Plan Review Details - Permit 19081158
Plan Review Stops For Permit 19081158
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-02-13 Cont ID  
Sent By cpuell Date 2020-02-13 Time 13:59 Rev Time 0.00
Received By cpuell Date 2020-02-12 Time 14:13 Sent To  
Notes
2020-02-12 14:13:29ADDRESS WILL BE CHANGED TO 682 7TH ST, WORKING ON
 CHANGING IT. CP

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By rmcdouga Date 2020-01-30 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2020-01-30 Time 14:12 Sent To  
Notes
2020-01-30 14:14:54ADDRESS AND PCN WILL NEED TO BE VERIFIED AFTER LOTS ARE
 SPLIT FOR THIS CRA PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-05-29 Cont ID  
Sent By rmcdouga Date 2020-05-29 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2020-05-29 Time 13:05 Sent To  
Notes
2020-05-29 13:15:11NOTE 14 ON SHEET A1.0 REQUIRES THE CONTRACTOR TO COMPLY
 WITH ASBESTOS NOTIFICATION.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By rmcdouga Date 2020-04-13 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2020-04-13 Time 16:30 Sent To  
Notes
2020-04-13 16:33:16ASBESTOS NOTIFICATION REQUIREMENTS, PROVIDE A SIGNED
 ACKNOWLEDGMENT FROM THE CONTRACTOR STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By rmcdouga Date 2020-01-29 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2020-01-29 Time 07:34 Sent To  
Notes
2020-01-29 07:42:16ASBESTOS NOTIFICATION REQUIREMENTS, PROVIDE A SIGNED
 ACKNOWLEDGMENT FROM THE CONTRACTOR STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. IF THIS PROJECT IS NOT SUBJECT TO
 ASBESTOS NOTIFICATION REQUIREMENTS, THE CONTRACTOR IS
 TO PROVIDE A SIGNED STATEMENT ON LETTERHEAD EXPLAINING
 WHY IT IS EXEMPT (FOR EXAMPLE, ?THIS PROJECT IS EXEMPT
 BECAUSE IT IS A SINGLE FAMILY RESIDENCE AND IS NOT A
 PART OF A COMMERCIAL OR PUBLIC PROJECT, AND IS NOT A
 CITY-INITIATED DEMOLITION?).
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-09-29 Cont ID  
Sent By rmcdouga Date 2020-09-29 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2020-09-29 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-08-10 Cont ID  
Sent By rmcdouga Date 2020-08-10 Time 14:53 Rev Time 0.00
Received By rmcdouga Date 2020-08-10 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-29 Cont ID  
Sent By rmcdouga Date 2020-05-29 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2020-05-29 Time 15:03 Sent To  
Notes
2020-05-29 13:30:46PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIANT. THE OCCUPANT LOAD CALCULATIONS WERE
 CORRECTED ON SHEET A0.0 TO 38 OCCUPANTS. HOWEVER, THE
 LIFE SAFETY PLAN ON SHEET A2.0 WAS NOT CHANGED FROM 19
 TO 38 OCCUPANTS. PLEASE CORRECT SHEET A2.0. THE
 OCCUPANT LOAD CALCULATIONS ARE INCORRECT. THE JUICE BAR
 AND THE YOGA AREA ARE BOTH ASSEMBLY OCCUPANCIES.
 THEREFORE, YOU WOULD USE THE ASSEMBLY OCCUPANT LOAD
 FROM TABLE 1004.1.2 AND DIVIDE THE NET FLOOR AREA OF
 EACH OF THESE TWO AREAS BY 15. BASED ON THE AREAS
 PROVIDED, THIS GIVES YOU AN OCCUPANT LOAD OF 11
 (DECIMALS ALWAYS ROUND UP) FOR THE JUICE BAR AND 26 FOR
 THE YOGA AREA. INCLUDING THE 1 OCCUPANT FROM THE
 MECHANICAL ROOM AND BATHROOM AREAS THE TOTAL NUMBER OF
 OCCUPANTS IS 38. BECAUSE THE OCCUPANT LOAD IS LESS THAN
 50, THIS IS A TYPE B OCCUPANCY PER FBC 303.1.1.
 (ORIGINAL COMMENT FOLLOWS) SPECIFY OCCUPANCY TYPE AND
 OCCUPANT LOAD ON THE PLANS. FBC 302 & 1004 IT APPEARS
 THAT DUE TO SMALL SIZE BUILDING AND THE YOGA AREA THAT
 THERE WILL BE LESS THAN 50 PERSONS WHICH WOULD ALLOW
 THIS TO BE CLASSIFIED AS A BUSINESS OCCUPANCY. SEE
 SECTIONS 303.1.1, 303.1.2 AND 304.1.
  
