2019-08-29 11:50:44 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) THERE IS ONLY ONE HORN STOBE INDICATED WITH EACH |
| UNIT, WHICH MAY NOT MEET THE DECIBEL LEVELS AT THE |
| PILLOW HEIGHT PER NFPA 72 |
| |
| PER NFPA 72 |
| |
| 18.4.5 SLEEPING AREA REQUIREMENTS. |
| 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO |
| PROVIDE |
| SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND |
| LEVEL OF AT |
| LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 |
| DB |
| ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT |
| LEAST |
| 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, |
| WHICHEVER IS |
| GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA |
| REQUIRED TO BE |
| SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). |
| 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR |
| RETRACTABLE |
| PARTITION, IS LOCATED BETWEEN THE NOTIFICATION |
| APPLIANCE AND |
| THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED |
| WITH THE |
| BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW. |
| |
| PLEASE ENUSRE COMPLIANCE AND PROVIDE REVISIONS AS |
| APPLICABLE BEFORE FINAL INSPECTIONS, |
| |
| |