Plan Review Details - Permit 19080975
Plan Review Stops For Permit 19080975
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-24 Cont ID  
Sent By jgomez Date 2019-09-24 Time 15:14 Rev Time 0.00
Received By jgomez Date 2019-09-24 Time 14:53 Sent To  
Notes
2019-09-24 14:53:18DISCUSSED WITH SAMANTHA HILL. OK TO PASS HARD COPY
 PLANS WITH ORIGINAL SEAL AND SIGNATURE EVEN IF THE
 ORIGINAL MASTER PLANS WERE SUBMITTED WITH DIGITAL
 SIGNATURE. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By jgomez Date 2019-09-24 Time 09:27 Rev Time 0.00
Received By jgomez Date 2019-09-24 Time 08:32 Sent To  
Notes
2019-09-24 09:34:26RESIDENTIAL (R3) SITE WALL REVISION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- MASTER PERMIT 18120193 IS A DIGITAL SUBMITTAL. PLANS
 SUBMITTED ARE PRINTED COPIES. PRINTED COPIES OF DIGITAL
 SIGNATURES ARE NOT CONSIDERED SIGNED AND SEALED. SEE
 SEC. 61G15-23.004 FAC FOR PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 DRAWINGS NEED TO BE UPLOADED AND HAVE DIGITAL
 SIGNATURE. PLEASE CONTACT THE LIBRARIANS FOR DIGITAL
 SUBMITTAL.
  LAURA ELIZABETH MARCHANT
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6658
  E-MAIL: [email protected]
  
  CAROLINE PUELL
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6659
  E-MAIL: [email protected]
  
  
 RESPONSE:
 REPEAT COMMENT. PLANS WERE ORIGINALLY SUBMITTED AS A
 DIGITAL SUBMITTAL. ANY REVISED PLANS TO THE ORIGINAL
 APPROVED PERMIT NEED TO BE CONSISTENT AND SUBMITTED AS
 DIGITAL SUBMITTAL FOR PROPER RECORDS RETENTION. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
  
  
  
 IMPORTANT REMAINDERS:
  
 *****(1)PERMIT WAS APPROVED WITH PROVISO. PROVIDE
 REQUIRED INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. SEE PROVISO BELOW:
  
 BUILDING REVIEW APPROVED WITH PROVISO (SUBMIT
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1-REVISE PLANS AND RESUBMIT FOR REVIEW. SHOW ATTIC
 ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN THE 1ST & 2ND
 FLOOR.
 2-SUBMIT PRODUCT APPROVALS FOR REVIEW: A)WINDOW
 MULLIONS AND SPECIFY MULLION SIZE. B)DOORS PRODUCT
 APPROVAL FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE
 SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28:
 CLEARLY MARK WHICH ASSEMBLY L IS GOING TO BE USED. D)
 SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE. E) WATER PROOFING AT
 TERRACE. PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO
 RECEIVE MATERIAL SPECIFIED BY THE DESIGNER OF RECORD.
 F) DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.
 3-SUBMIT COMPLETE INFORMATION FOR ALUMINUM TRELLIS
 UNDER SEPARATE PERMIT PER ARCHITECT'S RESPONSE LETTER.
 4-REVISE PLANS AND RE-SUBMIT FOR REVIEW: ENTRY FOYER
 FINISH ELEVATION IN ALL PLANS. PER JOHN MELHORN, THE
 ELEVATION WILL BE 9'-0" (NAVD OF 1988) NOT 8'-6".
 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS.
 PROVIDE PRODUCT APPROVAL AND REVISE PLANS FOR REVIEW
 SHOWING LOCATION. ALSO, POWDER ROOM LOCATED IN THE
 GARAGE NEEDS TO BE ELEVATED TO 9'-0".
  