 2) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH REVIEW COMMENT ALONG
 WITH THE CITY RE-SUBMITTAL FORM. THIS WILL ALSO HELP
 REDUCE PLAN REVIEW TIME.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-15 Cont ID  
Sent By rmcdouga Date 2020-04-15 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2020-04-13 Time 09:04 Sent To  
Notes
2020-04-13 16:49:21PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) THE BUILDING AREA ON SHEET A1.0 IS 724 SQFT THE
 AREAS SPECIFIED ON SHEET A2.0 TOTAL 614 SQFT. PROVIDE
 AN AREA TABULATION THAT LISTS THE CONDITIONED SPACE,
 PORCHES, RAMPS, ETC. (ORIGINAL COMMENT FOLLOWS) SPECIFY
 THE AREA TABULATIONS ON THE PLANS. FBC 107.2.1.2
  
 5) THE OCCUPANT LOAD CALCULATIONS ARE INCORRECT. THE
 JUICE BAR AND THE YOGA AREA ARE BOTH ASSEMBLY
 OCCUPANCIES. THEREFORE, YOU WOULD USE THE ASSEMBLY
 OCCUPANT LOAD FROM TABLE 1004.1.2 AND DIVIDE THE NET
 FLOOR AREA OF EACH OF THESE TWO AREAS BY 15. BASED ON
 THE AREAS PROVIDED, THIS GIVES YOU AN OCCUPANT LOAD OF
 11 (DECIMALS ALWAYS ROUND UP) FOR THE JUICE BAR AND 26
 FOR THE YOGA AREA. INCLUDING THE 1 OCCUPANT FROM THE
 MECHANICAL ROOM AND BATHROOM AREAS THE TOTAL NUMBER OF
 OCCUPANTS IS 38. BECAUSE THE OCCUPANT LOAD IS LESS THAN
 50, THIS IS A TYPE B OCCUPANCY PER FBC 303.1.1.
 (ORIGINAL COMMENT FOLLOWS) SPECIFY OCCUPANCY TYPE AND
 OCCUPANT LOAD ON THE PLANS. FBC 302 & 1004 IT APPEARS
 THAT DUE TO SMALL SIZE BUILDING AND THE YOGA AREA THAT
 THERE WILL BE LESS THAN 50 PERSONS WHICH WOULD ALLOW
 THIS TO BE CLASSIFIED AS A BUSINESS OCCUPANCY. SEE
 SECTIONS 303.1.1, 303.1.2 AND 304.1.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) THE DRAWINGS ON SHEET A3.0 SHOW A HORIZONTAL
 HANDRAIL EXTENSION AT THE BOTTOM OF THE STAIRS. THE
 HANDRAIL AT THE BOTTOM OF THE STAIRS IS REQUIRED TO
 FOLLOW THE SLOPE OF THE STAIR AND EXTEND THE LENGTH OF
 ONE TREAD PAST THE LAST RISER PER FBC ACCESSIBILITY
 505.10.3. (ORIGINAL COMMENT FOLLOWS) THE STAIRS ARE
 REQUIRED TO COMPLY WITH FBC ACCESSIBILITY SECTIONS 504
 STAIRWAYS AND 505 HANDRAILS.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) CHECK THAT THE CLEAR SPANS OF THE 2X6 CEILING
 JOISTS ARE ACCEPTABLE AS SHOWN ON PLANS. (ORIGINAL
 COMMENT FOLLOWS) PROVIDE ROOF FRAMING DETAILS FOR THE 2
 X 6 RAFTERS, CEILING JOISTS, RIDGE BOARD, COLLAR TIES,
 GABLE END FRAMING AND BRACING, ETC. SPECIFY THE RAFTER
 TO RIDGE CONNECTIONS. FBC CHAPTER 23 THE SECTIONS ON
 THE ROOF FRAMING PLAN ON SHEET S-2 ARE FLOOR DETAILS.
  
 14) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH REVIEW COMMENT ALONG
 WITH THE CITY RE-SUBMITTAL FORM. THIS WILL ALSO HELP
 REDUCE PLAN REVIEW TIME.
  
 NEW COMMENTS:
  
 15) SPECIFY THE ROOF SLOPE ON THE PLANS. FBC 107.2.1
  
 16) ON SHEET S-3 BOTH 5/8" AND 3/4" ROOF SHEATHING IS
 SPECIFIED. PLEASE CLARIFY. FBC 107.2.1
  
 17) CLEARLY SPECIFY THE REQUIRED 42" GUARD HEIGHT ON
 THE PLANS. FBC 1015.3
  
 18) THE PLANS SPECIFY BOTH LAWSON AND JELD WEN WINDOWS.
 THE PRODUCT APPROVAL FOR JELD WEN WERE NOT SUBMITTED.
 FBC 107.2.1
  
 19) THE SMALL WINDOWS APPEAR TO BE HORIZONTAL SLIDING
 WINDOWS ON THE ELEVATION DRAWINGS. PLEASE CLARIFY. FBC
 107.2.1
  
 20) THE WINDOWS ARE DESCRIBED AS DOUBLE HUNG IN THE
 WINDOW SCHEDULE DESCRIPTION AND PRODUCT APPROVALS ARE
 FOR SINGLE HUNG. PLEASE CLARIFY. FBC 107.2.1
  
 21) THE DESCRIPTION AND COMMENTS FOR THE DOORS IN THE
 DOOR SCHEDULE DO NOT MATCH. CORRECT SCHEDULE AND
 COORDINATE PRODUCT APPROVALS WITH THE SCHEDULE. FBC
 107.2.1
  
 22) THE PLANS SHOW OUTSWING EXTERIOR DOORS AND THE DOOR
 PRODUCT APPROVAL IS FOR OUTSWING DOORS. FBC 107.2.1
  
 23) ON SHEET S-2 THE SILL BEAM TO PIER CONNECTION
 DETAIL SHOWS SIMPSON MSTA CONNECTORS AT 24" O.C. THE
 PIER SPACING IS MORE THAN 24". PLEASE CLARIFY. FBC
 107.2.1
  
