Plan Review Details - Permit 19081368
Plan Review Stops For Permit 19081368
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-04 Cont ID  
Sent By rmcdouga Date 2019-11-04 Time 08:36 Rev Time 0.00
Received By rmcdouga Date 2019-11-04 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-09 Cont ID  
Sent By shill Date 2019-10-09 Time 07:18 Rev Time 0.00
Received By shill Date 2019-10-09 Time 07:17 Sent To  
Notes
2019-10-09 07:19:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 109, THE COST BREAKDOWN DID NOT INCLUDE SQUARE
 FOOT AREAS; REVISE AND SEND TO ME VIA EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER 19081368 IN THE SUBJECT LINE.
  
 2. SEE MECHANICAL COMMENTS. PROVIDE A MECHANICAL PLAN
 AND SHOW LOCATION OF NEW UNITS AS A ZONING REVIEW WILL
 BE REQUIRED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By rmcdouga Date 2019-09-16 Time 19:16 Rev Time 0.00
Received By rmcdouga Date 2019-09-16 Time 17:56 Sent To M
Notes
2019-09-16 19:16:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A FLOOR PLAN DRAWING SHOWING
 THE LOCATIONS AND SIZES OF THE EXISTING WINDOWS THAT
 WILL BE REPLACED. INDICATE IF THERE ARE ANY OPENINGS
 WITH MULTIPLY WINDOWS THAT ARE CONNECTED WITH
 STRUCTURAL MULLIONS. (IF SO SUBMIT PRODUCT APPROVALS
 FOR THE MULLIONS.) FBC 107.2.1
  
 2) THE VALUE FOR THIS WORK APPEARS TO BE LOW. SUBMIT A
 COPY OF THE SIGNED CONTRACT TO VERIFY VALUE. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-11-06 Cont ID  
Sent By ppetty Date 2019-11-06 Time 09:45 Rev Time 0.00
Received By ppetty Date 2019-11-06 Time 09:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-03 Cont ID  
Sent By ppetty Date 2019-10-03 Time 13:08 Rev Time 0.00
Received By ppetty Date 2019-10-03 Time 13:08 Sent To  
Notes
2019-10-03 13:08:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By jpearson Date 2019-09-13 Time 13:39 Rev Time 0.00
Received By jpearson Date 2019-09-13 Time 09:37 Sent To  
Notes
2019-09-13 13:39:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-11-14 Cont ID  
Sent By hmoser Date 2019-11-14 Time 13:36 Rev Time 0.00
Received By hmoser Date 2019-11-08 Time 15:50 Sent To  
Notes
2019-11-12 15:50:34RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-06 Cont ID  
Sent By ppetty Date 2019-11-06 Time 09:46 Rev Time 0.00
Received By ppetty Date 2019-10-30 Time 13:56 Sent To  
Notes
2019-10-31 13:56:21R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-09 Cont ID  
Sent By shill Date 2019-10-09 Time 07:19 Rev Time 0.00
Received By shill Date 2019-09-27 Time 13:33 Sent To  
Notes
2019-10-01 13:33:08R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-17 Cont ID  
Sent By hmoser Date 2019-09-17 Time 08:54 Rev Time 0.00
Received By hmoser Date 2019-08-27 Time 15:11 Sent To  
Notes
2019-08-27 15:11:40R08

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-11-14 Cont ID  
Sent By hmoser Date 2019-11-14 Time 13:36 Rev Time 0.00
Received By hmoser Date 2019-11-14 Time 12:55 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-11-04 Cont ID  
Sent By hmoser Date 2019-11-04 Time 11:00 Rev Time 0.00
Received By hmoser Date 2019-11-04 Time 10:42 Sent To  
Notes
2019-11-04 10:59:53PLAN DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON PLAN. PER SECTION
 107 FBC 2017.
 2) PROVIDE GRILL SIZE ON PLAN. PER SECTION
 107 FBC 2017
 3) REFER TO SECTION 107.2.1 FBC INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. FBC 2017.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-10-04 Cont ID  
Sent By hmoser Date 2019-10-04 Time 13:01 Rev Time 0.00
Received By hmoser Date 2019-10-04 Time 11:42 Sent To I
Notes
2019-10-04 13:00:52FAIL
 NO AIR CONDITIONING PLAN SUBMITTED HM.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By rmcdouga Date 2019-09-17 Time 08:52 Rev Time 0.00
Received By hmoser Date 2019-09-17 Time 08:52 Sent To I
Notes
2019-09-17 08:54:08PLAN DENIED
 NO PLANS SUBMITTED HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-03 Cont ID  
Sent By lcrespo Date 2019-10-03 Time 06:34 Rev Time 0.00
Received By lcrespo Date 2019-10-03 Time 06:34 Sent To  
Notes
2019-10-03 06:35:3210/03/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By lcrespo Date 2019-08-30 Time 16:09 Rev Time 0.00
Received By lcrespo Date 2019-08-30 Time 16:09 Sent To  
Notes
2019-08-30 16:09:3308/30/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS, PLEASE
 IDENTIFY ALL USE OF ROOMS ON PLANS PER THE 2017 FBC WPB
 AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
  
 2. PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE
 UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES PER THE 2017 FLORIDA BUILDING CODE
 TO WEST PALM BEACH AMENDMENTS SEC 107.2.1.3.
  
 3. A SUB PLUMBING PERMIT IS REQUIRED FOR PER 2017 FBC
 TO WPB AMENDMENTS SEC. 105.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  