Plan Review Details - Permit 19081182
Plan Review Stops For Permit 19081182 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-11-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-11-21 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-11-21 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-09-19 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-09-19 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-09-19 |
Time |
13:42 |
Sent To |
|
|
Notes |
2019-09-19 13:42:16 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB | | FBC 107.2.1, 107.3.5; FS 471, 481 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-11-21 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-11-13 |
Time |
07:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-09-19 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-09-05 |
Time |
13:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-11-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-11-21 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-11-21 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-09-19 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-09-19 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-09-19 |
Time |
13:41 |
Sent To |
|
|
Notes |
2019-09-19 13:41:34 | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | VERIFICATION. ADDITIONALLY, THE DIGITAL SIGNATURE MUST | | INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC | | 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS | | 471/481 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-11-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-11-18 |
Time |
13:43 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2019-11-18 |
Time |
12:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-09-13 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-09-13 |
Time |
15:09 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2019-09-13 |
Time |
15:09 |
Sent To |
|
|
Notes |
2019-09-13 16:24:15 | FAILED | | | | PROVIDE WRITTEN RESPONSE. | | | | 1) THE ZONING AND LAND DEVELOPMENT CODE REQUIRES THAT | | THE MAXIMUM FOOTCANDLE AT THE PROPERTY LINE IS 1.0. THE | | FOOTCANDLE VALUES ALONG OKEECHOBEE BOULEVARD, WHILE | | SHOWN AT LESS THAN 1.0 FOOTCANDLE, ARE NOT SHOWN AT THE | | PROPERTY LINE, BUT RATHER WITHIN THE OKEECHOBEE | | BOULEVARD RIGHT-OF-WAY. THE PHOTOMETRIC PLAN NEEDS TO | | BE REVISED TO SHOW THE FOOTCANDLE MEASURES AT THE | | PROPERTY LINE. | | | | 2) PROVIDE VERIFICATION THAT THE LIGHT POLES ALONG THE | | ROADWAYS DO NOT CREATE GLARE INTO THE ADJACENT | | RIGHTS-OF-WAY. | | | | 3) THE PLANS DO NOT INDICATE IF THE POLES ALONG | | OKEECHOBEE BOULEVARD EXCHANGE COURT AND THE EAST | | PROPERTY LINE ARE NEW OR EXISTING. ALL NEW POLES ARE TO | | BE SET BACK A MINIMUM OF FIVE (5) FEET FROM THE | | PROPERTY LINE. THE FIVE (5) FOOT SETBACK IS REQUIRED TO | | BE SHOWN ON THE PLANS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|
|
|