 24) THE PLANS SHOW BATT INSULATION AT THE GABLE ENDS.
 THE BUILDING IS SHOWN WITH AN INSULATED CEILING AND A
 NON-INSULATED ATTIC. PLEASE CLARIFY AND SPECIFY THE
 R-VALUE OF THE ATTTIC WALLS AND UNDER FLOOR INSULATION.
 FBC 107.2.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By rmcdouga Date 2020-01-30 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2020-01-29 Time 07:34 Sent To  
Notes
2020-01-30 10:10:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GOVERNING CODES ON SHEET AO ARE INCORRECT. THIS
 PROPOSED PROJECT IS THE CONVERSION OF AN EXISTING
 SINGLE FAMILY DWELLING TO A COMMERCIAL USE AS A JUICE
 BAR AND YOGA STUDIO. THE SIXTH EDITION (2017) FBC
 EXISTING BUILDING AND FBC BUILDING ARE THE GOVERNING
 CODES. THE CLASSIFICATION OF WORK FROM THE EXISTING
 BUILDING CODE SECTION 506 WOULD BE CHANGE OF OCCUPANCY.
 SECTIONS 508 HISTORIC BUILDINGS AND SECTIONS 509
 RELOCATED BUILDINGS MAY ALSO APPLY.
  
 2) GENERAL NOTE #1 ON SHEET A1.0 SPECIFIES THE FIFTH
 EDITION (2014) FBC RESIDENTIAL. THIS IS INCORRECT.
 PLEASE UPDATE NOTES.
  
 3) THE STRUCTURAL PLAN SHEETS NEED TO BE UPDATED TO
 REFERENCE THE 2017 FBC RATHER THAN THE 2014 FBC.
  
 4) SPECIFY THE AREA TABULATIONS ON THE PLANS. FBC
 107.2.1.2
  
 5) SPECIFY OCCUPANCY TYPE AND OCCUPANT LOAD ON THE
 PLANS. FBC 302 & 1004 IT APPEARS THAT DUE TO SMALL SIZE
 BUILDING AND THE YOGA AREA THAT THERE WILL BE LESS THAN
 50 PERSONS WHICH WOULD ALLOW THIS TO BE CLASSIFIED AS A
 BUSINESS OCCUPANCY. SEE SECTIONS 303.1.1, 303.1.2 AND
 304.1.
  
 6) PROVIDE A LIFE SAFETY PLAN. SHOW THE OCCUPANT LOADS,
 REQUIRED NUMBER OF EXITS, EXIT PATHS OF TRAVEL, EXIT
 ACCESS TRAVEL DISTANCE, EXIT AND EXIT ACCESS DOOR SIZES
 (CAPACITY AND ACTUAL NUMBER OF OCCUPANTS SERVED), ETC.
 FBC CHAPTER 10.
  
 7) SHOW COMPLIANCE WITH SIXTH EDITION (2017) FBC
 ACCESSIBILITY. THE PROPOSED RAMP DOES NOT MEET ALL OF
 THE ADA REQUIREMENTS FOR A RAMP. A 60" X 60" MINIMUM
 CLEAR LANDING IS REQUIRED BETWEEN RAMP RUNS WHEN THERE
 IS A CHANGE OF DIRECTION PER SECTION 405.7.4.
  
 8) THE RAMP HANDRAILS ARE REQUIRED TO COMPLY WITH FBC
 ACCESSIBILITY SECTION 505 INCLUDING TOP AND BOTTOM
 EXTENSIONS.
  
 9) THE STAIRS ARE REQUIRED TO COMPLY WITH FBC
 ACCESSIBILITY SECTIONS 504 STAIRWAYS AND 505 HANDRAILS.
  
 10) THE ACCESSIBLE DOORS ARE REQUIRED TO COMPLY WITH
 FBC ACCESSIBILITY 404, INCLUDING SECTION 404.2.5 FOR
 MAXIMUM 1/2" HIGH THRESHOLDS.
  
 11) THE SALE/SERVICE COUNTER IS REQUIRED TO COMPLY WITH
 FBC ACCESSIBILITY SECTION 904.4.2. IT APPEARS THAT YOU
 INTEND TO PROVIDE FOR A FORWARD APPROACH SINCE THE
 ACCESSIBLE COUNTER SPACE IS 30" WIDE. HOWEVER, SECTION
 904.4.2 REQUIRES KNEE AND TOE SPACE UNDER THE COUNTER
 COMPLYING WITH SECTION 306. I DID NOT SEE A DETAIL FOR
 THIS ON THE PLANS. PLEASE CLARIFY.
  
 12) SHEET S-1 OF THE STRUCTURAL PLANS SPECIFIES A FLOOR
 LIVE LOAD OF 40 PSF WHICH IS FOR RESIDENTIAL. PLEASE
 REVIEW FBC 1603.1 & 1607 TO DETERMINE THE FLOOR LIVE
 LOADS FOR THIS PROJECT.
  
 13) PROVIDE ROOF FRAMING DETAILS FOR THE 2 X 6 RAFTERS,
 CEILING JOISTS, RIDGE BOARD, COLLAR TIES, GABLE END
 FRAMING AND BRACING, ETC. SPECIFY THE RAFTER TO RIDGE
 CONNECTIONS. FBC CHAPTER 23 THE SECTIONS ON THE ROOF
 FRAMING PLAN ON SHEET S-2 ARE FLOOR DETAILS.
  
