Plan Review Details - Permit 19081171
Plan Review Stops For Permit 19081171
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By jgomez Date 2019-10-03 Time 10:07 Rev Time 0.00
Received By jgomez Date 2019-10-03 Time 09:41 Sent To  
Notes
2019-10-03 10:45:02RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ACCESSIBLE PARKING SPACE AS REQUIRED BY SEC.
 208.1 FBC-ACCESSIBILITY.
 1(A) PARKING SPACE SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE TO THE ENTRANCE OF THE BUILDING AS
 REQUIRED BY SEC. 208.3.1 FBC-ACCESSIBILITY. PROVIDE
 COMPLETE SITE PLAN DRAWN TO SCALE SHOWING THE PARKING
 LOT AND THE ENTRANCE TO THE BUILDING. SEC. 107.2.1.3
 AND 107.3.5.1 CITY AMENDMENTS.
 1(B) SPECIFY THE SIZE OF THE ACCESSIBLE PARKING SPACE
 AND ADJACENT AISLE. SEC. 502.2 AND SEC. 502.3
 FBC-ACCESSIBILITY
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-10-07 Cont ID  
Sent By rrossano Date 2019-10-07 Time   Rev Time  
Received By rrossano Date 2019-10-07 Time   Sent To  
Notes
2019-10-07 13:54:46PLEASE ADDRESS ZONING COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-07 Cont ID  
Sent By hmtribou Date 2019-10-07 Time 14:02 Rev Time 0.00
Received By cpuell Date 2019-08-28 Time 16:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-10-09 Cont ID  
Sent By shill Date 2019-10-09 Time 06:10 Rev Time 0.00
Received By shill Date 2019-10-09 Time 06:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-05 Cont ID  
Sent By hdanfort Date 2019-09-05 Time 16:51 Rev Time 0.00
Received By hmtribou Date 2019-09-05 Time 17:02 Sent To I
Notes
2019-09-05 17:02:31PROVIDE UPDATED SURVEY WITH ALL EXTERIOR DECKING
 CANNOT REMOVE SIDEWALK
 MINIMUM DRIVEWAY OPENING 20 FEET
 PARKING CONFIGURATION MUST MEET 94-485(J)(1)
 CROSS ACCESS SUGGESTED SINCE SAME OWNER AND WILL
 PROVIDE BETTER CIRCULATION
 PROVIDE ADA ACCESSIBLE PARKING SPACE AND PEDESTRIAN
 ACCESS
 REDUCE LANDSCAPE NONCONFORMITY
  