Plan Review Details - Permit 19080775
Plan Review Stops For Permit 19080775
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-17 Cont ID  
Sent By dbattles Date 2019-10-17 Time 15:40 Rev Time 0.00
Received By dbattles Date 2019-10-17 Time 14:09 Sent To  
Notes
2019-10-17 15:47:15PROVISOS:
 DEFERRED SUBMITTALS - ROOF TRUSS SHOP DWGS TO INSPECTOR
 PRIOR TO INSTALLATION.
 PROVIDE ROOFING (TILE) ATTACHMENT WITH ROOFING SUB
 PERMIT
 SEPARATE PERMITS REQUIRED FOR-
 DRIVEWAY
 FENCING
 SUBMIT PRODUCT APPROVAL FOR GARAGE DOOR
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-09-06 Time 16:05 Rev Time 0.00
Received By dbattles Date 2019-09-06 Time 07:52 Sent To  
Notes
2019-09-06 16:06:04BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19080775
 REVIEWED: SEPTEMBER 6, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.2(7)FIGURE FBC[R]PROVIDE WIND DIAGRAM THAT
 MATCHES THE ROOF CONDITION OF THIS HOUSE.
  
 2) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 3) [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE
 DRAINAGE PLAN. SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET. EXCEPTION: WHERE LOT LINES,
 WALLS, SLOPES OR OTHER PHYSICAL BARRIERS PROHIBIT 6
 INCHES OF FALL WITHIN 10 FEET (3048 MM), DRAINS OR
 SWALES SHALL BE CONSTRUCTED TO ENSURE DRAINAGE AWAY
 FROM THE STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET
 OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
 -
  
 4) 403.1.7.3 FBC[R] FOUNDATION ELEVATION. ON GRADED
 SITES, THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND
 ABOVE THE ELEVATION OF THE STREET GUTTER AT POINT OF
 DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A
 MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE
 ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE
 BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT
 REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY
 FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE
 SITE.
  
 5) 703.4 FBC[R] PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMENTS OF R703.4
  
 6) 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 7) INDICATE THE ROOF TILE ATTACHMENT METHOD THAT WILL
 BE USED BY MARKING THE APPROPRIATE INFORMATION ON THE
 PRODUCT APPROVAL. FBC 107.2.1 IF AN ADHESIVE WILL BE
 USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC 107.3.4
 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE PRODUCT
 APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT WILL MEET
 WINDLOADS.
  
 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 SLIDING GLASS DOOR, ARCH WINDOWS AND MULL BETWEEN, OR
 INDICATE THAT YOU WOULD LIKE IT DEFERRED.
  
 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 TILE ROOFING ADHESIVE, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERRED.
  
 PROVISOS:
 DEFERRED SUBMITTALS - ROOF TRUSS SHOP DWGS TO INSPECTOR
 PRIOR TO INSTALLATION.
 PROVIDE ROOFING (TILE) ATTACHMENT OR INDICATE THAT IT
 WILL BE DEFERRED UNTIL ROOFING SUB PERMIT IS APPLIED
 FOR.
 SEPARATE PERMITS REQUIRED FOR-
 DRIVEWAY
 FENCING
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - PROVISOS WILL BE ADDED TO THE PLANS AT FINAL
 STAMPING.
  
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-18 Cont ID  
Sent By jpearson Date 2019-10-18 Time 13:47 Rev Time 0.00
Received By jpearson Date 2019-10-18 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By jpearson Date 2019-09-09 Time 15:48 Rev Time 0.00
Received By jpearson Date 2019-09-09 Time 13:02 Sent To  
Notes
2019-09-09 14:37:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEED TO MAIN HOUSE PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 2. PROVIDE GROUNDING ELECTRODE SYSTEM FOR MAIN HOUSE AS
 REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED BY A
 FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE MAIN HOUSE PANEL. NEC
 225.31, 225.32
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 5. AFCI PROTECTION SHOWN IN NOTE 18 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 6. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 8. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 9. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-08-26 Cont ID  
Sent By lcrespo Date 2019-08-26 Time 16:56 Rev Time 0.00
Received By lcrespo Date 2019-08-26 Time 16:56 Sent To  
Notes
2019-08-26 16:56:38GAS PERMIT AND REVIEW UNDER 19081201