  
 *****(2)PROPERTY IS LOCATED IN FLOOD ZONE AE. ELEVATION
 CERTIFICATES ARE REQUIRED FOR BUILDING UNDER
 CONSTRUCTION AND FINISHED CONSTRUCTION. THERE ARE NO
 CITY RECORDS FOR THE BUILDING UNDER CONSTRUCTION
 ELEVATION CERTIFICATE. NEED TO PROVIDE ELEVATION
 CERTIFICATE FOR BUILDING UNDER CONSTRUCTION.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE CONTACT
 ME IF YOU HAVE ANY QUESTIONS:
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By jgomez Date 2019-09-10 Time 15:42 Rev Time 0.00
Received By jgomez Date 2019-09-10 Time 15:42 Sent To  
Notes
2019-09-10 15:43:31RESIDENTIAL (R3) SITE WALL REVISION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MASTER PERMIT 18120193 IS A DIGITAL SUBMITTAL. PLANS
 SUBMITTED ARE PRINTED COPIES. PRINTED COPIES OF DIGITAL
 SIGNATURES ARE NOT CONSIDERED SIGNED AND SEALED. SEE
 SEC. 61G15-23.004 FAC FOR PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 DRAWINGS NEED TO BE UPLOADED AND HAVE DIGITAL
 SIGNATURE. PLEASE CONTACT THE LIBRARIANS FOR DIGITAL
 SUBMITTAL.
  
  LAURA ELIZABETH MARCHANT
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6658
  E-MAIL: [email protected]
  
  OR
  
  
  CAROLINE PUELL
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6659
  E-MAIL: [email protected]
  
  
 IMPORTANT REMAINDERS:
  
 *****(1)PERMIT WAS APPROVED WITH PROVISO. PROVIDE
 REQUIRED INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. SEE PROVISO BELOW:
  
 BUILDING REVIEW APPROVED WITH PROVISO (SUBMIT
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1-REVISE PLANS AND RESUBMIT FOR REVIEW. SHOW ATTIC
 ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN THE 1ST & 2ND
 FLOOR.
 2-SUBMIT PRODUCT APPROVALS FOR REVIEW: A)WINDOW
 MULLIONS AND SPECIFY MULLION SIZE. B)DOORS PRODUCT
 APPROVAL FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE
 SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28:
 CLEARLY MARK WHICH ASSEMBLY L IS GOING TO BE USED. D)
 SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE. E) WATER PROOFING AT
 TERRACE. PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO
 RECEIVE MATERIAL SPECIFIED BY THE DESIGNER OF RECORD.
 F) DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.
 3-SUBMIT COMPLETE INFORMATION FOR ALUMINUM TRELLIS
 UNDER SEPARATE PERMIT PER ARCHITECT'S RESPONSE LETTER.
 4-REVISE PLANS AND RE-SUBMIT FOR REVIEW: ENTRY FOYER
 FINISH ELEVATION IN ALL PLANS. PER JOHN MELHORN, THE
 ELEVATION WILL BE 9'-0" (NAVD OF 1988) NOT 8'-6".
 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS.
 PROVIDE PRODUCT APPROVAL AND REVISE PLANS FOR REVIEW
 SHOWING LOCATION. ALSO, POWDER ROOM LOCATED IN THE
 GARAGE NEEDS TO BE ELEVATED TO 9'-0".
  
