Plan Review Details - Permit 19080683
Plan Review Stops For Permit 19080683
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-16 Cont ID  
Sent By dbattles Date 2020-01-16 Time 14:27 Rev Time 0.00
Received By dbattles Date 2020-01-16 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-12-05 Cont ID  
Sent By dbattles Date 2019-12-05 Time 12:29 Rev Time 0.00
Received By dbattles Date 2019-12-04 Time 15:07 Sent To  
Notes
2019-12-05 12:29:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19080683
 REVIEWED: DECEMBER 5, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 107.3.5 FBC[AMENDED]PLEASE PROVIDE A PLAN VIEW TO
 SHOW THE SIZE OF THE ROOM, SIZE OF GENERATOR AND SPACE
 PROVIDED AROUND THE UNIT. ALSO ACCOUNT FOR ACCESS DOOR
 SWINGS TO ALLOW TO FULLY OPEN.
 2) PROVIDE DETAILS OF HOW THE UNIT CONNECTS TO FLOOR
 AND HOW PENETRATIONS FOR AIR DUCTS AND EXHAUST MEET
 CODE REQUIRMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-18 Cont ID  
Sent By shill Date 2020-01-18 Time 11:20 Rev Time 0.00
Received By jleahy Date 2020-01-21 Time 09:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-01-16 Cont ID  
Sent By jpearson Date 2020-01-16 Time 07:23 Rev Time 0.00
Received By jpearson Date 2020-01-16 Time 07:23 Sent To  
Notes
2020-01-16 07:23:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED, VALUE ACCEPTED.
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481 (THE COMMENT RESPONSE
 REFERS TO THE ORIGINAL PERMIT 17110874. DURING THE
 FIRST PLAN REVIEW, THE VERY FIRST COMMENT NOTED STATED
 THE FOLLOWING: "FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1" A NOTE WAS ADDED TO THE PLAN TO THIS
 EFFECT. PLAN REVIEW FOR THE GENERATOR WAS NOT DONE ON
 THE ORIGINAL REVIEW AND MUST BE COMPLETED NOW.
 ADDITIONALLY, AS A MATTER OF PUBLIC RECORD, PLANS MUST
 BE INCLUDED. PROVIDE ALL PLAN SHEETS THAT RELATE TO
 GENERATOR INSTALLATION FOR REVIEW. THE SPEC SHEET FOR
 THE GENERATOR IS NOT CONSIDERED A PLAN.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-13 Cont ID  
Sent By jleahy Date 2019-11-13 Time 15:15 Rev Time 0.00
Received By jleahy Date 2019-11-13 Time 15:15 Sent To I
Notes
2019-11-13 15:18:26FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR A 250 KW GENSET IS LOW, PLEASE SUBMIT A
 VALUE WHICH WILL REFLECT THE ACTUAL VALUE OF THE
 GENERATOR INSTALLATION.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) NO ELECTRICAL DIAGRAMS HAVE BEEN SUBMITTED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By pleduc Date 2020-01-17 Time   Rev Time 0.00
Received By pleduc Date 2020-01-17 Time 08:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-11-06 Cont ID  
Sent By pleduc Date 2019-11-06 Time   Rev Time 0.00
Received By pleduc Date 2019-11-06 Time 09:10 Sent To  
Notes
2019-11-06 16:09:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE GENERATOR EXHAUST
 SYSTEM.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH ALL
 APPLICABLE NFPA 110 AND 37.
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2) THERE ARE NO INDICATIONS OF VENTILATION AIRFLOW.
  
 PER NFPA 110
  
 7.7 HEATING, COOLING, AND VENTILATING.
 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION
 AIRFLOW
 SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE
 IN THE
 EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE
 MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS
 MANUFACTURER.
  
 7.7.3 VENTILATION AIR SUPPLY SHALL BE FROM OUTDOORS OR
 FROM A
 SOURCE OUTSIDE THE BUILDING BY AN EXTERIOR WALL OPENING
 OR
 FROM A SOURCE OUTSIDE THE BUILDING BY A 2-HOUR
 FIRE-RATED AIR
 TRANSFER SYSTEM.
 7.7.4 VENTILATION AIR SHALL BE PROVIDED TO SUPPLY AND
 DISCHARGE
 COOLING AIR FOR RADIATOR COOLING OF THE EPS WHEN
 RUNNING
 AT RATED LOAD.
 7.7.4.1 VENTILATION AIR SUPPLY AND DISCHARGE FOR
 RADIATORCOOLED
 EPS SHALL HAVE A MAXIMUM STATIC RESTRICTION OF 125 PA
 (0.5 IN. OF WATER COLUMN) IN THE DISCHARGE DUCT AT THE
 RADIATOR
 OUTLET.
 7.7.4.2 RADIATOR AIR DISCHARGE SHALL BE DUCTED OUTDOORS
 OR TO
 AN EXTERIOR OPENING BY A 2-HOUR RATED AIR TRANSFER
 SYSTEM.
  
 PLEASE PROVIDE DETAILS
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-01-15 Cont ID  
Sent By gjohnson Date 2020-01-15 Time 18:44 Rev Time 0.00
Received By gjohnson Date 2020-01-15 Time 14:38 Sent To  
Notes
2020-01-15 18:46:40APPROVED UNDER MASTER 17110874
  
 GAS PROVISO UNDER MASTER:
  
 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR
 ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW
 WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS
 NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE
 MANUFACTURE WILL BE REQUIRED STATING THAT THIS
 CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION
 PROPERLY. PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DOCUMENT A SIGNED AND SEALED LETTER FROM THE
 MANUFACTURES AND THE ENGINEER. STATING THAT THIS PIPING
 LAYOUT WILL ALLOW BOTH THE GENERATOR AND THE BOILERS TO
 FUNCTION PROPERLY SIMULTANEOUSLY.
  
 PREVIOUS COMMENT NOT COMPLIED 5. SHT. P-407 PLEASE SHOW
 ON THE PLAN THE MIN DISTANCE BETWEEN THE INTAKE AND
 EXHAUST. . PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DIMENSIONS ON THE PLAN.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-11-12 Cont ID  
Sent By abelisle Date 2019-11-12 Time 06:49 Rev Time 0.00
Received By abelisle Date 2019-11-12 Time 06:45 Sent To  
Notes
2019-11-12 06:49:1611/12/2019 2ND GAS REVIEW**DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1- THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8,
 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 2-GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 3-WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 4- THE INFORMATION PROVIDED STATES THAT THE
 MANUFACTURE" OFFERS" A UL 2200. PROVIDE A COPY OF THE
 UL 2200 LISTING FOR THE GENERATOR
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By abelisle Date 2019-09-09 Time 06:49 Rev Time 0.00
Received By abelisle Date 2019-09-05 Time 06:23 Sent To  
Notes
2019-09-09 06:50:219/9/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS NOTE -
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1-SUBMIT 2 COPIES OF THE GENERATORS MANUFACTURES
 INSTALLATION WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2-PROVIDE COPY OF THE UL LISTING FOR THE GENERATOR, IT
 SHALL MEET UL 2200
  
 3-THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8,
 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 4-GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 5-WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-18 Cont ID  
Sent By shill Date 2020-01-18 Time 11:20 Rev Time 0.00
Received By shill Date 2020-01-14 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-13 Cont ID  
Sent By shill Date 2019-12-13 Time 07:22 Rev Time 0.00
Received By shill Date 2019-10-30 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-11 Cont ID  
Sent By lmarchan Date 2019-09-11 Time 09:37 Rev Time 0.00
Received By lmarchan Date 2019-08-14 Time 12:44 Sent To  
Notes
2019-08-30 11:55:15TO LMARCHAN
2019-08-15 12:44:55ROUTED TO ZONING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-01-17 Cont ID  
Sent By ccole Date 2020-01-17 Time 12:20 Rev Time 0.00
Received By ccole Date 2020-01-17 Time 10:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-01-16 Cont ID  
Sent By ccole Date 2020-01-16 Time 11:51 Rev Time 0.00
Received By ccole Date 2020-01-16 Time 08:42 Sent To  
Notes
2020-01-16 12:15:382ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19080683
 1/16/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 110-2013
 NFPA 37-2015
 NFPA 54-2015
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101: THE GENERATOR SHALL BE INSTALLED AT A
 MINIMUM OF 5' FROM THE EXTERIOR DOOR OPENING. PLEASE
 SHOW THE CLEARANCE DISTANCE ON THE PLAN- SECTION 4.1.4
 NFPA 37.
  
 2) SHEET P-102 APPROVED UNDER THE MAIN BUILDING PERMIT
 #17110874 SHOWS A FLOOR DRAIN IN THE CENTER OF THE
 OPEN-ROOFED GENERATOR ENCLOSURE. VERIFY THAT THERE IS
 ADEQUATE SPACE BELOW THE GENERATOR FOR WATER TO DRAIN
 INTO THE FIXTURE. PLEASE REVIEW THE ENCLOSURE
 INSTALLATION DETAILS BY ENGINEERING EXPRESS AND
 DESIGNATE WHICH METHOD WILL BE USED. SECTION 107.2.1
 WPB.
  
 3) CONCERNING COMMENT #4D FROM THE 1ST REVIEW PRINTED
 BELOW, THE ENGINEER OF RECORD HAS REQUESTED APPROVAL OF
 THE GENERATOR PERMIT WITH A PROVISO PENDING A LETTER
 FROM FLORIDA PUBLIC UTILITIES. PLEASE NOTE THAT A HOLD
 MAY BE PLACED ON THE CERTIFICATE OF OCCUPANCY UNTIL THE
 DOCUMENT HAS BEEN RECEIVED.
  
 4D) PLEASE REVIEW SECTION 5.1.1 NFPA 110 AND PROVIDE
 DOCUMENTATION THAT VERIFIES THE LOW PROBABILTY OF GAS
 SERVICE INTERUPTION, OR PROVIDE ON-SITE STORAGE OF AN
 ALTERNATE ENERGY SOURCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By ccole Date 2019-12-09 Time 16:02 Rev Time 0.00
Received By ccole Date 2019-12-09 Time 14:39 Sent To  
Notes
2019-12-09 16:09:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080683
 12/9/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 110-2013
 NFPA 37-2015
 NFPA 54-2015
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO FIRE REVIEW COMMENTS DATED 11/6/2019 FOR
 THE EPS (GENERATOR) ROOM ENCLOSURE AND ROOM VENTILATION
 REQUIREMENTS AS LISTED UNDER NFPA 110- 2013 STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS. COMPLY WITH
 THOSE COMMENTS AND THESE ADDITIONAL COMMENTS LISTED
 BELOW.
  
 2) PLEASE PROVIDE AN ENLARGED DRAWING OF THE EPS ROOM
 THAT INDICATES:
 A) FIRE RESISTANCE RATINGS OF THE WALLS AND CEILING-
 SECTION 7.2.1.1 NFPA 110.
 B) HOW THE GENERATOR WILL BE POSITIONED IN THE ROOM
 WITH CLEARANCES. IT APPEARS BY THE SUBMITTED SITE PLAN
 THAT THERE COULD BE DIFFICULTY IN COMPLYING WITH
 SECTION 7.7.4.2 NFPA 110 WHICH REQUIRES THE GENERATOR
 RADIATOR TO BE DUCTED OUTDOORS OR TO AN EXTERIOR
 OPENING BY A 2-HR RATED AIR TRANSFER SYSTEM.
 C) REQUIRED ROOM VENTILATION AND MAKEUP AIR FOR THE
 EXHAUST- SEE FIRE COMMENTS.
 D) GAS AND EXHAUST PIPING LAYOUTS IN THE ROOM.
 E) HOW COMBUSTION AIR WILL BE PROVIDED- SECTION 304 FBC
 FG. PLEASE SHOW THE MEANS AND METHOD, AND PROVIDE
 CALCULATIONS.
  
 3) ENGINE EXHAUST PIPING:
 A) SUBMIT MANUFACTURER'S PRODUCT DATA FOR THE EXHAUST
 PIPING.
 B) PROVIDE AN EXHAUST PIPING DRAWING SHOWING THE PIPING
 RUN, PIPING TYPE AND SIZE, AND EXHAUST DISCHARGE
 LOCATION WITH CLEARANCE DISTANCE MEASUREMENTS FROM THE
 TERMINATION TO MECHANICAL AND OPERABLE AIR INLETS INTO
 THE BUILDING, TO GRADE, AND TO PROPERTY LINES.
 C) PROVIDE A BACK PRESSURE CALCULATION.
  
 4) GAS PIPING:
 A) PROVIDE AN ISOMETRIC DRAWING.
 B) PROVIDE A GAS PIPING LAYOUT DRAWING SHOWING THE
 PIPING RUN FROM THE METER TO THE EPS ROOM.
 C) REFER TO SECTIONS 7.9.6, 7.9.7, & 7.9.9 NFPA 110 AND
 PROVIDE A DETAIL THAT SHOWS THE CORRECT LOCATION FOR
 EPS GAS LINE CONNECTION AND VALVE LABELING AT THE
 UTILTY METER.
 D) PLEASE REVIEW SECTION 5.1.1 NFPA 110 AND PROVIDE
 DOCUMENTATION THAT VERIFIES THE LOW PROBABILTY OF GAS
 SERVICE INTERUPTION, OR PROVIDE ON-SITE STORAGE OF AN
 ALTERNATE ENERGY SOURCE.
  
 5) DESIGN CRITERIA: PROVIDE A CURRENT LIST OF ALL
 APPLICABLE CODES AND STANDARDS USED IN THE DESIGN OF
 THE EPS PROJECT- SECTION 107.2.1 WPB.
  
 6) PLEASE CLARIFY WHY WINDLOAD ENGINEERING BY FRANK
 BERNARDO P.E. HAS BEEN SUBMITTED IF THE GENERATOR IS TO
 BE LOCATED IN AN ENCLOSED ROOM INSIDE THE BUILDING-
 SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-01-15 Cont ID  
Sent By gjohnson Date 2020-01-15 Time 18:46 Rev Time 0.00
Received By gjohnson Date 2020-01-15 Time 14:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-10 Cont ID  
Sent By shill Date 2019-11-12 Time 08:19 Rev Time 0.00
Received By shill Date 2019-11-12 Time 08:19 Sent To  
Notes
2019-12-10 08:20:04SEE GAS REVIEW
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-01-16 Cont ID  
Sent By dbattles Date 2020-01-16 Time 14:27 Rev Time 0.00
Received By dbattles Date 2020-01-16 Time 14:27 Sent To  
Notes
2020-01-16 14:33:07ANY ADDITIONAL SHEETS SUBMITTED WILL NEED DIGITAL
 SIGNATURES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-12-09 Cont ID  
Sent By ccole Date 2019-12-09 Time 16:57 Rev Time 0.00
Received By ccole Date 2019-12-09 Time 16:57 Sent To  
Notes
2019-12-09 17:03:37 
 DIGITAL SIGNATURE REVIEW
 PERMIT #19080863
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SITE PLAN REQUIRES AN ELECTRONIC SEAL AND
 SIGNATURE BY THE ARCHITECT OF RECORD- FL STATUTE
 481.221 AND SECTION 61G-16.005 FLORIDA ADMINISTRATIVE
 CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By aaponte Date 2019-12-10 Time 09:12 Rev Time 0.00
Received By aaponte Date 2019-12-10 Time 09:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By aaponte Date 2019-08-30 Time 11:54 Rev Time 0.00
Received By aaponte Date 2019-08-30 Time 11:54 Sent To B
Notes
2019-08-30 11:54:571. PLEASE PROVIDE A SITE PLAN INDICATING THE LOCATION
 OF THE GENERATOR.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.