Review Stop HIST HISTORICAL
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-10-10 Time   Rev Time 0.00
Received By aborngra Date 2019-10-10 Time 11:19 Sent To PC
Notes
2019-10-10 11:19:55THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. A SEPARATE PERMIT IS REQUIRED FOR: FENCE/WALL,
 AWNINGS, GENERATOR, MECHANICAL/AC/POOL EQUIPMENT,
 IRRIGATION, LANDSCAPE, AND DRIVEWAY.
 2. THIS PERMIT DOES NOT APPROVE ITEMS THAT HAVE BEEN
 DEFERRED SUCH AS THE GARAGE DOOR AND ROOFING MATERIAL.
 3. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 4. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL OGEE
 DIMENSIONAL MUNTINS.
 5. ALL WINDOWS FRAMES SHALL BE WHITE OR BRONZE IN
 COLOR.
 6. ALL WINDOWS SHALL BE INSET WITHIN THE WINDOW FRAME
 OPENING. A FLUSH INSTALLATION WITH EXTERIOR WALL IS
 PROHIBITED.
 7. THE APPLICANT SHALL CONFIRM WITH HISTORIC
 PRESERVATION PRIOR TO PURCHASING AND INSTALLING FRONT
 DOOR AND SIDELITES.
 8. A LANDSCAPING PERMIT WILL BE SUBMITTED AND COMPLY
 WITH THE LANDSCAPING REQUIREMENTS FOR THE CITY OF WEST
 PALM BEACH. (CONDITIONAL APPROVAL FORM IS ATTACHED TO
 EACH PLAN)
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By aborngra Date 2019-08-19 Time 11:04 Rev Time 0.00
Received By aborngra Date 2019-08-16 Time 12:10 Sent To PC
Notes
2019-08-19 11:04:31THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. A LANDSCAPING PERMIT SHALL BE SUBMITTED PRIOR TO
 RECEIVING APPROVAL OF THIS REVIEW. ILLUSTRATE
 COMPLIANCE WITH A MINIMUM OF 75% OF THE FRONT YARD AREA
 SHALL BE LIVING PLANT MATERIAL.
 2. A SEPARATE PERMIT IS REQUIRED FOR: FENCE/WALL,
 AWNINGS, SIGNS, PARKING LOT, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE,
 IRRIGATION, LANDSCAPE, AND DRIVEWAY. PLEASE CONFIRM
 THAT THIS IS UNDERSTOOD.
 3. PROVIDE A PRODUCT APPROVAL FOR THE GARAGE DOOR TO BE
 USED.
 4. THE PLANS SHOW A BARREL TILE TO BE USED. A PRODUCT
 APPROVAL FOR S-TILE WAS SUBMITTED WITH THE PERMIT.
 REVISE AND INCLUDE COLOR OF THE TILE TO BE USED.
 5. THE PLANS ILLUSTRATE A SLIDING GLASS DOOR IN THE
 REAR. A PRODUCT APPROVAL WAS NOT SUBMITTED WITH THE
 PERMIT. PLEASE INCLUDE.
  
 THE FOLLOWING ARE PROPOSED CONDITIONS OF APPROVAL,
 ADDITIONAL CONDITIONS MAY BE ADDED AFTER RESUBMITTAL.
 PLEASE CONFIRM THAT THESE CONDITIONS WILL BE COMPLIED
 WITH.
  
 A. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 B. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL OGEE
 DIMENSIONAL MUNTINS.
 C. ALL WINDOW FRAMES SHALL BE WHITE OR BRONZE IN COLOR.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-10-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-04 Time 14:55 Sent To  
Notes
2019-10-07 14:55:12R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-13 Cont ID  
Sent By hmoser Date 2019-09-13 Time 10:55 Rev Time 0.00
Received By hmoser Date 2019-08-14 Time 13:07 Sent To  
Notes
2019-09-13 09:32:21TO HM DESK
  
  
2019-08-15 13:07:57R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By dbattles Date 2019-10-24 Time 08:16 Rev Time 0.00
Received By dbattles Date 2019-10-24 Time 08:16 Sent To  
Notes
2019-10-24 08:17:11OK-STAMP ON PLANS
 MU-2019-032911-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-09-06 Time 13:17 Rev Time 0.00
Received By dbattles Date 2019-09-06 Time 07:52 Sent To  
Notes
2019-09-06 13:17:55109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-09-13 Cont ID  
Sent By hmoser Date 2019-09-13 Time 10:55 Rev Time 0.00
Received By hmoser Date 2019-09-13 Time 10:55 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-30 Cont ID  
Sent By lcrespo Date 2019-08-30 Time 13:27 Rev Time 0.00
Received By lcrespo Date 2019-08-29 Time 07:30 Sent To  
Notes
2019-08-29 16:10:1208/29/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-10-17 Cont ID  
Sent By dbattles Date 2019-10-17 Time 15:45 Rev Time 0.00
Received By dbattles Date 2019-10-17 Time 15:40 Sent To  
Notes
2019-10-24 08:17:47ROOFING PRODUCT APPROVAL DUE WITH SUB PERMIT
 APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-09-06 Time 16:04 Rev Time 0.00
Received By dbattles Date 2019-09-06 Time 07:52 Sent To  
Notes
2019-09-06 16:05:04SEE BUILDING COMMENT #9

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By aborngra Date 2019-10-11 Time 08:26 Rev Time 0.00
Received By aborngra Date 2019-10-09 Time 16:03 Sent To PC
Notes
2019-10-10 11:20:07THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. A SEPARATE PERMIT IS REQUIRED FOR: FENCE/WALL,
 AWNINGS, GENERATOR, MECHANICAL/AC/POOL EQUIPMENT,
 IRRIGATION, LANDSCAPE, AND DRIVEWAY.
 2. THIS PERMIT DOES NOT APPROVE ITEMS THAT HAVE BEEN
 DEFERRED SUCH AS THE GARAGE DOOR AND ROOFING MATERIAL.
 3. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 4. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL OGEE
 DIMENSIONAL MUNTINS.
 5. ALL WINDOWS FRAMES SHALL BE WHITE OR BRONZE IN
 COLOR.
 6. ALL WINDOWS SHALL BE INSET WITHIN THE WINDOW FRAME
 OPENING. A FLUSH INSTALLATION WITH EXTERIOR WALL IS
 PROHIBITED.
 7. THE APPLICANT SHALL CONFIRM WITH HISTORIC
 PRESERVATION PRIOR TO PURCHASING AND INSTALLING FRONT
 DOOR AND SIDELITES.
 8. A LANDSCAPING PERMIT WILL BE SUBMITTED AND COMPLY
 WITH THE LANDSCAPING REQUIREMENTS FOR THE CITY OF WEST
 PALM BEACH. (CONDITIONAL APPROVAL FORM IS ATTACHED TO
 EACH PLAN)
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By aborngra Date 2019-08-19 Time 11:04 Rev Time 0.00
Received By aborngra Date 2019-08-19 Time 11:04 Sent To PC
Notes
2019-08-19 11:04:48THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. A LANDSCAPING PERMIT SHALL BE SUBMITTED PRIOR TO
 RECEIVING APPROVAL OF THIS REVIEW. ILLUSTRATE
 COMPLIANCE WITH A MINIMUM OF 75% OF THE FRONT YARD AREA
 SHALL BE LIVING PLANT MATERIAL.
 2. A SEPARATE PERMIT IS REQUIRED FOR: FENCE/WALL,
 AWNINGS, SIGNS, PARKING LOT, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE,
 IRRIGATION, LANDSCAPE, AND DRIVEWAY. PLEASE CONFIRM
 THAT THIS IS UNDERSTOOD.
 3. PROVIDE A PRODUCT APPROVAL FOR THE GARAGE DOOR TO BE
 USED.
 4. THE PLANS SHOW A BARREL TILE TO BE USED. A PRODUCT
 APPROVAL FOR S-TILE WAS SUBMITTED WITH THE PERMIT.
 REVISE AND INCLUDE COLOR OF THE TILE TO BE USED.
 5. THE PLANS ILLUSTRATE A SLIDING GLASS DOOR IN THE
 REAR. A PRODUCT APPROVAL WAS NOT SUBMITTED WITH THE
 PERMIT. PLEASE INCLUDE.
  
 THE FOLLOWING ARE PROPOSED CONDITIONS OF APPROVAL,
 ADDITIONAL CONDITIONS MAY BE ADDED AFTER RESUBMITTAL.
 PLEASE CONFIRM THAT THESE CONDITIONS WILL BE COMPLIED
 WITH.
  
 A. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
 B. ALL WINDOWS AND DOORS SHALL HAVE EXTERNAL OGEE
 DIMENSIONAL MUNTINS.
 C. ALL WINDOW FRAMES SHALL BE WHITE OR BRONZE IN COLOR.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  