND CLEARANCES FROM AIR INTAKES TO EXHAUST
 OUITLETS- SECTION 401.4 FBC M.
  
 6) PROVIDE WIND LOAD ENGINEERING FOR THE RTU'S- SECTION
 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-06 Cont ID  
Sent By gjohnson Date 2019-11-06 Time 09:10 Rev Time 0.00
Received By gjohnson Date 2019-11-06 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-11-04 Cont ID  
Sent By gjohnson Date 2019-11-04 Time 15:01 Rev Time 0.00
Received By gjohnson Date 2019-11-04 Time 15:01 Sent To  
Notes
2019-11-04 15:23:312ND REVIEW: 19081399
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 11. A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND
 CAPPING OF THE GAS APPLIANCES AND PIPING.PLEASE PLACE
 NOTE ON PLAN. PER AMEND TO FBC 107.2.1 AND 105.1
  
 12. PROVIDE FLOOR PLAN SHOWING LOCATION OF GAS PIPING
 TO BE CAPPED . PER WPB AMEND TO FBC
 107.3.5.1.5(1)(2)(9)
  
 THE RESPONSE LETTER CLAIMS THERE IS NO GAS WORK THAT
 THE GAS PIPING AND APPLIANCES WAS ALREADY ABANDONED AND
 CAPPED OFF BUT THE SHEET P-2 SHOWS A EXISTING WATER
 HEATER TO BE REMOVED AND NOTE #4 STATES GAS TO BE
 CAPPED. THERE IS NO RECORD OF GAS PERMIT FOR DEMOLITION
 OF GAS PIPING. REMOVE NOTE FROM PLAN REFERENCING GAS
 PIPING AND APPLIANCES
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-23 Cont ID  
Sent By gjohnson Date 2019-09-23 Time 10:58 Rev Time 0.00
Received By gjohnson Date 2019-09-21 Time 09:40 Sent To  
Notes
2019-09-23 10:59:481ST REVIEW: 19081399
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SHOWER IN THE PRIVATE OFFICE BATHROOM APPEARS TO
 BE A ALTERNATE ROLL IN TYPE SHOWER IF SO THE INSIDE
 DIMENSION OF THE WIDTH SHALL BE 36" EXACT. PER FBC ACC
 608.2.3
  
 2. THE SHOWER VALVE CONTROLS SHALL COMPLY WITH. FBC ACC
 608.5.3 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS. IN
 ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT
 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR
 SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15
 INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE
 SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY.
  
 3. SHOW COMPLIANCE WITH FBC ACC 608.6 SHOWER SPRAY UNIT
 AND WATER. A SHOWER SPRAY UNIT WITH A HOSE 59 INCHES
 LONG MINIMUM THAT CAN BE USED BOTH AS A FIXED-POSITION
 SHOWER HEAD AND AS A HAND-HELD SHOWER SHALL BE
 PROVIDED. THE SHOWER SPRAY UNIT SHALL HAVE AN ON/OFF
 CONTROL WITH A NON-POSITIVE SHUT-OFF. IF AN
 ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS
 USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT
 THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER
 WATER THAT IS 120?F MAXIMUM.
  
 4. SHT. ID-3 THE GRAB BARS SHALL BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC
 ACC 609.4
  
 5. SHOW COMPLIANCE WITH FBC ACC 608.7 THRESHOLDS.
 THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2
 INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR
 VERTICAL.
  
 6. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.6
  
 7. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE.PER FBC ACC 604.5.2
  
 8. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. THE
 SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR
 SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT.
  
 9. SHT P-1 THE EXISTING WATER METER AND BACK FLOWS ARE
 SHOWN IN 2 DIFFERENT LOCATIONS 1 IS NEXT TO CORNER OF
 THE BUILDING THE OTHER 1 IS SHOWN BY THE DOUBLE DOORS.
 PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 10. A BACK FLOW IS REQUIRED ON THE REFRIGERATOR ICE
 MAKER NOTE ON PLAN OR SHOW ON WATER ISOMETRIC. PER FBC
 PL 608.3
  
 11. A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND
 CAPPING OF THE GAS APPLIANCES AND PIPING.PLEASE PLACE
 NOTE ON PLAN. PER AMEND TO FBC 107.2.1 AND 105.1
  
 12. PROVIDE FLOOR PLAN SHOWING LOCATION OF GAS PIPING
 TO BE CAPPED . PER WPB AMEND TO FBC
 107.3.5.1.5(1)(2)(9)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-02 Cont ID  
Sent By aaponte Date 2019-10-02 Time 15:34 Rev Time 0.00
Received By elevesqu Date 2019-10-02 Time 15:34 Sent To  
Notes
***NONE***