Plan Review Details - Permit 19081310
Plan Review Stops For Permit 19081310
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-10-01 Cont ID  
Sent By dbattles Date 2019-08-30 Time 10:19 Rev Time 0.00
Received By dbattles Date 2019-08-30 Time 10:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-07 Cont ID  
Sent By tklarge Date 2019-10-07 Time 09:38 Rev Time 0.00
Received By tklarge Date 2019-10-07 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-01 Cont ID  
Sent By dbattles Date 2019-10-01 Time 09:18 Rev Time 0.00
Received By dbattles Date 2019-08-26 Time 16:44 Sent To  
Notes
2019-08-26 16:44:43REVISION ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-10-07 Cont ID  
Sent By tklarge Date 2019-10-07 Time 09:36 Rev Time 0.00
Received By tklarge Date 2019-10-07 Time 09:36 Sent To  
Notes
2019-10-07 09:37:44SEE PERMIT APPLICATION #19091173 FOR PLUMBING PERMIT
 APPLICATION AND PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-10-01 Time 09:18 Rev Time 0.00
Received By tklarge Date 2019-09-06 Time 06:19 Sent To Z
Notes
2019-09-06 06:34:191) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE DRINKING FOUNTAINS AND THE
 SHOWERS. WPB AMEND. TTO FBC SEC. 107.2.1.
 2) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2017
 FBC-ACCESSIBILITY SECS.211.1, 211.2, 602.
 3) ONE OF THE SHOWERS SHALLL COMPLY WITH 2017 FBC-
 ACCESSIBILITY SEC.309. AND BE ON AN ACCESSIBLE ROUTE
 AND COMPLY WITH FBC-ACCESS. SECS. 402, 403. SHOW THE
 HEIGHT OF THE CONTROLS FOR THE SHOWER ON THE PLANS.
 4) IDENTIFY THE LOCATIONS OF BOTH DRINKING FOUNTAINS (
 A & B ) ON SHT. C5.00.
 5) THE DRINKING FOUNTAINS SHALL CONNECT TO THE DRAINAGE
 SYSTEM PER THE 2017 FBC-PLUMBING SEC. 301.3.
 6) SHOW THE SIZE OF THE DRINKING FOUNTAIN DRAIN ON THE
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1. COMPLY WITH 2017
 FBC-PLUMBING TABLE 710.1(1).
 7 SUBMIT A PLUMBING PERMIT APPLICATION FROM A LICENSED
 PLUMBING CONTRACTOR FOR THIS WORK. THIS IS TO BE A
 SSTAND ALONE PLUMBING PERMIT, NOT A REVISION. A GENERAL
 CONTRACTOR CANNOT BE ISSUED THIS PERMIT AS IT FALLS
 OUTSIDE THE SCOPE OF THEIR LICENSE PER FL. STATUTE 489.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-09-25 Cont ID  
Sent By eschneid Date 2019-09-25 Time 15:38 Rev Time 0.25
Received By eschneid Date 2019-09-25 Time 15:37 Sent To  
Notes
***NONE***