Plan Review Details - Permit 19081187
Plan Review Stops For Permit 19081187
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By cthroop Date 2019-10-24 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-10-23 Time 17:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By cthroop Date 2019-09-16 Time 11:00 Rev Time 0.00
Received By cthroop Date 2019-09-13 Time 15:04 Sent To  
Notes
2019-09-16 11:09:27BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOW AND DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 2. PROVIDE SHUTTER SCHEDULE PER NOTE ON PLAN PAGE 1 OF
 5.
 FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES" OR PROVIDE ALL INFORMATION
 REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE
 FACTORS THAT APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 3. PROVIDE ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 4. DESIGNER TO SHOW LOCATION AND R VALUE OF INSULATION.
 R402.1 GENERAL (PRESCRIPTIVE).
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4.
  
 R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE).
 IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1,
 INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF
 SECTIONS R402.2.1 THROUGH R402.2.13.
  
 5. ENGINEER OF RECORD SHALL PLACE STATEMENT ON PLAN
 THAT EXISTING RAFTERS CAN SUPPORT THE ADDITION LOAD OF
 THE NEW AHU.
 M1201.1SCOPE.
 THE PROVISIONS OF CHAPTERS 12 THROUGH 24 SHALL REGULATE
 THE DESIGN, INSTALLATION, MAINTENANCE, ALTERATION AND
 INSPECTION OF MECHANICAL SYSTEMS THAT ARE PERMANENTLY
 INSTALLED AND USED TO CONTROL ENVIRONMENTAL CONDITIONS
 WITHIN BUILDINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-11-01 Cont ID  
Sent By jpearson Date 2019-11-01 Time 12:39 Rev Time 0.00
Received By jpearson Date 2019-11-01 Time 12:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-21 Cont ID  
Sent By jpearson Date 2019-10-21 Time 10:14 Rev Time 0.00
Received By jpearson Date 2019-10-21 Time 08:31 Sent To  
Notes
2019-10-21 09:38:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By jpearson Date 2019-09-12 Time 11:21 Rev Time 0.00
Received By jpearson Date 2019-09-12 Time 08:40 Sent To  
Notes
2019-09-12 10:59:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. AFCI PROTECTION SHOWN IN NOTES IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED IS NOT
 CODE COMPLIANT. SEE FBC RES. E3602. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 4. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW
 OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. PANEL SCHEDULE PROVIDED
 IN SOME LOCATIONS SHOWS THE INCORRECT WIRE SIZES FOR
 THE OVERCURRENT PROTECTION OF THE CIRCUIT. NEC 210.8,
 210.12, 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5;
 FBC RE E3706.2, E3902
 5. LOAD CALCULATION STATES THAT A 200 AMP SERVICE WILL
 BE PROVIDED. RISER DIAGRAM SHOWS A 150 AMP SERVICE
 BEING INSTALLED. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED. NEC 215.5, 230, 250.50, 250.94, 408.30; FBC
 RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 6. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-24 Cont ID  
Sent By cthroop Date 2019-10-24 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-10-08 Time 14:29 Sent To  
Notes
2019-10-09 14:29:45R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-16 Cont ID  
Sent By cthroop Date 2019-09-16 Time 11:12 Rev Time 0.00
Received By cthroop Date 2019-08-23 Time 12:10 Sent To  
Notes
2019-08-23 12:10:54R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By cthroop Date 2019-10-24 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-10-23 Time 17:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By cthroop Date 2019-09-16 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-09-13 Time 15:04 Sent To  
Notes
2019-09-16 11:12:12MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENERGY SUBMITTAL. INCLUDE MANUAL J
 CALCULATIONS.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. DESIGNER TO SHOW LOCATION AND R VALUE OF INSULATION.
 R402.1 GENERAL (PRESCRIPTIVE).
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4.
  
 R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE).
 IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1,
 INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF
 SECTIONS R402.2.1 THROUGH R402.2.13.
  
 3. ENGINEER OF RECORD SHALL PLACE STATEMENT ON PLAN
 THAT EXISTING RAFTERS CAN SUPPORT THE ADDITION LOAD OF
 THE NEW AHU.
 M1201.1SCOPE.
 THE PROVISIONS OF CHAPTERS 12 THROUGH 24 SHALL REGULATE
 THE DESIGN, INSTALLATION, MAINTENANCE, ALTERATION AND
 INSPECTION OF MECHANICAL SYSTEMS THAT ARE PERMANENTLY
 INSTALLED AND USED TO CONTROL ENVIRONMENTAL CONDITIONS
 WITHIN BUILDINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-05 Cont ID  
Sent By gjohnson Date 2019-11-05 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2019-11-05 Time 10:37 Sent To  
Notes
2019-11-05 10:39:42APPROVED FOR PLUMBING FIXTURES ONLY ANY PIPING WORK
 WILL REQUIRE A REVISION TO INCLUDE A FLOOR PLAN AND
 SANITARY ISOMETRIC DRAWING.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-10-11 Cont ID  
Sent By gjohnson Date 2019-10-11 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2019-10-11 Time 15:31 Sent To  
Notes
2019-10-11 16:53:141ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIALL, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. IT APPEARS THE SCOPE OF THE PLUMBING HAS BEEN
 ENLARGED SHT. 4OF 5 STATES THE SCOPE IS REPLACEMENT OF
 THE FIXTURE BUT IN THE SUBMITTAL PACKAGE I FOUND A 7 X
 11 SHEET OF PAPER THAT APPEARS TO BE FROM A PLUMBING
 CONTRACTOR STATING THE SCOPE OF THE WORK WAS REPLACING
 THE SEWER AND PIPING TO THE TOILET AND ALSO AL
 UNDERGROUND PIPING SHALL BE CPVC IT IS UNCLEAR EXACTLY
 WHAT IS BEING DONE PLEASE PROVIDE ON THE MAIN PLAN A
 CLEAR AND COMPLETE SCOPE OF PLUMBING WORK, IF THE
 UNDERGROUND SANITARY IS BEING REPLACED PLEASE PROVIDE A
 SANITARY ISOMETRIC. PER WPB AMEND TO FBC ACC
 107.3.5.3(12)
  
 2. HOW WILL THE JOB BE COMPLETED WILL THE CONCRETE BE
 CHANNELED OUT IF SO PROVIDE A REPAIR DETAIL IF IT IS A
 TUNNEL JOB PROVIDE A REPORT OF HOW THE HOLE WILL BE
 BACK FILLED TO PROVIDE STRUCTURAL STABILITY FOR THE
 HOUSE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-30 Cont ID  
Sent By lcrespo Date 2019-08-30 Time 15:11 Rev Time 0.00
Received By lcrespo Date 2019-08-30 Time 14:33 Sent To  
Notes
2019-08-30 15:11:5908/30/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  