  
 *****(2)PROPERTY IS LOCATED IN FLOOD ZONE AE. ELEVATION
 CERTIFICATES ARE REQUIRED FOR BUILDING UNDER
 CONSTRUCTION AND FINISHED CONSTRUCTION. THERE ARE NO
 CITY RECORDS FOR THE BUILDING UNDER CONSTRUCTION
 ELEVATION CERTIFICATE. NEED TO PROVIDE ELEVATION
 CERTIFICATE FOR BUILDING UNDER CONSTRUCTION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-09-23 Cont ID  
Sent By rrossano Date 2019-09-23 Time   Rev Time 0.00
Received By rrossano Date 2019-09-23 Time   Sent To B
Notes
2019-09-23 07:46:35PASSED WITH PROVISO:
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. MORE INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2019-09-05 Cont ID  
Sent By rrossano Date 2019-09-05 Time   Rev Time 0.00
Received By rrossano Date 2019-09-05 Time   Sent To B
Notes
2019-09-05 07:56:25PASSED WITH PROVISO:
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. MORE INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By fmittner Date 2019-09-20 Time 14:20 Rev Time 0.00
Received By fmittner Date 2019-09-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-08-27 Cont ID  
Sent By fmittner Date 2019-08-27 Time 10:53 Rev Time 0.00
Received By fmittner Date 2019-08-27 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-24 Cont ID  
Sent By jgomez Date 2019-09-24 Time 15:14 Rev Time 0.00
Received By jgomez Date 2019-09-24 Time 14:47 Sent To  
Notes
2019-09-24 14:51:30DISCUSSED WITH SAMANTHA HILL. OK TO PASS HARD COPY
 PLANS WITH ORIGINAL SEAL AND SIGNATURE EVEN IF THE
 ORIGINAL MASTER PLANS WERE SUBMITTED WITH DIGITAL
 SIGNATURE. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-24 Cont ID  
Sent By jgomez Date 2019-09-24 Time 09:34 Rev Time 0.00
Received By jgomez Date 2019-09-17 Time 14:05 Sent To I
Notes
2019-09-18 14:05:18RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-10 Cont ID  
Sent By jgomez Date 2019-09-10 Time 15:43 Rev Time 0.00
Received By jgomez Date 2019-08-20 Time 15:53 Sent To I
Notes
2019-08-20 15:53:50REVISION ROUTED TO HISTORIC INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2019-09-24 Cont ID  
Sent By jgomez Date 2019-09-24 Time 14:54 Rev Time 0.00
Received By jgomez Date 2019-09-24 Time 14:54 Sent To  
Notes
2019-09-24 14:54:24DISCUSSED WITH SAMANTHA HILL. OK TO PASS HARD COPY
 PLANS WITH ORIGINAL SEAL AND SIGNATURE EVEN IF THE
 ORIGINAL MASTER PLANS WERE SUBMITTED WITH DIGITAL
 SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By jgomez Date 2019-09-24 Time 08:47 Rev Time 0.00
Received By jgomez Date 2019-09-24 Time 08:47 Sent To  
Notes
2019-09-24 08:48:12REPEAT COMMENT:
  
 1- MASTER PERMIT 18120193 IS A DIGITAL SUBMITTAL. PLANS
 SUBMITTED ARE PRINTED COPIES. PRINTED COPIES ARE NOT
 CONSIDERED SIGNED AND SEALED. SEE SEC. 61G15-23.004 FAC
 FOR PROCEDURES FOR DIGITALLY SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 DRAWINGS NEED TO BE UPLOADED AND HAVE DIGITAL
 SIGNATURE. PLEASE CONTACT THE LIBRARIANS FOR DIGITAL
 SUBMITTAL.
  
  LAURA ELIZABETH MARCHANT
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6658
  E-MAIL: [email protected]
  
  OR
  
  
  CAROLINE PUELL
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6659
  E-MAIL: [email protected]
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By jgomez Date 2019-09-10 Time 15:53 Rev Time 0.00
Received By jgomez Date 2019-09-10 Time 15:47 Sent To  
Notes
2019-09-10 15:54:27RESIDENTIAL (R3) SITE WALL REVISION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MASTER PERMIT 18120193 IS A DIGITAL SUBMITTAL. PLANS
 SUBMITTED ARE PRINTED COPIES. PRINTED COPIES ARE NOT
 CONSIDERED SIGNED AND SEALED. SEE SEC. 61G15-23.004 FAC
 FOR PROCEDURES FOR DIGITALLY SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 DRAWINGS NEED TO BE UPLOADED AND HAVE DIGITAL
 SIGNATURE. PLEASE CONTACT THE LIBRARIANS FOR DIGITAL
 SUBMITTAL.
  
  LAURA ELIZABETH MARCHANT
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6658
  E-MAIL: [email protected]
  
  OR
  
  
  CAROLINE PUELL
  PLANS REVIEW LIBRARIAN
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  PHONE: 805-6700 EXT: 6659
  E-MAIL: [email protected]
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By fmittner Date 2019-09-20 Time 14:20 Rev Time 0.00
Received By fmittner Date 2019-09-20 Time 14:20 Sent To ENG
Notes
2019-09-20 14:20:54FOUNTAIN/POOL FEATURES SUBJECT TO HPB CLASS B AMENDMENT
 APPROVAL

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-27 Cont ID  
Sent By fmittner Date 2019-08-27 Time 11:13 Rev Time 0.00
Received By fmittner Date 2019-08-27 Time 11:13 Sent To ENG
Notes
***NONE***