 14) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH REVIEW COMMENT ALONG
 WITH THE CITY RE-SUBMITTAL FORM. THIS WILL ALSO HELP
 REDUCE PLAN REVIEW TIME.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-11 Cont ID  
Sent By fgiaquin Date 2020-08-11 Time 22:14 Rev Time 0.00
Received By fgiaquin Date 2020-08-11 Time 21:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-01 Cont ID  
Sent By jleahy Date 2020-05-01 Time 08:09 Rev Time 0.00
Received By jleahy Date 2020-04-30 Time 14:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-12 Cont ID  
Sent By fgiaquin Date 2020-01-12 Time 17:15 Rev Time 0.00
Received By fgiaquin Date 2020-01-09 Time 07:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-17 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-05-20 Cont ID  
Sent By pleduc Date 2020-05-20 Time   Rev Time 0.00
Received By pleduc Date 2020-05-20 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-13 Cont ID  
Sent By pleduc Date 2020-04-13 Time   Rev Time 0.00
Received By pleduc Date 2020-04-13 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-03 Cont ID  
Sent By pleduc Date 2020-01-03 Time   Rev Time 0.00
Received By pleduc Date 2020-01-03 Time 15:39 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2020-07-24 Cont ID  
Sent By fmittner Date 2020-07-24 Time 09:55 Rev Time 0.00
Received By fmittner Date 2020-07-24 Time 09:55 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-05-22 Cont ID  
Sent By fmittner Date 2020-05-22 Time 12:04 Rev Time 0.00
Received By fmittner Date 2020-05-22 Time 12:04 Sent To  
Notes
2020-05-22 12:05:21APPROVED WITH PROVIZO THAT WINDOW BE SWITCHED FROM HR
 TO SH OR CASEMENT

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-04-15 Cont ID  
Sent By fmittner Date 2020-04-15 Time 11:58 Rev Time 0.00
Received By fmittner Date 2020-04-15 Time 11:58 Sent To  
Notes
2020-04-15 11:59:021. WOOD SIDING DETAIL FOR ALL STRUCTURES WITH PROFILE,
 MATERIAL AND SIZE SHALL BE INCLUDED.
  
 2. ALL LATTICEWORK SHALL BE MADE OF WOOD AND NOTATIONS
 FOR VINYL SHALL BE REMOVED.
  
 3. ALL RAILINGS SHALL BE ALUMINUM OR WOOD.
  
 4. A WINDOW AND DOOR SCHEDULE SHALL BE PROVIDED FOR ALL
 STRUCTURES.
  
 5. A MUNTIN DETAIL SHALL BE PROVIDED DURING THE
 PERMITTING PROCESS (LAWSON MAY NO LONGER
 MANUFACTURE AN OGEE MUNTIN PROFILE).
 6. ALL PLANS SHALL BE CONSISTENT AND UNIFORM FOR ALL
 STRUCTURES.
  
 7. THE FAR DIAGRAM SHALL BE UPDATED TO INCLUDE THE
 PORTION OF COVERED WALKWAYS AND PATIOS IN THE
 AMOUNT AS DEFINED BY THE FAR DEFINITION FOR HISTORIC
 STRUCTURES. APPLICANT SHALL UPDATE LOT
 COVERAGE PERCENTAGE DATA TO WHOLE PERCENTAGES (E.G. 33%
 NOT .33%).
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By fmittner Date 2020-01-06 Time 16:08 Rev Time 0.00
Received By fmittner Date 2020-01-06 Time 16:08 Sent To  
Notes
2020-01-06 16:08:36TWO SMALL WINDOWS TO BE VERTICALLY ORIENTED NOT
 HORIZONTALLY AS SHOWN

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 11:17 Rev Time 0.00
Received By equinone Date 2020-09-08 Time 13:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-12 Cont ID  
Sent By lmarchan Date 2020-08-12 Time 11:24 Rev Time 0.00
Received By lmarchan Date 2020-07-15 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-24 Cont ID  
Sent By tklarge Date 2020-06-24 Time 08:12 Rev Time 0.00
Received By tklarge Date 2020-05-18 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-01 Cont ID  
Sent By jleahy Date 2020-05-01 Time 08:13 Rev Time 0.00
Received By jleahy Date 2020-04-10 Time 13:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-30 Cont ID  
Sent By rmcdouga Date 2020-01-30 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2019-12-17 Time 13:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-03-24 Cont ID  
Sent By lmarchan Date 2021-03-24 Time 08:37 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 13:36 Sent To  
Notes
2021-03-24 08:37:10RECEIPT MU-2020-37770 - $14,483.98 - PAID
  
2020-09-18 14:56:259/18/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By rmcdouga Date 2020-01-29 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2020-01-29 Time 08:14 Sent To  
Notes
2020-01-29 08:16:54PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-09-22 Cont ID  
Sent By medwards Date 2020-09-22 Time 11:06 Rev Time 0.00
Received By medwards Date 2020-09-22 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-08-05 Cont ID  
Sent By medwards Date 2020-08-05 Time 07:50 Rev Time 0.00
Received By medwards Date 2020-08-05 Time 06:24 Sent To  
Notes
2020-08-05 07:51:094TH REVIEW FBC-2017 MECHANICAL
 PERMIT-19081158
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED SHEET M1.1 SHOWS A GRIDDLE ON THE COUNTERTOP
 OF THE KITCHEN. PLEASE PROVIDE A MENU FOR THIS PROJECT.
 WHAT IS TO BE COOKED ON THE GRIDDLE? PLEASE SHOW THIS
 GRIDDLE WILL MEET FBC M 507.1
  
 2) BASED ON FBC M 507.1, ALL COMMERCIAL COOKING
 APPLIANCES MUST BE UNDER EITHER A TYPE I OR TYPE II
 HOOD. PLEASE UPDATE THE PLANS TO SHOW THE HOOD, ALSO
 SHOW THE DUCTWORK AND OUTDOOR TERMINATION LOCATION.
 PLEASE ALSO SHOW THE MAKE UP AIR CALCULATIONS AND HOW
 IT WILL BE PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-05-29 Cont ID  
Sent By medwards Date 2020-05-29 Time 12:17 Rev Time 0.00
Received By medwards Date 2020-05-29 Time 12:17 Sent To  
Notes
2020-05-29 12:18:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT-19081158
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FB FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPLOAD THE AC COOLING AND HEATING
 CALCULATIONS, DO NOT SEE THEM IN THIS VERSION. FBC FS
 107.2.1
  
 2) PLEASE UPLOAD REVISED MECHANICAL SHEETS. UPDATES
 STATED IN REVIEW COMMENTS ARE NOT SHOWN ON THE
 MECHANICAL SHEETS. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By ccole Date 2020-04-13 Time 16:07 Rev Time 0.00
Received By ccole Date 2020-04-13 Time 15:09 Sent To  
Notes
2020-04-13 16:09:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081158
 4/13/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED- PLEASE COMPLY.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEM- SECTION 312.1 FBC M.
  
 2) M1 & A6.0: INDICATE THAT A NON-COMBUSTIBLE BI-FOLD
 DOOR WILL ENCLOSE THE AC CLOSET- SEE SECTION 602.1 FBC
 M.
  
 3) M1: SHOW THE TOILET AND MOP SINK CLOSET EXHAUST DUCT
 RUNS AND TERMINATION LOCATIONS- SECTION 501.3.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-15 Cont ID  
Sent By ccole Date 2020-01-15 Time 11:07 Rev Time 0.00
Received By ccole Date 2020-01-15 Time 10:05 Sent To  
Notes
2020-01-15 11:12:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081158
 1/15/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEM- SECTION 312.1 FBC M.
  
 2) M1 & A6.0: INDICATE THAT A NON-COMBUSTIBLE BI-FOLD
 DOOR WILL ENCLOSE THE AC CLOSET- SEE SECTION 602.1 FBC
 M.
  
 3) M1: SHOW THE TOILET AND MOP SINK CLOSET EXHAUST DUCT
 RUNS AND TERMINATION LOCATIONS- SECTION 501.3.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-09-29 Cont ID  
Sent By lcrespo Date 2020-09-29 Time 13:21 Rev Time 0.00
Received By lcrespo Date 2020-09-29 Time 07:49 Sent To  
Notes
2020-09-29 13:21:109/29/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 4 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tklarge Date 2020-08-11 Time 13:37 Sent To  
Notes
2020-08-12 10:50:061) SHOW THE LOCATION OF THE DRINING FOUNTAINS ON THE
 ARCHITECTURAL FLOOR PLAN AND THE PLUMBING FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 3) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
 SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE PER
 FBC-BUILDING SEC. 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 4) THE BACKFLOWS FOR THE IRRIGATION SYTEM AND THE
 DOMESTIC WATE RSYSTEM WILL REQUIRE A SEPARATE PERMIT.
 MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING
 PERMIT SHALL BE SUBMITTED PRIOR TO THE INSTALLATION OF
 THESE DEVICES. THE DEVICES MUST BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR.F.S.489.103.
 5) A SEPARATE PERRMIT WILL BE REQUIRED FOR THE GREASE
 INTERCEPTOR. MANUFACTURER'S SPECIFICATIONS & DETAILS
 AND FACTORY SIZING CALCULATIONS WILL BE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE INTERCEPTOR PERMIT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-06-24 Cont ID  
Sent By tklarge Date 2020-06-24 Time 08:11 Rev Time 0.00
Received By tklarge Date 2020-06-23 Time 10:57 Sent To  
Notes
2020-06-23 14:03:091) SHT. A0.0 NOTES THE OCCUPANT LOAD AS 38 PERSONS AND
 SHT.A2.0 NOTES THE OCCUPANT LOAD AS 19 PERSONS.
 CLARIFY.
 2) IF THE OCCUPANT LOAD EXCEEDS 15 PERSONS, SEPARATE
 TOILET FACILITIES ARE REQUIRED FOR MALES AND FEMALES IN
 ACCORDANCE WITH FBC-PLUMBING SEC.403.2 AND TABLE 403.1.
 SINCE THIS IS CLASSIFIED AS A BUSINESS OCCUPANCY, THERE
 SHALL BE ONE WATER CLOSET AND LAVATORY FOR THE FIRST 25
 MALES AND ONE WATER CLOSET AND LAVATORY FOR THE FIRST
 40 FEMALES PER FBC-PLUMBING TABLE 403.1.
 3) DUE TO THE OCCUPANT LOAD THE PLUMBING CODE REQUIRES
 A DRINKING FOUNTAIN PER TABLE 403.1. THE DRINKING
 FOUNTAIN SHALL COMPLY WITH FBC-ACCESS. SEC. 211 AND
 FBC-PLUMBING SEC.410.3.
 4) SHT. A2.1 - DETAIL #1 - THE GRAB BAR ADJACENT TO THE
 WATER CLOSET IS SHOWN AS 36 INCHES IN LENGTH. THE
 MINIMUM LENGTH SHALL BE 42 INCHES IN ACCORDANCE WITH
 FBC-ACCESS. SEC. 604.5.1.
 5) SHT. P1.1 - THE PLUMBING PLAN STILL SHOWS A SHOWER
 ON THE EXTERIOR WHICH WAS SUPPOSED TO BE DELETED.
 CLARIFY.
 6) SHT. P1.1 - BACKFLOW PREVENTION SCHEDULE - THE
 BACKFLOW DEVICE FOR THE ICE MACHINE IS FOR CARBONATION
 AND BEVERAGE DISPENSING MACHINES AND SHALL COMPLY WITH
 ASSE 1024 PER FBC-PLUMBING SEC.608.13.10. THIS UNIT
 DOES NOT.
 7) SHT. P1.1 - PLACE A NOTE ON THE PLANS THAT ALL THE
 BACKFLOW PREVENTION DEVICES WILL BE LEAD FREE. 2ND
 REQUEST
 8) SUBMIT A DETAIL SHOWING THE CONNECTION OF THE HOT
 WATER RETURN LINE TO THE WATER HEATER COLD WATER LINE.
 WPB AMEND. TO FBC SEC. 107.2.1. SHT. P1.1 DOES NOT SHOW
 THIS CONNECTION. 2ND REQUEST.
 9) A BACKFLOW PREVENTION DEVICE MUST BE INSTALLED AT
 THE WATER METER ON THE WATER SERVICE TO THIS STRUCTURE
 PER THE CITY OF WEST PALM BEACH CROSS-CONNECTION
 CONTROL MANUAL.THE DEVICE MUST BE A REDUCED PRESSURE
 ZONE DEVICE AND MUST BE LEAD FREE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-30 Cont ID  
Sent By jpearson Date 2020-04-30 Time 17:43 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 14:49 Sent To  
Notes
2020-04-30 14:48:01REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19081158 682 7TH ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: EXTERIOR SHOWER NOTED ON PLAN SHEET A2.0 AND
 P1.1; PER FBC PL 303.1, PLUMBING FIXTURES, DRAINS,
 APPURTENANCES AND APPLIANCES USED TO RECEIVE OR
 DISCHARGE LIQUID WASTE OR SEWAGE SHALL BE DIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE SYSTEM OF THE
 BUILDING OR PREMISES, IN ACCORDANCE WITH THE
 REQUIREMENTS OF THIS CODE. THE OUTDOOR SHOWER SHALL NOT
 CONNECT TO THE STORM DRAINAGE SYSTEM AS NOTED ON P1.1.
 PER WPB FBC 107.2.1, PROVIDE CONNECTION TO SANITARY
 THROUGH A TRAPPED AND VENTED FIXTURE DRAIN. COMPLY WITH
 APPLICABLE SECTIONS OF FBC PL CHAPTERS 7 AND 9.
 2. RE: MOP SINK WALL FINISHES; A2.2/DETAIL 3 AND 5
 PERTAIN TO THE BATHROOM. PER WPB FBC 107.21.1, CLEARLY
 AND SPECIFICALLY INDICATE ON THE PLANS COMPLIANT WITH
 FBC 1210.2.2.
 3. RE: TOILET ROOM WALL FINISHES; A2.1/DETAIL 3 DOES
 NOT COMPLY WITH FBC 1210.2.2. PER WPB FBC 107.2.1,
 PROVIDE COMPLIANCE.
 4. RE: TOILET PAPER HOLDER; A2.1/DETAIL 1 SHOWS TOILET
 PAPER HOLDER AT 7 INCHES FROM FRONT OF TOILET TO EDGE
 OF HOLDER. PER FBC ACC 604.7 THE TOILET PAPER HOLDER
 SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM FROM
 FRONT OF TOILET TO CENTERLINE OF HOLDER. PER WPB FBC
 107.2.1, INDICATE THE SAME ON THE PLANS.
 5. RE: P1.1 BACKFLOW PREVENTION SCHEDULE; PER FBC PL
 605.2, ALL DEVICES SHALL BE LEAD FREE. PER WPB FBC
 107.2.1, PROVIDE CORRECT MODEL NUMBERS FOR DEVICES
 INDICATING THEY ARE LEAD FREE. IT IS NOTED THAT THE
 SD-3 FOR THE COFFEE MAKER IS OF STAINLESS STEEL
 CONSTRUCTION AND AS SUCH IS NOT AN ISSUE.
 6. PER WPB FBC 107.2.1, PROVIDE A DETAIL OF HOW THE HOT
 WATER RETURN WILL CONNECT TO THE WATER HEATER OR TO THE
 COLD WATER INTO THE WATER HEATER. SHOW ALL VALVING.
  
 A SEPARATE PERMIT AND REVIEW IS REQUIRED FOR
 IRRIGATION.
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY
 THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 19081158 682 7TH ST
  
  
 PHONE 561-805-6715
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
  
 PLUMBING COMMENTS: DENIED
  
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 1) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER 2017
  
 FBC - BUILDING SEC. 302.
  
 2) INDICATE THE OCCUPANCY LOAD ON THE PLANS PER 2017
  
 FBC-BUILDING SEC. 1104 & TABLE 1004.1.2.
  
 3) SHT.A1.0 REFERS TO THE 2014 FBC. THE CODE IN EFFECT
  
 IS THE 2017 FBC. REVISE THE NOTE.
  
 4) SHT. A2.0 & SHT.P1.1 SHOWS AN EXTERIOR SHOWER. WHAT
  
 WILL THIS SHOWER BE USED FOR? CLARIFY ON THE PLANS. WPB
  
 AMEND. TO FBC SEC. 107.1. DETAIL 1 ON P1.1 CALLS THIS
  
 OUT AS A CONDENSATE WELL AND CONDENSATE LINE. CLARIFY.
  
 5) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
  
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
  
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
  
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE CALLS
  
 OUT FLAT PAINT. THIS DOES NOT COMPLY.
  
 6) WALLS AND PARTITIONS WITHIN 2 FEET OF WATER CLOSETS
  
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
  
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
  
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE ON
  
 SHT.A6.0 DOES NOT SPECIFY THE HEIGHT OF THE
  
 TILE.CLARIFY.
  
 7) AN UNDER THE SINK GREASE TRAP MAY BE REQUIRED.
  
 8) SHT. A2.1 - THE TOP OF THE LAVATORY IN THE TOILET
  
 ROOM SHALL BE LOCATED A MAXIMUM OF 34 INCHES TO THE TOP
  
 OF THE RIM PER 2017 FBC - ACCESS. SEC.606.3.
  
 9) A MINIMUM CLEARANCE OF 27 INCHES SHALL BE PROVIDED
  
 UNDER THE LAVATORY PER 2017 FBC SEC.306.3.
  
 10) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
  
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
  
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
  
 FLOOR OR GROUND.2017 FBC-ACCESS. SEC.603.3.
  
 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7
  
 INCHES MINIMUM AND 9 INCHES MAXIMUM FROM THE FRONT OF
  
 THE WATER CLOSET TO THE CENTERLINE OF THE DISPENSER.
  
 2017 FBC ACCESS. SEC.604.7.
  
 12) THE DISHWASHER, ICE MACHINE, AND COFFEE MACHINE
  
 SHALL BE EQUIPPED WITH AA BACKFLOW DEVICE PER 2017
  
 FBC-PLUMBING SEC.608.2, 608.3, 608.16.10,
  
 13) A RECIRCULATION LINE MAY BE REQUIRED FOR THE HOT
  
 WATER SYSTEM IF THE DEVELOPED LENGTH OF THE HOT WATER
  
 PIPING EXCEEDS 50 FEET FROM THE SOURCE OF HOT WATER TO
  
 THE FIXTURES THAT REQUIRE HOT WATER PER 2017
  
 FBC-PLUMBING SEC.607.2.
  
 14) SHT. P1.1 - SHOW THE SIZE OF THE EXPANSION TANK ON
  
 THE PLANS.
  
 15) TEMPERED WATER IS REQUIRED TO THE LAVATORY IN THE
  
 TOILET ROOM PER 2017 FBC-PLUMBING SEC.607.1, 416.5.
  
 16) SHT. IR-1 - IRRIGATION SCHEDULE - THE BACKFLOW
  
 PREVENTER FOR THE IRRIGATION SHALL BE LEAD FREE. 2017
  
 FBC-PLUMBING SEC.605.2. THE 975 XL BACKFLOW DEVICE IS
  
 NOT LEAD FREE.
  
 17) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
  
 PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY
  
 THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY
  
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
  
  
 TIM LARGE
  
 CHIEF PLUMBING INSPECTOR
  
 PLUMBING PLAN REVIEW
  
 561-805-6692
  
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-13 Cont ID  
Sent By tklarge Date 2020-01-13 Time 11:07 Rev Time 0.00
Received By tklarge Date 2020-01-10 Time 13:23 Sent To  
Notes
2020-01-13 11:07:011) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER 2017
 FBC - BUILDING SEC. 302.
 2) INDICATE THE OCCUPANCY LOAD ON THE PLANS PER 2017
 FBC-BUILDING SEC. 1104 & TABLE 1004.1.2.
 3) SHT.A1.0 REFERS TO THE 2014 FBC. THE CODE IN EFFECT
 IS THE 2017 FBC. REVISE THE NOTE.
 4) SHT. A2.0 & SHT.P1.1 SHOWS AN EXTERIOR SHOWER. WHAT
 WILL THIS SHOWER BE USED FOR? CLARIFY ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.1. DETAIL 1 ON P1.1 CALLS THIS
 OUT AS A CONDENSATE WELL AND CONDENSATE LINE. CLARIFY.
 5) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE CALLS
 OUT FLAT PAINT. THIS DOES NOT COMPLY.
 6) WALLS AND PARTITIONS WITHIN 2 FEET OF WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE ON
 SHT.A6.0 DOES NOT SPECIFY THE HEIGHT OF THE
 TILE.CLARIFY.
 7) AN UNDER THE SINK GREASE TRAP MAY BE REQUIRED.
 8) SHT. A2.1 - THE TOP OF THE LAVATORY IN THE TOILET
 ROOM SHALL BE LOCATED A MAXIMUM OF 34 INCHES TO THE TOP
 OF THE RIM PER 2017 FBC - ACCESS. SEC.606.3.
 9) A MINIMUM CLEARANCE OF 27 INCHES SHALL BE PROVIDED
 UNDER THE LAVATORY PER 2017 FBC SEC.306.3.
 10) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.2017 FBC-ACCESS. SEC.603.3.
 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM FROM THE FRONT OF
 THE WATER CLOSET TO THE CENTERLINE OF THE DISPENSER.
 2017 FBC ACCESS. SEC.604.7.
 12) THE DISHWASHER, ICE MACHINE, AND COFFEE MACHINE
 SHALL BE EQUIPPED WITH AA BACKFLOW DEVICE PER 2017
 FBC-PLUMBING SEC.608.2, 608.3, 608.16.10,
 13) A RECIRCULATION LINE MAY BE REQUIRED FOR THE HOT
 WATER SYSTEM IF THE DEVELOPED LENGTH OF THE HOT WATER
 PIPING EXCEEDS 50 FEET FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT WATER PER 2017
 FBC-PLUMBING SEC.607.2.
 14) SHT. P1.1 - SHOW THE SIZE OF THE EXPANSION TANK ON
 THE PLANS.
 15) TEMPERED WATER IS REQUIRED TO THE LAVATORY IN THE
 TOILET ROOM PER 2017 FBC-PLUMBING SEC.607.1, 416.5.
 16) SHT. IR-1 - IRRIGATION SCHEDULE - THE BACKFLOW
 PREVENTER FOR THE IRRIGATION SHALL BE LEAD FREE. 2017
 FBC-PLUMBING SEC.605.2. THE 975 XL BACKFLOW DEVICE IS
 NOT LEAD FREE.
 17) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY
 THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2020-09-29 Cont ID  
Sent By lcrespo Date 2020-09-29 Time 09:09 Rev Time 0.00
Received By lcrespo Date 2020-09-29 Time 09:09 Sent To  
Notes
2020-09-29 09:10:06A SEPARATE PERMIT FOR THE GREASE INTERCEPTOR IS
 REQUIRED BY A LICENSED CONTRACTOR FOR THE SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-08-10 Cont ID  
Sent By rmcdouga Date 2020-08-10 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2020-08-10 Time 14:13 Sent To  
Notes
2020-08-10 14:15:02GAF ASPHALT SHINGLES - NOA NO. 18-0123.06

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 13:50 Rev Time 0.00
Received By equinone Date   Time   Sent To  
Notes
2020-10-20 13:51:34CHECKED THE DIGITAL SIGNATURE WITH PDF EXPRESS AND IT
 WAS OK, PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 11:13 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 11:13 Sent To  
Notes
2020-10-20 11:15:46ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 CIVIL PAGES SHOW A SIGNATURE THAT IS INVALID. PLEASE
 CONTACT ME FOR A PROVISO
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-08-10 Cont ID  
Sent By rmcdouga Date 2020-08-10 Time 15:01 Rev Time 0.00
Received By rmcdouga Date 2020-08-05 Time 08:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-29 Cont ID  
Sent By medwards Date 2020-05-29 Time 12:26 Rev Time 0.00
Received By medwards Date 2020-05-29 Time 12:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-01 Cont ID  
Sent By jleahy Date 2020-05-01 Time 08:12 Rev Time 0.00
Received By jleahy Date 2020-05-01 Time 08:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-30 Cont ID  
Sent By rmcdouga Date 2020-01-30 Time 13:43 Rev Time 0.00
Received By rmcdouga Date 2020-01-30 Time 13:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-07-24 Cont ID  
Sent By elevesqu Date 2020-07-24 Time 11:14 Rev Time 0.00
Received By elevesqu Date 2020-07-24 Time 11:14 Sent To  
Notes
2020-07-24 11:14:49EXTERIOR WALL MOUNTED UTILITIES SHALL BE PAINTED TO
 MATCH BUIDING COLOR UNLESS OTHERWISE SPECIFIED BY
 HISTORIC PRESERVATION DEPT.
  
 AC UNITS SHALL BE SCREENED BY LANDSCAPE
 ALL UTILITIES TO BE SCREENED BY LANSCAPE TO BEST EXTENT
 POSSIBLE
  
  
  
 LANDSCAPE REVIEWED THROUGH SEPARATE PERMIT
 FENCE THROUGH SEPARATE PERMIT
 SIGNAGE THORUGH SEPARATE PERMIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2020-05-29 Cont ID  
Sent By elevesqu Date 2020-05-29 Time 15:48 Rev Time 0.00
Received By elevesqu Date 2020-05-29 Time 15:48 Sent To  
Notes
2020-05-29 15:48:37PROVISOS:
  
 EXTERIOR WALL MOUNTED UTILITIES SHALL BE PAINTED TO
 MATCH BUIDING COLOR UNLESS OTHERWISE SPECIFIED BY
 HISTORIC PRESERVATION DEPT.
  
 AC UNITS SHALL BE SCREENED BY LANDSCAPE
 ALL UTILITIES TO BE SCREENED BY LANSCAPE TO BEST EXTENT
 POSSIBLE
  
  
  
 LANDSCAPE REVIEWED THROUGH SEPARATE PERMIT
 FENCE THROUGH SEPARATE PERMIT
 SIGNAGE THORUGH SEPARATE PERMIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2020-04-15 Cont ID  
Sent By elevesqu Date 2020-04-15 Time 14:10 Rev Time 0.00
Received By elevesqu Date 2020-04-15 Time 14:10 Sent To  
Notes
2020-04-15 14:10:43BUILDING SF ON COVER SHEET DOES NOT MATCH SF LISTED ON
 LOT DATA FROM SITE PLAN APPROVAL - PLEASE CLARIFY
  
 FLOOR PLAN DOES NOT MATCH LATEST SITE PLAN APPROVAL -
 FOR EXAMPLE, REAR LANDING DOES NOT MATCH SITE PLAN
 APPROVAL (WIDTH FOR DOOR OPENING)
 PLEASE UPLOAD RECENT PLANS FROM SITE PLAN APPROVAL
  
 MASTER SITE PLAN TO UPDATED- SHOWS CONCRETE PAD ON
 WRONG SIDE - PLEASE UPDATE TO MOST RECENT PLAN FROM
 SITE PLAN APPROVAL
  
 FENCING REQUIRES SEPARATE PERMIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By fmittner Date 2020-01-06 Time 16:08 Rev Time 0.00
Received By fmittner Date 2020-01-06 Time 16:08 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy