Plan Review Details - Permit 19081131
Plan Review Stops For Permit 19081131
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jwitmer Date 2019-09-16 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2019-09-16 Time 09:39 Sent To  
Notes
2019-09-16 13:51:02BUILT IN 1971.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.
  
 IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO
 ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY
 TO COMPLY WITH THE STATE & FEDERAL ASBESTOS
 REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61-
 NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS
 SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: *
 DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jwitmer Date 2019-09-16 Time 13:47 Rev Time 0.00
Received By jwitmer Date 2019-09-16 Time 09:39 Sent To  
Notes
2019-09-16 13:47:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081131
 ADD: 3800 WASHINGTON RD. SUITE: 1211
 CONT: PILLAR CONSTRUCTION
 TEL: 561-317-4042
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 16/ 2019
 ACTION: DENIED
  
 1) SHEET 2 OF 3 SHOWS IN DETAIL # 2 A SUSPENDED GRID
 SUSPENSION SYSTEM. WHAT THIS DETAIL NOR ANY OTHER
 DETAIL INDICATING HOW THE HANGING WIRE IS TO BE
 FASTENED TO THE STRUCTURAL CONCRETE DECK ABOVE NOR
 SPACING OF THE ANCHORS. THE PLANS ARE ALSO SILENT AS TO
 THE TYPE OF CONCRETE DECK POST TENSIONED SLAB,
 REQUIRING X-RAY FOR THE LOCATION OF TENDONS OR A
 CONVENTIONAL CONCRETE SLAB & REBAR SYSTEM? 2017 FBC-B
 TABLE 2508.1/ ASTM C754.
  
 2) SHEET 2 OF 3 SHOWS DETAIL # 2 WITH THE MAIN BEAMS
 BEING 1 ? INCH COLD ROLLED CHANNEL AND 7/8 INCH
 HIGH-HAT FURRING CHANNEL. WHAT THIS DETAIL INDICATES
 THE MAIN HANGER WIRE HANGER WIRE SPACING IS TO BE 4
 FEET ON CENTER. THE PLANS ARE SILENT AS TO THE GAUGE OF
 THE WIRE SIZE? 2017 FBC-B TABLE 2508.1/ ASTM C754. (6)
 SUSPENDED AND FURRED CEILINGS. MINIMUM OF # 12 GAUGE
 GALVANIZED SOFT ANNEALED, MILD STEEL WIRE. PLEASE
 UPDATE PLANS.
  
 3A) SHEET 2 OF 3 DETAIL 2 SHOWS THE HANGER WIRE
 ATTACHING TO THE MAIN RUNNER/ BEAM. THE PLANS ARE
 SILENT TO THE NUMBER OF WRAPS THE HANGER WIRE ONCE
 AROUND THE MAIN RUNNER IS TO WRAP AROUND ITSELF. ASTM
 C754. (6) SUSPENDED AND FURRED CEILINGS. SECTION 6. 1.
 3 TO DEVELOP THE FULL STRENGTH OF THE HANGER WIRE A
 MINIMUM OF 3 WRAPS AROUND ITSELF AND WITHIN 3 INCHES.
 PLEASE UPDATE PLANS.
  
 3B) THE PLANS ARE ALSO SILENT AS TO THE FASTENING OF
 THE 7/8 INCH HI-HAT CHANNEL TO THE MAIN RUNNER CHANNEL?
 PLEASE ALSO REFER TO ASTM C754 SECTION 6.1.3 REQUIRING
 A SADDLE TIE AROUND THE MAIN RUNNER AND FURRING
 MEMBERS. PLEASE UPDATE PLANS.
  
 3C) SHEET 2 OF 3 DETAIL 4 SHOWS THE HANGER WIRES AT 4
 FEET ON CENTER BUT DOES NOT INDICATE WHAT HAPPENS
 WITHIN THE LAST 4 FEET FROM THE WALL, THE HI-HAT IS
 LEFT FLOATING? PLEASE REVIEW ASTM C754 6.5.1 A CHANNEL
 SHALL BE LOCATED WITHIN 6 INCHES OF THE PARALLELING
 WALLS TO SUPPORT THE ENDS OF THE CROSS FURRING. THE
 ENDS SHALL BE SUPPORTED BY HANGER WIRE NOT LESS THAN 6
 INCHES FROM SUCH ENDS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By jpearson Date 2019-09-17 Time 15:25 Rev Time 0.00
Received By jpearson Date 2019-09-17 Time 14:26 Sent To I
Notes
2019-09-17 15:25:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION STATES THERE IS ELECTRICAL WORK,
 BUT NO ELECTRICAL IS SHOWN ON PLAN. PROVIDE ELECTRICAL
 PLAN FOR REVIEW, SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. WPB FBC 107.2.1, 107.3.5;
 FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-23 Cont ID  
Sent By pleduc Date 2019-08-23 Time   Rev Time 0.00
Received By pleduc Date 2019-08-23 Time 14:07 Sent To  
Notes
2019-08-23 14:15:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PROTECT AND MAINTAIN ANY APPLICABLE FIRE ALARM
 DEVICES AND SYSTEM FUNCTION DURING DEMO AND
 CONSTRUCTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-17 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-22 Time 14:08 Sent To  
Notes
2019-08-22 14:08:40B22

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-09-17 Cont ID  
Sent By ccole Date 2019-09-17 Time 08:30 Rev Time 0.00
Received By ccole Date 2019-09-17 Time 08:21 Sent To  
Notes
***NONE***