Plan Review Details - Permit 19081310
Plan Review Stops For Permit 19081310 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-08-30 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-30 |
Time |
10:19 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-10-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-07 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-10-07 |
Time |
09:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-10-01 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-10-01 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-08-26 |
Time |
16:44 |
Sent To |
|
|
Notes |
2019-08-26 16:44:43 | REVISION ROUTED TO ZONING INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2019-10-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-10-07 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-10-07 |
Time |
09:36 |
Sent To |
|
|
Notes |
2019-10-07 09:37:44 | SEE PERMIT APPLICATION #19091173 FOR PLUMBING PERMIT | | APPLICATION AND PLANS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-09-06 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-10-01 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-09-06 |
Time |
06:19 |
Sent To |
Z |
|
Notes |
2019-09-06 06:34:19 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE DRINKING FOUNTAINS AND THE | | SHOWERS. WPB AMEND. TTO FBC SEC. 107.2.1. | | 2) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2017 | | FBC-ACCESSIBILITY SECS.211.1, 211.2, 602. | | 3) ONE OF THE SHOWERS SHALLL COMPLY WITH 2017 FBC- | | ACCESSIBILITY SEC.309. AND BE ON AN ACCESSIBLE ROUTE | | AND COMPLY WITH FBC-ACCESS. SECS. 402, 403. SHOW THE | | HEIGHT OF THE CONTROLS FOR THE SHOWER ON THE PLANS. | | 4) IDENTIFY THE LOCATIONS OF BOTH DRINKING FOUNTAINS ( | | A & B ) ON SHT. C5.00. | | 5) THE DRINKING FOUNTAINS SHALL CONNECT TO THE DRAINAGE | | SYSTEM PER THE 2017 FBC-PLUMBING SEC. 301.3. | | 6) SHOW THE SIZE OF THE DRINKING FOUNTAIN DRAIN ON THE | | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. COMPLY WITH 2017 | | FBC-PLUMBING TABLE 710.1(1). | | 7 SUBMIT A PLUMBING PERMIT APPLICATION FROM A LICENSED | | PLUMBING CONTRACTOR FOR THIS WORK. THIS IS TO BE A | | SSTAND ALONE PLUMBING PERMIT, NOT A REVISION. A GENERAL | | CONTRACTOR CANNOT BE ISSUED THIS PERMIT AS IT FALLS | | OUTSIDE THE SCOPE OF THEIR LICENSE PER FL. STATUTE 489. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2019-09-25 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-09-25 |
Time |
15:38 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2019-09-25 |
Time |
15:37 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |